- Part number
- A9MEM1580
Description
About the A9MEM1580
About the A9MEM1580
The Schneider Electric A9MEM1580 PowerTag Energy F160 is a 3P or 3P+N wireless energy sensor rated 160 A maximum current (25 A base current), mounted top or bottom via a removable spring terminal block on a 27 mm pitch. It covers Acti9 C120/NG125, ComPacT NSXm/INS, TeSys GV4, iSW/iSW-NA/iID and PowerPact B devices, reporting active, reactive and apparent energy and power, current, voltage and power factor to IEC 61557-12 over a 2.4 GHz radio link.
Certifications & Standards
- UL listed
- CE
- DNV Marine
- IEC 61557-12
- IEC 61010-1
- IEC 61010-2-030
- IEC 61326-1
- ETSI EN 300 328
- ETSI EN 301 489-1
Selection Notes
Step up from the 63 A Monoconnect/Flex/PhaseNeutral sensors to the A9MEM1580 once the feeder exceeds 63 A, up to 160 A, on C120, NG125, NSXm, GV4 or PowerPact B devices -- it also adds apparent and reactive energy/power readings (Class 2) beyond the active-only measurement of the smaller PowerTags, and its overvoltage/measurement Category IV rating suits distribution-level installation points rather than only final circuits.
Specification
Full specification
Main 21
| Range of product | PowerLogic |
|---|---|
| Product name | PowerTag F160 |
| Product or component type | Energy sensor |
| Poles | 3P, 3P + N |
| Maximum current [Imax] | 160 A |
| [Ib] Basic current | 25 A |
| Starting current | 100 mA |
| Saturation current | 320 A |
| Product specific application | Energy management, Overload alarm, Power factor, Load monitoring, Circuit monitoring |
| Concentrator compatibility | EcoStruxure Panel Server Entry, EcoStruxure Panel Server Universal, EcoStruxure Panel Server Advanced, Harmony Hub, Acti9 PowerTag Link, Acti9 PowerTag Link HD |
| Range compatibility | Acti9 Acti9 C120, Acti9 Acti9 NG125, ComPacT ComPact NSXm, TeSys TeSys GV4, ComPacT ComPacT INS, Acti9 Acti9 iSW, Acti9 Acti9 iSW-NA, Acti9 Acti9 iID, PowerPact PowerPact B |
| Type of measurement | Active and reactive energy, Apparent energy, Active and reactive power, Apparent power, Current, Voltage, Power factor, Internal temperature, Frequency |
| Accuracy class | Class 1 active energy conforming to IEC 61557-12, Class 2 reactive energy conforming to IEC 61557-12, Class 2 apparent energy conforming to IEC 61557-12, Class 1 active power conforming to IEC 61557-12, Class 2 reactive power conforming to IEC 61557-12, Class 2 apparent power conforming to IEC 61557-12, Class 1 current conforming to IEC 61557-12, Class 0.5 voltage conforming to IEC 61557-12, Class 1 power factor conforming to IEC 61557-12, Class 0.5 frequency conforming to IEC 61557-12 |
| Metering type | Active energy E -a- IN/OUT 0...281 x 10exp(9) kWh at total per phase, Active energy E -a- IN/OUT 0...281 x 10exp(9) kWh at partial per phase, Active energy E -a- IN/OUT 0...281 x 10exp(9) kWh at 3-phase total, Active energy E -a- IN/OUT 0...281 x 10exp(9) kWh at 3-phase partial, Reactive energy E -rA- IN/OUT 0...281 x 10exp(9) kVARh at total per phase, Reactive energy E -rA- IN/OUT 0...281 x 10exp(9) kVARh at partial per phase, Reactive energy E -rA- IN/OUT 0...281 x 10exp(9) kVARh at 3-phase total, Reactive energy E -rA- IN/OUT 0...281 x 10exp(9) kVARh at 3-phase partial, Apparent energy E -apA- 0...281 x 10exp(9) kVAh at total per phase, Apparent energy E -apA- 0...281 x 10exp(9) kVAh at partial per phase, Apparent energy E -apA- 0...281 x 10exp(9) kVAh at 3-phase total, Apparent energy E -apA- 0...281 x 10exp(9) kVAh at 3-phase partial, Active power P, P1, P2, P3, Reactive power Q, Q1, Q2, Q3, Apparent power S, S1, S2, S3, Current I1, I2, I3, Calculated neutral current, Voltage U12, U23, U31, Voltage V1N, V2N, V3N, Frequency 45...65 Hz, Power factor at per phase, Power factor at total |
