Part number
6EP4136-3AB00-0AY0
Model no
UPS1600
$322.92 In stock · 25 Dispatch Planned dispatch date. We aim to ship within 1 business day. Depending on warehouse workload it can take 2–3 business days. · From Türkiye

Siemens 6EP4136-3AB00-0AY0 SITOP UPS1600 24V DC 20A Uninterruptible Supply

SITOP UPS1600 DC UPS module - 24V DC 20A, adjustable backup time 0.5-20 min

Rated current
20 A
Rated operational voltage
24 V AC
Motor power
0.48 kW
EAN
4025515154211
Description

About the UPS1600

The Siemens 6EP4136-3AB00-0AY0 is a SITOP UPS1600 DC uninterruptible power supply module rated 24 V DC at 20 A, providing 21-29 V input buffering with an adjustable cut-in threshold and a rotary-switch-selectable backup time from 0.5 to 20 minutes. It delivers up to 60 A peak, runs at 97.7% efficiency with 10 W typical power loss, and carries an IP20 rating in a compact 50 x 139 x 125 mm DIN-rail enclosure weighing 0.39 kg.

Certifications & Standards

  • CE
  • UKCA
  • EAC
  • CB
  • ABS
  • DNV
  • EPD

Selection Notes

The rotary-coded backup-time switch (0.5 to 20 minutes, or maximum) sets how long the 24 V rail rides through a supply interruption before the connected battery module is exhausted, letting the same UPS1600 serve either a quick-ride-through role or a full shutdown-sequence role without reprogramming. The adjustable cut-in threshold (21-25 V in seven steps) lets it buffer only on a genuine dip rather than normal ripple from a lightly loaded 24 V supply. At 20 A rated and 60 A peak, it covers inrush from contactors and solenoids during the switchover without derating the connected battery module.

Applications

Used to bridge short mains interruptions for PLCs, I/O, and drives on a 24 V DC bus in control cabinets where an orderly shutdown or ride-through is required instead of an immediate loss of power.

Specification

Full specification

99 values · Last verified 01 Nov 2026

General information 3

product brand name SITOP
product type designation UPS1600
type of current supply DC UPS 24 V/20 A

Input 6

voltage curve at input DC
supply voltage at DC rated value 24 V
input voltage at DC 21 ... 29 V
adjustable response value voltage for buffer connection preset 21.5 V
adjustable response value voltage for buffer connection 21 ... 25 V; Adjustable: 21 V, 21.5 V, 22 V, 22.5 V, 23 V, 24 V, 25 V DC
input current at rated input voltage 24 V rated value 25 A; for max. charging current (4 A)

Memory 3

type of energy storage with batteries
product function DC-UPS modularly expandable Yes
design of the mains power cut bridging-connection Adjustable range using rotary coding switch: 0.5 min, 1 min, 2 min, 5 min, 10 min, 20 min, max. buffering time
Show all 99 specifications ↓ Show less ↑87 more values in Identification, Output, Efficiency, Protection and monitoring, Interfaces, Safety, Standards, specifications, approvals, Standards, specifications, approvals hazardous environments, Standards, specifications, approvals marine classification, Standards, specifications, approvals Environmental Product Declaration, Ambient conditions, Connection method, Mechanical data, Accessories, Additional information, EClass 7.1 27-04-06-90, Logistics.

Identification 10

Part number 6EP4136-3AB00-0AY0
Type designation UPS1600
Brand Siemens
Condition New, factory sealed
Source Siemens and its authorised distributors
Warranty Manufacturer warranty
Lifecycle status Active, in production
EAN 4025515154211
ETIM class EC000382
eCl@ss 27040705

Output 13

output voltage: in normal operation at DC rated value 24 V
output voltage: in buffering mode at DC rated value 24 V
formula for output voltage Vin - approx. 0.2 V
startup delay time typical 60 ms
voltage increase time of the output voltage typical 60 ms
output voltage in buffering mode at DC 18.5 ... 27 V
output current: rated value 20 A
output current: in normal operation 0 ... 60 A
output current: in buffering mode 0 ... 60 A
peak current 60 A
property of the output short-circuit proof Yes
design of short-circuit protection Limitation to 3 x I rated for 30 ms/min; through-conductivity for 1.5 x I rated for 5 sec/min
charging current 0.1 A, 4 A

Efficiency 5

efficiency in percent: at rated output voltage for rated value of the output current typical 97.7 %
efficiency in percent: in case of operation on rechargeable battery typical 97.7 %
power loss [W]: at rated output voltage for rated value of the output current typical 10 W
power loss [W]: in case of operation on rechargeable battery typical 10 W
supplied active power typical 480 W

