Part number
3RT2035-1NB30
$145.27 In stock · 50+ Dispatch Planned dispatch date. We aim to ship within 1 business day. Depending on warehouse workload it can take 2–3 business days. · From Türkiye

Siemens 3RT2035-1NB30 3RT2 41A 3P 400V Contactor

The Siemens 3RT2035-1NB30 is a 3-pole SIRIUS 3RT2 contactor rated 41 A (AC-3) / 18.5 kW at 400 V, 30 hp at 480 V, with a 20–33 V AC/DC coil and 1 NO + 1 NC auxiliary contacts.

Poles
3
AC-3 current (400 V)
41 A
Motor power (400 V)
18.5 kW
Motor power (480 V)
30 hp @ 460/480 V
Coil voltage
20–33 V AC/DC
Auxiliary contacts
1 NO + 1 NC
EAN
4011209939400
Description

About the 3RT2035-1NB30

The Siemens 3RT2035-1NB30 is a contactor from the SENTRON/SIRIUS 3RT2 series. Power contactor, AC-3e/AC-3, 41 A, 18.5 kW / 400 V, 3-pole, 20-33 V AC/DC, 50/60 Hz, with integrated varistor, auxiliary contacts: 1 NO + 1 NC, screw terminal, size: S2. Supplied by Stoklink for industrial and commercial low-voltage applications.

Certifications & Standards

  • EN 60715

Applications & Use Cases

The Siemens 3RT2035-1NB30 is used in industrial control panels, distribution boards and automation systems. As part of the Siemens 3RT2 range it integrates with compatible SENTRON/SIRIUS components for a coordinated low-voltage installation. Genuine Siemens product supplied by Stoklink with fast dispatch from Türkiye.

Specification

Full specification

216 values · Last verified 03 Nov 2026

General 4

Series SIRIUS 3RT2
Contactor size / frame S2
Number of poles 3
Main contact configuration 3 NO

Electrical 8

Rated operational current Ie, AC-3, 400 V 41 A
Rated motor power, AC-3, 400 V 18.5 kW
Rated operational current, AC-1 (60 °C) 55 A
Rated operational current, AC-1 (40 °C) 60 A
Rated operational current, AC-4, 400 V 35 A
Max. rated operational voltage Ue 690 V
Rated insulation voltage Ui 690 V
Rated impulse withstand voltage Uimp 6 kV

Control circuit 5

Rated control supply voltage Uc 20–33 V
Coil type AC-DC
Coil frequency 50/60 Hz
Coil technology Conventional, surge suppressor with varistor
Coil holding power 1 W | VA
Show all 53 specifications ↓ Show less ↑36 more values in Identification, Auxiliary contacts, Mechanical, Dimensions and weight, Environmental, North American ratings (UL/CSA), Certifications and standards, Logistics. 163 more as published by Siemens are shown on request.

Identification 14

Part number 3RT2035-1NB30
Model code S2
Brand Siemens
Series SIRIUS 3RT2
Family Contactors
Condition New, factory sealed
Source Siemens and its authorised distributors
Warranty Manufacturer warranty
Lifecycle status Active, in production
EAN 4011209939400
ETIM class EC000066
eCl@ss 27371003
UPC 887621915773
UNSPSC 39121529

Auxiliary contacts 4

Built-in auxiliary contacts, NO 1
Built-in auxiliary contacts, NC 1
Auxiliary contacts 1 NO + 1 NC
Mirror contact (IEC 60947-4-1 Annex F) Yes

Mechanical 2

Main circuit connection Screw terminal
Mounting 35 mm DIN rail, Panel (screw) mounting

Dimensions and weight 4

Width 55 mm
Height 114 mm
Depth 130 mm
Net weight 1.074 kg

Environmental 4

Ambient operating temperature -25 … 60 °C
Degree of protection IP20
Mechanical durability 10000000 cycles
Max. operating frequency, AC-3 1000 cycles/h

North American ratings (UL/CSA) 2

Motor rating (UL/CSA) 10 hp @ 200/208 V · 15 hp @ 220/230 V · 30 hp @ 460/480 V · 40 hp @ 575/600 V · 3 hp @ 110/120 V (1-ph) · 7.5 hp @ 230 V (1-ph)
Full-load amps @ 480 V 40 A

Certifications and standards 1

Certifications UL, Marine

Logistics 5

Package dimensions (L × W × H) 122 × 63 × 145 mm
Shipping weight 1.574 kg
Ships from Türkiye
Dispatch 18 Nov
Stock In stock
Additional manufacturer data 163 163 more values as published by Siemens, shown on request.

