Contactors for Data Center PDU and UPS Systems: Selection Guide
AC-1 and AC-6a contactors for data center PDU and UPS systems: sizing, harmonic derating, coil selection, and endurance guidance for engineers. Shop at Stoklink.
The Siemens 3RT2045-1NB30 is a 3-pole SIRIUS 3RT2 contactor rated 80 A (AC-3) / 37 kW at 400 V, 60 hp at 480 V, with a 20–33 V AC/DC coil and 1 NO + 1 NC auxiliary contacts.
The Siemens 3RT2045-1NB30 is a contactor from the SENTRON/SIRIUS 3RT2 series. Power contactor, AC-3e/AC-3, 80 A, 37 kW / 400 V, 3-pole, 20-33 V AC/DC, 50/60 Hz, with integrated varistor, auxiliary contacts: 1 NO + 1 NC, screw terminal, size: S3. Supplied by Stoklink for industrial and commercial low-voltage applications.
The Siemens 3RT2045-1NB30 is used in industrial control panels, distribution boards and automation systems. As part of the Siemens 3RT2 range it integrates with compatible SENTRON/SIRIUS components for a coordinated low-voltage installation. Genuine Siemens product supplied by Stoklink with fast dispatch from Türkiye.
| Series | SIRIUS 3RT2 |
|---|---|
| Contactor size / frame | S3 |
| Number of poles | 3 |
| Main contact configuration | 3 NO |
| Rated operational current Ie, AC-3, 400 V | 80 A |
|---|---|
| Rated motor power, AC-3, 400 V | 37 kW |
| Rated operational current, AC-1 (60 °C) | 105 A |
| Rated operational current, AC-1 (40 °C) | 125 A |
| Rated operational current, AC-4, 400 V | 66 A |
| Max. rated operational voltage Ue | 1000 V |
| Rated insulation voltage Ui | 1000 V |
| Rated impulse withstand voltage Uimp | 8 kV |
| Rated control supply voltage Uc | 20–33 V |
|---|---|
| Coil type | AC-DC |
| Coil frequency | 50/60 Hz |
| Coil technology | Conventional, surge suppressor with varistor |
| Coil holding power | 1.8 W | VA |
| Part number | 3RT2045-1NB30 |
|---|---|
| Model code | S3 |
| Brand | Siemens |
| Series | SIRIUS 3RT2 |
| Family | Contactors |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4047621024769 |
| ETIM class | EC000066 |
| eCl@ss | 27371003 |
| UPC | 804766405976 |
| UNSPSC | 39121529 |
| Built-in auxiliary contacts, NO | 1 |
|---|---|
| Built-in auxiliary contacts, NC | 1 |
| Auxiliary contacts | 1 NO + 1 NC |
| Mirror contact (IEC 60947-4-1 Annex F) | Yes |
| Main circuit connection | Screw terminal |
|---|---|
| Mounting | 35 mm DIN rail, Panel (screw) mounting |
| Width | 70 mm |
|---|---|
| Height | 140 mm |
| Depth | 152 mm |
| Net weight | 1.764 kg |
| Ambient operating temperature | -25 … 60 °C |
|---|---|
| Degree of protection | IP20 |
| Mechanical durability | 10000000 cycles |
| Max. operating frequency, AC-3 | 1000 cycles/h |
| Motor rating (UL/CSA) | 25 hp @ 200/208 V · 30 hp @ 220/230 V · 60 hp @ 460/480 V · 60 hp @ 575/600 V · 7.5 hp @ 110/120 V (1-ph) · 15 hp @ 230 V (1-ph) |
|---|---|
| Full-load amps @ 480 V | 77 A |
| Certifications | UL, Marine |
|---|
| Package dimensions (L × W × H) | 168 × 78 × 162 mm |
|---|---|
| Shipping weight | 2.264 kg |
| Ships from | Türkiye |
| Dispatch | 18 Nov |
| Stock | In stock |
| product brand name | SIRIUS |
|---|---|
| product designation | Power contactor |
| product extension · function module for communication | No |
| product extension · auxiliary switch | Yes |
| power loss [W] for rated value of the current · at AC in hot operating state | 15.9 W |
| power loss [W] for rated value of the current · without load current share typical | 1.8 W |
| type of calculation of power loss current-dependent | quadratic |
| insulation voltage · of auxiliary circuit with degree of pollution 3 rated value | 690 V |
| surge voltage resistance · of auxiliary circuit rated value | 6 kV |
| maximum permissible voltage for protective separation between coil and main contacts according to EN 60947-1 | 690 V |
| shock resistance at rectangular impulse · at AC | 10.3 g / 5 ms, 6,7 g / 10 ms |
| shock resistance at rectangular impulse · at DC | 6.7 g / 5 ms, 4 g / 10 ms |
| shock resistance with sine pulse · at AC | 16.3 g / 5 ms, 10.5 g / 10 ms |
| shock resistance with sine pulse · at DC | 10.6 g / 5 ms, 6.3 g / 10 ms |
| mechanical service life (operating cycles) · of the contactor with added electronically optimized auxiliary switch block typical | 5 000 000 |
