- Description
The Schneider Electric BMXEIA0100 is a Modicon X80 AS-Interface (AS-i) master module supporting up to 62 discrete I/O devices or 31 analog I/O devices on a single AS-i network. It draws 160 mA at 3.3 V DC, connects via a 3-pin SUB-D male connector, and carries an IP20 enclosure rating with Class I Division 2 hazardous-location approval.
Technical Specifications
| Reference | BMXEIA0100 |
| Brand | Schneider Electric |
| Range | Modicon X80 |
| GTIN | 3595864038032 |
| Product Type | Master module (AS-Interface) |
| AS-i Master Profile | M4 master profile |
| AS-i Slave Profiles Supported | S7.3, S7.A.7, S7.A.A, S7.A.8, S7.A.9, S6.0.X |
| Addressing | Standard and extended |
| Cycle Time | 5 ms (31 devices) / 10 ms (62 devices) |
| Server Devices (standard) | 124 discrete I/O, 124 analog I/O |
| Server Devices (extended) | 496 discrete I/O, 124 analog I/O |
| Electrical Connection | 1 male SUB-D connector, 3-pin |
| Maximum Cable Distance | 100 m (200 m line extension; 300 m with 2 repeaters; 500 m with 2 repeaters, master at center) |
| Current Consumption | 160 mA at 3.3 V DC |
| Ambient Air Temperature, Operation | 0...60 °C |
| Ambient Air Temperature, Storage | -40...70 °C |
| IP Degree of Protection | IP20 |
| Environmental Characteristic | Hazardous location, Class I Division 2 |
| Net Weight | 0.34 kg |
Certifications & Standards
- CE
- UL
- CSA
- RCM
- EAC
- Merchant Navy
- ATEX Zone 2/22
- IECEx Zone 2/22
- IEC 61131-2
- IEC 61010-2-201
- UL 61010-2-201
- CSA C22.2 No 61010-2-201
- IACS E10
- IEC 61000-6-5
- IEC 61850-3
- IEC 60079-0
Selection Notes
The BMXEIA0100's standard addressing mode covers 124 AS-i server devices (discrete and analog combined); switch to extended addressing when the network needs to scale toward the 496-device discrete ceiling, accepting the 10 ms cycle time instead of 5 ms. Because the module carries ATEX/IECEx Zone 2/22 and Class I Division 2 approval, it is the module to specify when the AS-i segment itself runs into a hazardous area rather than staying entirely inside a standard enclosure.
Applications
AS-Interface network integration for Modicon X80 I/O architectures — connecting up to 62 discrete or 31 analog AS-i field devices, including AS-i segments that extend into Zone 2/22 hazardous areas.