- Description
The Schneider Electric LV847385 is an MN instantaneous undervoltage release for fixed MasterPact MTZ1, MTZ2, and MTZ3 air circuit breakers, supplied for 380-480 V AC 50/60 Hz control circuits only. It opens the breaker automatically once the supervised voltage falls to 0.35-0.7 Un, then re-closes the circuit once voltage recovers to 0.85 Un.
Technical Specifications
| Reference | LV847385 |
| Brand | Schneider Electric |
| Range | MasterPact |
| Device short name | MN |
| Product or Component Type | Undervoltage release |
| Device Application | Safety |
| Range compatibility | MasterPact MTZ1, MTZ2, MTZ3 circuit breaker |
| Voltage release type | Instantaneous |
| Control Type | Standard |
| [Un] voltage power supply | 380-480 V AC 50/60 Hz |
| Threshold tripping voltage | 0.35-0.7 Un opening, 0.85 Un closing |
| Holding power consumption | 4.5 VA |
| Circuit breaker mounting mode | Fixed |
| Maximum response time | 45 ms on MTZ1, 95 ms on MTZ2, 95 ms on MTZ3 |
Selection Notes
The LV847385 is the AC-only, 380-480 V member of the MN family and has no DC rating, unlike the 100-130 V and 200-250 V versions that accept either AC or DC supply; confirm the control source is AC before specifying it. It fits fixed MTZ1, MTZ2, and MTZ3 breakers only. Because the trip threshold is 0.35-0.7 Un, it reacts well before a complete loss of control voltage, giving the downstream load an early, controlled disconnect rather than an uncontrolled one. Holding power consumption is specified in VA rather than W for this AC-only variant, reflecting the reactive component of the coil's steady-state draw.