- Part number
- C160S3NAFM
Description
About the C160S3NAFM
About the C160S3NAFM
The C160S3NAFM is a 3-pole Schneider Electric ComPacT NS1600NA switch-disconnector rated for an operational current (Ie) of 1600 A (AC-23A) at 690 V AC. It is a fixed, front-connected, manually-operated device for controlling and isolating LV distribution circuits ahead of downstream protection — it does not clear fault current on its own.
Certifications & Standards
- IECEE CB Scheme
- IEC 60947-3
Selection Notes
As an NA-code device the C160S3NAFM carries no Icu rating of its own — fault clearance is left to a breaker upstream or downstream, while this unit provides the lockable, visible-break isolation point required before maintenance. Its 25 kA/0.5 s short-time withstand (Icw) means it can stay closed through a fault long enough for a coordinated breaker to trip first, rather than opening itself. Pick the 4-pole C160S4NAFM instead when the installation switches the neutral as well as the three phases.
Specification
Full specification
Main 7
| Product name | ComPacT NS new generation |
|---|---|
| Product or component type | Switch disconnector |
| Device application | Distribution |
| Poles description | 3P |
| Network type | AC |
| Breaking capacity code | NA |
| Suitability for isolation | Yes conforming to IEC 60947-3 |
Complementary 21
| Network frequency | 50/60 Hz |
|---|---|
| Control type | Manually operated |
| Mounting mode | Fixed |
| Upside connection | Front |
| Downside connection | Front |
| [Ie] rated operational current | AC-23A: 1600 A AC 50/60 Hz 220/240 V, AC-23A: 1600 A AC 50/60 Hz 380/415 V, AC-23A: 1600 A AC 50/60 Hz 440/480 V, AC-23A: 1600 A AC 50/60 Hz 500/525 V, AC-23A: 1600 A AC 50/60 Hz 660/690 V |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz conforming to IEC 60947-3 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-3 |
| [Ith] conventional free air thermal current | 1600 A at 60 °C |
| [Icw] rated short-time withstand current | 25 kA during 0.5 s conforming to IEC 60947-3, 4 kA during 20 s conforming to IEC 60947-3 |
| [Icm] rated short-circuit making capacity | 52 kA 690 V AC at 50/60 Hz |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-3 |
| Contact position indicator | Yes |
| Visible break | No |
| Mechanical durability | 10000 cycles conforming to IEC 60947-3 |
| Electrical durability | 2000 cycles 440 V AC 50/60 Hz conforming to IEC 60947-3 |
| Connection pitch | 70 mm |
| Height | 210 mm |
| Width | 327 mm |
| Depth | 147 mm |
| Net weight | 14 kg |
Environment 7
| Standards | IEC 60947-3 |
|---|---|
| Product certifications | IECEE CB Scheme |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to EN 50102 |
| Pollution degree | 3 conforming to IEC 60947-3 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
Show all 52 specifications ↓ Show less ↑17 more values in Identification, Contractual warranty, Logistics.
Identification 6
| Part number | C160S3NAFM |
|---|---|
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
Contractual warranty 1
| Warranty (in months) | 18 |
|---|
Logistics 10
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 30.000 cm |
| Package 1 Width | 40.000 cm |
| Package 1 Length | 60.000 cm |
| Package 1 Weight | 13.862 kg |
| Shipping weight | 14.0 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
Documents
Documents for C160S3NAFM
No documents are on file for this part yet.
Ask us for the datasheet
Certifications
Certifications and standards
- CB Scheme
- IEC 60947-3
Quick answers
Questions about the C160S3NAFM
What is the rated current of C160S3NAFM?
The rated current of C160S3NAFM is 1600 A.
Which supply voltage is C160S3NAFM rated for?
The rated operational voltage of C160S3NAFM is 690 V AC.
What is the HS code of C160S3NAFM for customs?
The tariff (HS) code on file for C160S3NAFM is 853650.
Where does C160S3NAFM ship from, and how fast?
C160S3NAFM ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.