Additional manufacturer data 163

product brand name SIRIUS
product designation Power contactor
product extension · function module for communication No
product extension · auxiliary switch Yes
power loss [W] for rated value of the current · at AC in hot operating state 6.6 W
power loss [W] for rated value of the current · without load current share typical 1 W
type of calculation of power loss current-dependent quadratic
insulation voltage · of auxiliary circuit with degree of pollution 3 rated value 690 V
surge voltage resistance · of auxiliary circuit rated value 6 kV
maximum permissible voltage for protective separation between coil and main contacts according to EN 60947-1 400 V
shock resistance at rectangular impulse · at AC 7.7 g / 5 ms, 4.5 g / 10 ms
shock resistance at rectangular impulse · at DC 7.7 g / 5 ms, 4.5 g / 10 ms
shock resistance with sine pulse · at AC 12 g / 5 ms, 7 g / 10 ms
shock resistance with sine pulse · at DC 12 g / 5 ms, 7 g / 10 ms
mechanical service life (operating cycles) · of the contactor with added electronically optimized auxiliary switch block typical 5 000 000
reference code according to IEC 81346-2 Q
Substance Prohibitance (day/month/year) 10/01/2014
SVHC substance name Lead CAS-No. 7439-92-1 Lead monoxide (lead oxide) CAS-No. 1317-36-8 2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-one CAS-No. 71868- 10-5 Melamine CAS-No. 108-78-1
installation altitude at height above sea level maximum 2 000 m
ambient temperature · during storage -55 ... +80 °C
relative humidity minimum 10 %
relative humidity at 55 °C according to IEC 60068-2-30 maximum 95 %
number of NC contacts for main contacts 0
operating voltage · at AC-3e rated value maximum 690 V
operational current · at AC-1 · up to 690 V at ambient temperature 40 °C rated value 60 A
operational current · at AC-3 · at 500 V rated value 41 A
operational current · at AC-3 · at 690 V rated value 24 A
operational current · at AC-3e · at 400 V rated value 41 A
operational current · at AC-3e · at 500 V rated value 41 A
operational current · at AC-3e · at 690 V rated value 24 A
operational current · at AC-5a up to 690 V rated value 52.8 A
operational current · at AC-5b up to 400 V rated value 33.2 A
operational current · at AC-6a · up to 230 V for current peak value n=20 rated value 36.5 A
operational current · at AC-6a · up to 400 V for current peak value n=20 rated value 36.5 A
operational current · at AC-6a · up to 500 V for current peak value n=20 rated value 36.5 A
operational current · at AC-6a · up to 690 V for current peak value n=20 rated value 24 A
minimum cross-section in main circuit at maximum AC-1 rated value 16 mm2
operational current for approx. 200000 operating cycles at AC-4 · at 400 V rated value 22 A
operational current · at 1 current path at DC-1 · at 24 V rated value 55 A
operational current · at 1 current path at DC-1 · at 60 V rated value 23 A
operational current · at 1 current path at DC-1 · at 110 V rated value 4.5 A
operational current · at 1 current path at DC-1 · at 220 V rated value 1 A
operational current · at 1 current path at DC-1 · at 440 V rated value 0.4 A
operational current · at 1 current path at DC-1 · at 600 V rated value 0.25 A
operational current · with 2 current paths in series at DC-1 · at 24 V rated value 55 A
operational current · with 3 current paths in series at DC-1 · at 24 V rated value 55 A
operational current · at 1 current path at DC-3 at DC-5 · at 24 V rated value 35 A
operational current · at 1 current path at DC-3 at DC-5 · at 60 V rated value 6 A
operational current · at 1 current path at DC-3 at DC-5 · at 220 V rated value 1 A
operational current · at 1 current path at DC-3 at DC-5 · at 440 V rated value 0.1 A
operational current · at 1 current path at DC-3 at DC-5 · at 600 V rated value 0.06 A
operational current · with 2 current paths in series at DC-3 at DC-5 · at 24 V rated value 55 A
operational current · with 3 current paths in series at DC-3 at DC-5 · at 24 V rated value 55 A
operating power · at AC-2 at 400 V rated value 18.5 kW
operating power · at AC-3 · at 230 V rated value 11 kW
operating power · at AC-3 · at 500 V rated value 22 kW
operating power · at AC-3 · at 690 V rated value 22 kW
operating power · at AC-3e · at 230 V rated value 11 kW
operating power · at AC-3e · at 400 V rated value 18.5 kW
operating power · at AC-3e · at 500 V rated value 22 kW
operating power · at AC-3e · at 690 V rated value 22 kW
operating power for approx. 200000 operating cycles at AC-4 · at 400 V rated value 11.6 kW
operating apparent power at AC-6a · up to 230 V for current peak value n=20 rated value 14.5 kVA
operating apparent power at AC-6a · up to 400 V for current peak value n=20 rated value 25.2 kVA
operating apparent power at AC-6a · up to 500 V for current peak value n=20 rated value 31.6 kVA
operating apparent power at AC-6a · up to 690 V for current peak value n=20 rated value 28.6 kVA
short-time withstand current in cold operating state up to 40 °C · limited to 1 s switching at zero current maximum 843 A; Use minimum cross-section acc. to AC-1 rated value
no-load switching frequency · at AC 1 500 1/h
no-load switching frequency · at DC 1 500 1/h
operating frequency · at AC-1 maximum 1 200 1/h
operating frequency · at AC-2 maximum 750 1/h
operating frequency · at AC-3e · maximum 1 000 1/h
operating frequency · at AC-4 maximum 300 1/h
control supply voltage at DC rated value 20 ... 33 V
operating range factor control supply voltage rated value of magnet coil at DC · initial value 0.8
inrush current peak 3 A
duration of inrush current peak 50 µs
pickup current mean value 1 A
pickup current peak 2.6 A
