- Home
- All Products
- Schneider Electric C160S3NAFM ComPacT NS1600NA 3P 1600 A 690 V Fixed Manual Switch Disconnector Schneider Electric C160S3NAFM ComPacT NS1600NA 3P 1600 A 690 V Fixed Manual Switch Disconnector
Schneider Electric C160S3NAFM ComPacT NS1600NA 3P 1600 A 690 V Fixed Manual Switch Disconnector
Schneider Electric C160S3NAFM ComPacT NS1600NA 3P 1600 A 690 V Fixed Manual Switch Disconnector
Get Quote
- Description
The C160S3NAFM is a 3-pole Schneider Electric ComPacT NS1600NA switch-disconnector rated for an operational current (Ie) of 1600 A (AC-23A) at 690 V AC. It is a fixed, front-connected, manually-operated device for controlling and isolating LV distribution circuits ahead of downstream protection — it does not clear fault current on its own.
Technical Specifications
| SKU / Reference | C160S3NAFM |
| Brand | Schneider Electric |
| Range | ComPacT NS new generation |
| Series | NS1600NA |
| Device application | Distribution |
| Poles | 3P |
| [Ie] Rated operational current | 1600 A (AC-23A), 220/240–660/690 V AC 50/60 Hz |
| [Ue] Rated operational voltage | 690 V AC 50/60 Hz, conforming to IEC 60947-3 |
| [Ith] Conventional free-air thermal current | 1600 A at 60 °C |
| [Ui] Rated insulation voltage | 800 V AC 50/60 Hz |
| [Uimp] Rated impulse withstand voltage | 8 kV |
| [Icw] Rated short-time withstand current | 25 kA during 0.5 s, 4 kA during 20 s |
| [Icm] Rated short-circuit making capacity | 52 kA at 690 V AC |
| Suitability for isolation | Yes, conforming to IEC 60947-3 |
| Contact position indicator | Yes |
| Visible break | No |
| Control type | Manually operated |
| Mounting mode | Fixed |
| Connection | Front upside, front downside |
| Connection pitch | 70 mm |
| Dimensions (W x H x D) | 327 x 210 x 147 mm |
| Net weight | 14 kg |
| IP / IK degree | IP40 / IK07 (EN 50102) |
| Pollution degree | 3, conforming to IEC 60664-1 |
| Ambient temperature (operation / storage) | -25…70 °C / -50…85 °C |
Certifications & Standards
- IECEE CB Scheme
- IEC 60947-3
Selection Notes
As an NA-code device the C160S3NAFM carries no Icu rating of its own — fault clearance is left to a breaker upstream or downstream, while this unit provides the lockable, visible-break isolation point required before maintenance. Its 25 kA/0.5 s short-time withstand (Icw) means it can stay closed through a fault long enough for a coordinated breaker to trip first, rather than opening itself. Pick the 4-pole C160S4NAFM instead when the installation switches the neutral as well as the three phases.