| Mounting location | Top or bottom |
| Mounting support | Cables |
| Connection pitch | 27 mm |
| Product destination | Switchboard |
| Event management | Voltage loss with measured current at voltage loss |
| Transmission support medium | Radio frequency 2.4…2.4835 GHz conforming to IEEE 802.15.4 |
| Emission power | 10 mW |
Complementary 16
| Form factor | Flex |
|---|---|
| Mounting mode | Free mounting |
| Electrical connection (voltage sensing & power supply) | Removable spring terminal block |
| Cable cross section | 1 rigid cable 0.2…1.5 mm² without cable end, 1 stranded cable 0.2…2.5 mm² without cable end, 1 stranded cable 0.25…1.5 mm² with cable end |
| Wire stripping length | 11 mm |
| max power cable diameter | 17 mm |
| supply voltage | 100...277 V AC, +/- 20 %, phase to neutral, 173...480 V AC, +/- 20 %, phase to phase |
| Network frequency | 50 Hz, 60 Hz |
| Maximum power consumption | 3 VA |
| Standards | IEC 61557-12, IEC 61010-1, ETSI EN 301 489-1, IEC 61010-2-030, IEC 61326-1, ETSI EN 300 328 |
| Product certifications | UL listed, IEC, DNV Marine |
| Height | 39 mm |
| Width | 91 mm |
| Depth | 62 mm |
| Net weight | 80 g |
| Colour | White (RAL 9003) |
Environment 14
| Quality labels | CE |
|---|---|
| Directives | 2014/53/EU - radio equipment directive |
| Operating altitude | 0...2000 m |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Overvoltage category | IV conforming to IEC 61010-1 |
| Measurement category | Category IV conforming to IEC 61010-2-030 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| IK degree of protection | IK05 |
| Pollution degree | 3 |
| Relative humidity | 0…95 % at 55 °C conforming to IEC 60721-3-3 |
| Vibration resistance | 3M4 conforming to IEC 60721-3-3 |
| Electromagnetic compatibility | Industrial electromagnetic environment conforming to IEC 61326-1, Radiated EMC conforming to ETSI EN 301 489-17, Electromagnetic emission conforming to IEC 62311 |
| environmental characteristics | Indoor use |
Show all 74 specifications ↓ Show less ↑23 more values in Identification, Contractual warranty, Logistics.
Identification 6
| Part number | A9MEM1580 |
|---|---|
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
Contractual warranty 1
| Warranty (in months) | 18 |
|---|
Logistics 16
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.900 cm |
| Package 1 Width | 11.400 cm |
| Package 1 Length | 8.400 cm |
| Package 1 Weight | 135.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 24 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 3.624 kg |
| Shipping weight | 0.08 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
Documents
Documents for A9MEM1580
No documents are on file for this part yet.
Ask us for the datasheet
Certifications
Certifications and standards
- UL
- Marine
- IEC 61557-12
- IEC 61010-1
- ETSI EN 301 489-1
- IEC 61010-2-030
- IEC 61326-1
- ETSI EN 300 328
Quick answers
Questions about the A9MEM1580
What is the rated current of A9MEM1580?
The rated current of A9MEM1580 is 160 A.
Which supply voltage is A9MEM1580 rated for?
The rated operational voltage of A9MEM1580 is 100–277 V AC.
What is the HS code of A9MEM1580 for customs?
The tariff (HS) code on file for A9MEM1580 is 902830.
Where does A9MEM1580 ship from, and how fast?
A9MEM1580 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
Reviews
Customer reviews
Series
Schneider Electric PowerLogic
- Brand
- Schneider Electric
- Series
- PowerLogic