duration of pickup current 230 ms
holding current mean value 40 mA
apparent pick-up power of magnet coil at AC · at 50 Hz 40 V·A
apparent pick-up power of magnet coil at AC · at 60 Hz 40 V·A
apparent holding power · at minimum rated control supply voltage at DC 2 V·A
apparent holding power · at maximum rated control supply voltage at DC 2 V·A
apparent holding power of magnet coil at AC · at 50 Hz 2 V·A
apparent holding power of magnet coil at AC · at 60 Hz 2 V·A
inductive power factor with the holding power of the coil · at 50 Hz 0.95
closing power of magnet coil at DC 23 W
closing delay · at AC 35 ... 110 ms
closing delay · at DC 35 ... 110 ms
opening delay · at AC 30 ... 55 ms
opening delay · at DC 30 ... 55 ms
arcing time 10 ... 20 ms
control version of the switch operating mechanism Standard A1 - A2
operational current at AC-12 maximum 10 A
operational current at AC-15 · at 230 V rated value 10 A
operational current at AC-15 · at 400 V rated value 3 A
operational current at AC-15 · at 500 V rated value 2 A
operational current at AC-15 · at 690 V rated value 1 A
operational current at DC-12 · at 24 V rated value 10 A
operational current at DC-12 · at 48 V rated value 6 A
operational current at DC-12 · at 60 V rated value 6 A
operational current at DC-12 · at 110 V rated value 3 A
operational current at DC-12 · at 125 V rated value 2 A
operational current at DC-12 · at 220 V rated value 1 A
operational current at DC-12 · at 600 V rated value 0.15 A
operational current at DC-13 · at 24 V rated value 10 A
operational current at DC-13 · at 48 V rated value 2 A
operational current at DC-13 · at 60 V rated value 2 A
operational current at DC-13 · at 110 V rated value 1 A
operational current at DC-13 · at 125 V rated value 0.9 A
operational current at DC-13 · at 220 V rated value 0.3 A
operational current at DC-13 · at 600 V rated value 0.1 A
contact reliability of auxiliary contacts 1 faulty switching per 100 million (17 V, 1 mA)
full-load current (FLA) for 3-phase AC motor · at 600 V rated value 41 A
yielded mechanical performance [hp] · for single-phase AC motor · at 110/120 V rated value 3 hp
yielded mechanical performance [hp] · for 3-phase AC motor · at 200/208 V rated value 10 hp
yielded mechanical performance [hp] · for 3-phase AC motor · at 220/230 V rated value 15 hp
yielded mechanical performance [hp] · for 3-phase AC motor · at 460/480 V rated value 30 hp
yielded mechanical performance [hp] · for 3-phase AC motor · at 575/600 V rated value 40 hp
contact rating of auxiliary contacts according to UL A600 / P600
design of the miniature circuit breaker for short-circuit protection of the auxiliary circuit up to 230 V C characteristic: 10 A; 0.4 kA
design of the fuse link · for short-circuit protection of the main circuit · with type of coordination 1 required gG: 160 A (690 V, 100 kA), aM: 80 A (690 V, 100 kA), BS88: 125 A (415 V, 80 kA)
mounting position +/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface
fastening method side-by-side mounting Yes
required spacing · with side-by-side mounting · forwards 10 mm
required spacing · with side-by-side mounting · upwards 10 mm
required spacing · with side-by-side mounting · downwards 10 mm
required spacing · with side-by-side mounting · at the side 0 mm
required spacing · for grounded parts · forwards 10 mm
required spacing · for grounded parts · upwards 10 mm
required spacing · for grounded parts · at the side 6 mm
required spacing · for grounded parts · downwards 10 mm
required spacing · for live parts · forwards 10 mm
required spacing · for live parts · upwards 10 mm
required spacing · for live parts · downwards 10 mm
required spacing · for live parts · at the side 6 mm
type of electrical connection · for auxiliary and control circuit screw-type terminals
type of electrical connection · at contactor for auxiliary contacts Screw-type terminals
type of electrical connection · of magnet coil screw terminal
type of connectable conductor cross-sections · for main contacts · solid or stranded 2x (1 ... 35 mm2), 1x (1 ... 50 mm2)
type of connectable conductor cross-sections · for AWG cables for main contacts 2x (18 ... 2), 1x (18 ... 1)
connectable conductor cross-section for main contacts · finely stranded with core end processing 1 ... 35 mm2
connectable conductor cross-section for auxiliary contacts · solid or stranded 0.5 ... 2.5 mm2
connectable conductor cross-section for auxiliary contacts · finely stranded with core end processing 0.5 ... 2.5 mm2
type of connectable conductor cross-sections · for auxiliary contacts · solid or stranded 2x (0.5 ... 1.5 mm2), 2x (0.75 ... 2.5 mm2)
AWG number as coded connectable conductor cross section for main contacts 18 ... 1
product function · mirror contact according to IEC 60947-4-1 Yes
product function · positively driven operation according to IEC 60947-5-1 No
product function · suitable for safety function Yes
suitability for use safety-related switching OFF Yes
service life maximum 20 a
test wear-related service life necessary Yes
proportion of dangerous failures · with low demand rate according to SN 31920 40 %
proportion of dangerous failures · with high demand rate according to SN 31920 73 %
B10 value with high demand rate according to SN 31920 1 000 000
failure rate [FIT] with low demand rate according to SN 31920 100 FIT
device type according to ISO 13849-1 3
overdimensioning according to ISO 13849-2 necessary Yes
safety device type according to IEC 61508-2 Type A
touch protection on the front according to IEC 60529 finger-safe, for vertical contact from the front
Environmental Product Declaration · global warming potential [CO2 eq] / during manufacturing 5.88 kg