| reference code according to IEC 81346-2 | Q |
| Substance Prohibitance (day/month/year) | 03/01/2017 |
| SVHC substance name | Lead CAS-No. 7439-92-1 Lead monoxide (lead oxide) CAS-No. 1317-36-8 2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-one CAS-No. 71868- 10-5 Melamine CAS-No. 108-78-1 |
| installation altitude at height above sea level maximum | 2 000 m |
| ambient temperature · during storage | -55 ... +80 °C |
| relative humidity minimum | 10 % |
| relative humidity at 55 °C according to IEC 60068-2-30 maximum | 95 % |
| number of NC contacts for main contacts | 0 |
| operating voltage · at AC-3e rated value maximum | 1 000 V |
| operational current · at AC-1 · up to 690 V at ambient temperature 40 °C rated value | 125 A |
| operational current · at AC-3 · at 500 V rated value | 80 A |
| operational current · at AC-3 · at 690 V rated value | 58 A |
| operational current · at AC-3 · at 1000 V rated value | 30 A |
| operational current · at AC-3e · at 400 V rated value | 80 A |
| operational current · at AC-3e · at 500 V rated value | 80 A |
| operational current · at AC-3e · at 690 V rated value | 58 A |
| operational current · at AC-3e · at 1000 V rated value | 30 A |
| operational current · at AC-5a up to 690 V rated value | 110 A |
| operational current · at AC-5b up to 400 V rated value | 80 A |
| operational current · at AC-6a · up to 230 V for current peak value n=20 rated value | 80 A |
| operational current · at AC-6a · up to 400 V for current peak value n=20 rated value | 80 A |
| operational current · at AC-6a · up to 500 V for current peak value n=20 rated value | 80 A |
| operational current · at AC-6a · up to 690 V for current peak value n=20 rated value | 58 A |
| minimum cross-section in main circuit at maximum AC-1 rated value | 50 mm2 |
| operational current for approx. 200000 operating cycles at AC-4 · at 400 V rated value | 34 A |
| operational current · at 1 current path at DC-1 · at 24 V rated value | 100 A |
| operational current · at 1 current path at DC-1 · at 60 V rated value | 60 A |
| operational current · at 1 current path at DC-1 · at 110 V rated value | 9 A |
| operational current · at 1 current path at DC-1 · at 220 V rated value | 2 A |
| operational current · at 1 current path at DC-1 · at 440 V rated value | 0.6 A |
| operational current · at 1 current path at DC-1 · at 600 V rated value | 0.4 A |
| operational current · with 2 current paths in series at DC-1 · at 24 V rated value | 100 A |
| operational current · with 3 current paths in series at DC-1 · at 24 V rated value | 100 A |
| operational current · at 1 current path at DC-3 at DC-5 · at 24 V rated value | 40 A |
| operational current · at 1 current path at DC-3 at DC-5 · at 60 V rated value | 6 A |
| operational current · at 1 current path at DC-3 at DC-5 · at 110 V rated value | 2.5 A |
| operational current · at 1 current path at DC-3 at DC-5 · at 220 V rated value | 1 A |
| operational current · at 1 current path at DC-3 at DC-5 · at 440 V rated value | 0.15 A |
| operational current · at 1 current path at DC-3 at DC-5 · at 600 V rated value | 0.06 A |
| operational current · with 2 current paths in series at DC-3 at DC-5 · at 24 V rated value | 100 A |
| operational current · with 3 current paths in series at DC-3 at DC-5 · at 24 V rated value | 100 A |
| operating power · at AC-2 at 400 V rated value | 37 kW |
| operating power · at AC-3 · at 230 V rated value | 22 kW |
| operating power · at AC-3 · at 500 V rated value | 45 kW |
| operating power · at AC-3 · at 690 V rated value | 55 kW |
| operating power · at AC-3 · at 1000 V rated value | 37 kW |
| operating power · at AC-3e · at 230 V rated value | 22 kW |
| operating power · at AC-3e · at 400 V rated value | 37 kW |
| operating power · at AC-3e · at 500 V rated value | 45 kW |
| operating power · at AC-3e · at 690 V rated value | 55 kW |
| operating power · at AC-3e · at 1000 V rated value | 37 kW |
| operating power for approx. 200000 operating cycles at AC-4 · at 400 V rated value | 17.9 kW |
| operating apparent power at AC-6a · up to 230 V for current peak value n=20 rated value | 31 kVA |
| operating apparent power at AC-6a · up to 400 V for current peak value n=20 rated value | 55 kVA |
