- Home
- ACB Accessories & Releases
- Schneider Electric LV454444 MasterPact MTZ External Power Supply 24 V DC Air Circuit Breaker Accessory Schneider Electric LV454444 MasterPact MTZ External Power Supply 24 V DC Air Circuit Breaker Accessory
Schneider Electric LV454444 MasterPact MTZ External Power Supply 24 V DC Air Circuit Breaker Accessory
Schneider Electric LV454444 MasterPact MTZ External Power Supply 24 V DC Air Circuit Breaker Accessory
Get Quote
- Description
The Schneider Electric LV454444 is a regulated switch-mode external power supply that converts 200-240 V AC into a stable 24 V DC output at 1 A, built to feed the MicroLogic control and trip units on MasterPact MTZ, NT, NW, ComPact NSX and PowerPact breakers whenever an independent 24 V DC source is needed for communication.
Technical Specifications
| Reference | LV454444 |
| Brand | Schneider Electric |
| GTIN | 00785901810926 |
| Product Type | External power supply module |
| Device Application | Power supply for MicroLogic trip units |
| Range Compatibility | MasterPact MTZ, NT, NW; ComPact NSX, NSX DC; PowerPact H, J, L, P, R |
| [Us] Rated Supply Voltage | 200-240 V AC 50/60 Hz, +10% / -15% |
| Input Voltage Limits | 170-264 V AC, 47.5-63 Hz |
| Output Voltage | 24 V DC +/-5% |
| Output Current | 1 A |
| Rated Power | 24 W |
| Inrush Current | 20 A for 2 ms |
| Efficiency | 85% |
| Power Dissipation | 4.2 W |
| Overvoltage Category | IV per IEC 62477-1, III per UL 61010-1 |
| IP Degree of Protection | IP4X front face, IP2X terminals, IP3X housing |
| Mounting Support | 35 x 7.5 mm symmetrical DIN rail |
| Dimensions (H x W x D) | 90 x 108 x 67.5 mm |
Certifications & Standards
- CE
- UL 61010-1
- IEC 62477-1
Selection Notes
LV454444 is the single-output 1 A / 24 W version of this external power supply — size the DIN-rail branch around that 24 W ceiling when a MicroLogic unit also has to drive communication modules on the same circuit. The regulated 24 V DC output and -25...70 degC operating range suit switchboard enclosures where ambient heating from adjacent breakers is a factor. Choose this module only when the panel design already runs a 200-240 V AC feed to the compartment; the MicroLogic unit otherwise takes its power from the breaker itself.