Source: manufacturer data · Last verified: 03 Nov 2026

Documents

Documents for 3RT2035-1NB30

No documents are on file for this part yet.

Ask us for the datasheet
Certifications

Certifications and standards

  • UL
  • Marine
  • EN 60715
Quick answers

Questions about the 3RT2035-1NB30

What is the rated current of 3RT2035-1NB30?

The rated current of 3RT2035-1NB30 is 41 A (AC-3, 400 V).

Which supply voltage is 3RT2035-1NB30 rated for?

The rated operational voltage of 3RT2035-1NB30 is 690 V AC.

What motor power is 3RT2035-1NB30 rated for?

The rated motor power of 3RT2035-1NB30 is 18.5 kW (AC-3, 400 V).

Which control voltage does 3RT2035-1NB30 need?

The control voltage range of 3RT2035-1NB30 is 20–33 V AC/DC.

What is the EAN of 3RT2035-1NB30?

The EAN (GTIN) of 3RT2035-1NB30 is 4011209939400.

Where does 3RT2035-1NB30 ship from, and how fast?

3RT2035-1NB30 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1 business day.

Guides

Guides for contactors

All guides for contactors
Reviews

Customer reviews

Series

Siemens SIRIUS 3RT2

Brand
Siemens
Series
SIRIUS 3RT2
Series page →
Series

Other series in Contactors

$145.27 In stock · 18 Nov
Quote

Get a Quote

Genuine parts

Genuine, factory-sealed parts

Siemens · 3RT2035-1NB30

Every part on Stoklink is new, unused and made by the manufacturer named on the page.

Condition
New and unused, in the manufacturer's factory-sealed packaging.
Sourced from
Siemens and its authorised distributors.
Warranty
The manufacturer's warranty applies.
If a part is not genuine
We refund the full amount.

Added to cart Could not add to cart