| operating apparent power at AC-6a · up to 500 V for current peak value n=20 rated value | 69 kVA |
| operating apparent power at AC-6a · up to 690 V for current peak value n=20 rated value | 69 kVA |
| short-time withstand current in cold operating state up to 40 °C · limited to 1 s switching at zero current maximum | 1 500 A; Use minimum cross-section acc. to AC-1 rated value |
| no-load switching frequency · at AC | 1 000 1/h |
| no-load switching frequency · at DC | 1 000 1/h |
| operating frequency · at AC-1 maximum | 900 1/h |
| operating frequency · at AC-2 maximum | 400 1/h |
| operating frequency · at AC-3e · maximum | 1 000 1/h |
| operating frequency · at AC-4 maximum | 300 1/h |
| control supply voltage at DC rated value | 20 ... 33 V |
| operating range factor control supply voltage rated value of magnet coil at DC · initial value | 0.8 |
| inrush current peak | 6.5 A |
| duration of inrush current peak | 50 µs |
| pickup current mean value | 3.2 A |
| pickup current peak | 6.5 A |
| duration of pickup current | 150 ms |
| holding current mean value | 75 mA |
| apparent pick-up power of magnet coil at AC · at 50 Hz | 151 V·A |
| apparent pick-up power of magnet coil at AC · at 60 Hz | 151 V·A |
| apparent holding power · at minimum rated control supply voltage at DC | 1.8 V·A |
| apparent holding power · at maximum rated control supply voltage at DC | 1.8 V·A |
| apparent holding power of magnet coil at AC · at 50 Hz | 3.1 V·A |
| apparent holding power of magnet coil at AC · at 60 Hz | 3.1 V·A |
| inductive power factor with the holding power of the coil · at 50 Hz | 0.95 |
| closing power of magnet coil at DC | 76 W |
| closing delay · at AC | 50 ... 70 ms |
| closing delay · at DC | 50 ... 70 ms |
| opening delay · at AC | 38 ... 57 ms |
| opening delay · at DC | 38 ... 57 ms |
| arcing time | 10 ... 20 ms |
| control version of the switch operating mechanism | Standard A1 - A2 |
| operational current at AC-12 maximum | 10 A |
| operational current at AC-15 · at 230 V rated value | 6 A |
| operational current at AC-15 · at 400 V rated value | 3 A |
| operational current at AC-15 · at 500 V rated value | 2 A |
| operational current at AC-15 · at 690 V rated value | 1 A |
| operational current at DC-12 · at 24 V rated value | 10 A |
| operational current at DC-12 · at 48 V rated value | 6 A |
| operational current at DC-12 · at 60 V rated value | 6 A |
| operational current at DC-12 · at 110 V rated value | 3 A |
| operational current at DC-12 · at 125 V rated value | 2 A |
| operational current at DC-12 · at 220 V rated value | 1 A |
| operational current at DC-12 · at 600 V rated value | 0.15 A |
| operational current at DC-13 · at 24 V rated value | 10 A |
| operational current at DC-13 · at 48 V rated value | 2 A |
| operational current at DC-13 · at 60 V rated value | 2 A |
| operational current at DC-13 · at 110 V rated value | 1 A |
| operational current at DC-13 · at 125 V rated value | 0.9 A |
| operational current at DC-13 · at 220 V rated value | 0.3 A |
| operational current at DC-13 · at 600 V rated value | 0.1 A |
| contact reliability of auxiliary contacts | 1 faulty switching per 100 million (17 V, 1 mA) |
| full-load current (FLA) for 3-phase AC motor · at 600 V rated value | 62 A |
| yielded mechanical performance [hp] · for single-phase AC motor · at 110/120 V rated value | 7.5 hp |
| yielded mechanical performance [hp] · for 3-phase AC motor · at 200/208 V rated value | 25 hp |
| yielded mechanical performance [hp] · for 3-phase AC motor · at 220/230 V rated value | 30 hp |
| yielded mechanical performance [hp] · for 3-phase AC motor · at 460/480 V rated value | 60 hp |
| yielded mechanical performance [hp] · for 3-phase AC motor · at 575/600 V rated value | 60 hp |
| contact rating of auxiliary contacts according to UL | A600 / P600 |
| design of the miniature circuit breaker for short-circuit protection of the auxiliary circuit up to 230 V | C characteristic: 10 A; 0.4 kA |
| design of the fuse link · for short-circuit protection of the main circuit · with type of coordination 1 required | gG: 250 A (690 V, 100 kA), aM: 160 A (690 V, 100 kA), BS88: 200 A (415 V, 80 kA) |
