How to Get Air Circuit Breaker Spare Parts and Accessories Fast
Source ACB accessories fast with verified OEM parts, lead times, authenticity checks, and stocking strategy to cut downtime on Emax 2 frames. Shop at...
The Schneider Electric LV947383 is an MN instantaneous undervoltage release for fixed MasterPacT MTZ1, MTZ2, and MTZ3 Active circuit breakers fitted with the MicroLogic Active control unit, supplied for 200-250 V AC 50/60 Hz or 200-250 V DC. It opens the breaker once the supervised voltage drops to 0.35-0.7 Un.
Specify the LV947383 instead of the 100-130 V LV947382 when the breaker's supervised control circuit runs at 200-250 V AC or DC; both are built for the MasterPacT Active platform with the MicroLogic Active control unit rather than the earlier MasterPact MTZ range. It fits fixed breakers only, and response time is unchanged from the rest of the MN family at 45 ms on MTZ1 and 95 ms on MTZ2/MTZ3, so safety-interlock timing calculations carry over directly. It ships one piece per package with no bulk packaging options listed.
| Maximum response time | 45 ms on opening for MasterPact MTZ1, 95 ms on opening for MasterPact MTZ2, 95 ms on opening for MasterPact MTZ3 |
|---|---|
| Range | MasterPacT |
| Device short name | MN |
| Product or component type | Undervoltage release |
| Device application | Safety |
| Range compatibility | MasterPacT MTZ1 Active circuit breaker, MasterPacT MTZ2 Active circuit breaker, MasterPacT MTZ3 Active circuit breaker |
| Voltage release type | Instantaneous |
| Control type | Standard |
|---|---|
| [Un] voltage power supply | 200...250 V AC 50/60 Hz, 200...250 V DC |
| Threshold tripping voltage | 0.35...0.7 Un opening, 0.85 Un closing |
| Holding power consumption | 4.5 W |
| Circuit breaker mounting mode | Fixed |
| Warranty (in months) | 18 |
|---|
| Part number | LV947383 |
|---|---|
| Type designation | MN |
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 2 cm |
| Package 1 Width | 1 cm |
| Package 1 Length | 2 cm |
| Package 1 Weight | 10 g |
| Shipping weight | 0.01 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated operational voltage of MN is 200–250 V AC.
The tariff (HS) code on file for MN is 853890.
MN ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
Source ACB accessories fast with verified OEM parts, lead times, authenticity checks, and stocking strategy to cut downtime on Emax 2 frames. Shop at...
Compare 1600-2500A ACB platforms: ABB Emax 2, Schneider MTZ2, Siemens 3WL2 on breaking capacity, trip units, endurance and lifecycle cost. Shop at Stoklink.
ABB Emax 2 air circuit breaker selection, sizing, trip units, selectivity, and maintenance guide for 630 to 6300 A LV switchgear engineers. Shop at...