| mounting position | +/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface |
| fastening method side-by-side mounting | Yes |
| required spacing · with side-by-side mounting · forwards | 20 mm |
| required spacing · with side-by-side mounting · upwards | 10 mm |
| required spacing · with side-by-side mounting · downwards | 10 mm |
| required spacing · with side-by-side mounting · at the side | 0 mm |
| required spacing · for grounded parts · forwards | 20 mm |
| required spacing · for grounded parts · upwards | 10 mm |
| required spacing · for grounded parts · at the side | 10 mm |
| required spacing · for grounded parts · downwards | 10 mm |
| required spacing · for live parts · forwards | 20 mm |
| required spacing · for live parts · upwards | 10 mm |
| required spacing · for live parts · downwards | 10 mm |
| required spacing · for live parts · at the side | 10 mm |
| type of electrical connection · for auxiliary and control circuit | screw-type terminals |
| type of electrical connection · at contactor for auxiliary contacts | Screw-type terminals |
| type of electrical connection · of magnet coil | screw terminal |
| type of connectable conductor cross-sections · for main contacts · finely stranded with core end processing | 2x (2.5 ... 35 mm2), 1x (2.5 ... 50 mm2) |
| type of connectable conductor cross-sections · for AWG cables for main contacts | 2x (10 ... 1/0), 1x (10 ... 2/0) |
| connectable conductor cross-section for main contacts · solid | 2.5 ... 16 mm2 |
| connectable conductor cross-section for main contacts · stranded | 6 ... 70 mm2 |
| connectable conductor cross-section for main contacts · finely stranded with core end processing | 2.5 ... 50 mm2 |
| connectable conductor cross-section for auxiliary contacts · solid or stranded | 0.5 ... 2.5 mm2 |
| connectable conductor cross-section for auxiliary contacts · finely stranded with core end processing | 0.5 ... 2.5 mm2 |
| type of connectable conductor cross-sections · for auxiliary contacts · solid or stranded | 2x (0.5 ... 1.5 mm2), 2x (0.75 ... 2.5 mm2) |
| AWG number extended as coded connectable conductor cross section for main contacts | 10 ... 2/0 |
| AWG number as coded connectable conductor cross section for auxiliary contacts | 20 ... 14 |
| product function · mirror contact according to IEC 60947-4-1 | Yes |
| product function · positively driven operation according to IEC 60947-5-1 | No |
| product function · suitable for safety function | Yes |
| suitability for use safety-related switching OFF | Yes |
| service life maximum | 20 a |
| test wear-related service life necessary | Yes |
| proportion of dangerous failures · with low demand rate according to SN 31920 | 40 % |
| proportion of dangerous failures · with high demand rate according to SN 31920 | 73 % |
| B10 value with high demand rate according to SN 31920 | 1 000 000 |
| failure rate [FIT] with low demand rate according to SN 31920 | 100 FIT |
| device type according to ISO 13849-1 | 3 |
| overdimensioning according to ISO 13849-2 necessary | Yes |
| safety device type according to IEC 61508-2 | Type A |
| touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front |
| Environmental Product Declaration · global warming potential [CO2 eq] / during manufacturing | 9.35 kg |
Source: manufacturer data · Last verified: 03 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of 3RT2045-1NB30 is 80 A (AC-3, 400 V).
The rated operational voltage of 3RT2045-1NB30 is 1000 V AC.
The rated motor power of 3RT2045-1NB30 is 37 kW (AC-3, 400 V).
The control voltage range of 3RT2045-1NB30 is 20–33 V AC/DC.
The EAN (GTIN) of 3RT2045-1NB30 is 4047621024769.
3RT2045-1NB30 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1 business day.
AC-1 and AC-6a contactors for data center PDU and UPS systems: sizing, harmonic derating, coil selection, and endurance guidance for engineers. Shop at Stoklink.
Compare AC3 rating IEC contactors versus NEMA size codes, with cross-reference tables, derating formulas, and selection tips for engineers. Shop at Stoklink.
Master AC3 rating selection with our complete contactor checklist covering load sizing, utilization categories, derating, and coordination. Shop at Stoklink.