Protection and monitoring 4

product function: reverse polarity protection against energy storage unit polarity reversal Yes
product function: reverse polarity protection against input voltage polarity reversal Yes
display version: for normal operation Normal operation: LED green (OK), floating changeover contact "Bat/OK" to setting "OK" ("OK" means: Voltage of the supplying power supply unit is greater than cut-in threshold set at the DC UPS module); Lack of buffer standby: LED red (alarm), floating changeover contact "Alarm/Bat" to setting "Alarm"; Battery replacement required: LED red (alarm) flashing with approx. 0.25 Hz, floating changeover contact "Alarm/Bat" switching with approx. 0.25 Hz; Energy storage > 85%: LED green (Bat > 85%), floating NOcontact "Bat > 85" closed; Permissible contact current capacity: DC 60 V/1 A or AC 30 V /1 A
display version: in buffering mode Buffered mode: LED yellow (Bat), floating changeover contact "OK/Bat" to setting "Bat"; Prewarning battery voltage 85%: LED green (Bat > 85%), floating NO contact "Bat > 85" closed

Interfaces 3

product component PC interface No
product function communication function Yes
design of the interface without

Safety 5

galvanic isolation between input and output No
operating resource protection class Class III
protection class IP IP20
standard: for emitted interference EN 55022 Class B
standard: for interference immunity EN 61000-6-2

Standards, specifications, approvals 6

certificate of suitability: CE marking Yes
certificate of suitability: UL approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
certificate of suitability: UKCA marking Yes
certificate of suitability: EAC approval Yes
type of certification CB-certificate Yes
MTBF at 40 °C 408 654 h

Standards, specifications, approvals hazardous environments 1

certificate of suitability: ATEX No

Standards, specifications, approvals marine classification 3

shipbuilding approval Yes
Marine classification association: American Bureau of Shipping Europe Ltd. (ABS) Yes
Marine classification association: Det Norske Veritas (DNV) Yes

Standards, specifications, approvals Environmental Product Declaration 5

Environmental Product Declaration Yes
global warming potential [CO2 eq]: total 269.9 kg
global warming potential [CO2 eq]: during manufacturing 16 kg
global warming potential [CO2 eq]: during operation 253.5 kg
global warming potential [CO2 eq]: after end of life 0.3 kg

Ambient conditions 4

ambient temperature: during operation -25 ... +70 °C; with natural convection
ambient temperature: during transport -40 ... +85 °C
ambient temperature: during storage -40 ... +85 °C
environmental category according to IEC 60721 Climate class 3K3, 5 ... 95% no condensation

Connection method 5

type of electrical connection screw terminal
at input 24 V DC: 2 screw terminals for 0.2 ... 6 mm2/24 ... 13 AWG
at output 24 V DC: 2 screw terminals for 0.2 ... 6 mm2/24 ... 13 AWG
for rechargeable battery module 24 V DC: 2 screw terminals for 0.2 ... 6 mm2/24 ... 13 AWG
for control circuit and status message 14 screw terminals for 0.2 ... 1.5 mm2/24 ... 16 AWG

Mechanical data 11

width × height × depth of the enclosure 50 × 139 × 125 mm
installation width × mounting height 50 mm × 239 mm
required spacing: top 50 mm
required spacing: bottom 50 mm
required spacing: left 0 mm
required spacing: right 0 mm
fastening method Snaps onto DIN rail EN 60715 35x7.5/15
DIN-rail mounting Yes
S7 rail mounting No
wall mounting No
housing can be lined up Yes

Accessories 1

electrical accessories Battery module

Additional information 1

other information Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

EClass 7.1 27-04-06-90 4

eClass 6 27-04-06-90
ETIM 10 EC000382
IDEA 4 4149
UNSPSC 15 39-12-10-11

Logistics 6

Net weight 0.39 kg
Country of origin Romania
Shipping weight 0.89 kg
Ships from Türkiye
Dispatch 13 Nov
Stock In stock

Source: manufacturer data · Last verified: 01 Nov 2026

Documents

Documents for 6EP4136-3AB00-0AY0 1

Certifications

Certifications and standards

  • CE marking
  • UKCA marking
  • EAC approval
  • type of certification CB-certificate
  • shipbuilding approval
  • American Bureau of Shipping Europe Ltd. (ABS)
  • Det Norske Veritas (DNV)
  • Environmental Product Declaration
Quick answers

Questions about the UPS1600

What is the rated current of UPS1600?

The rated current of UPS1600 is 20 A.

Which supply voltage is UPS1600 rated for?

The rated operational voltage of UPS1600 is 24 V AC.

What motor power is UPS1600 rated for?

The rated motor power of UPS1600 is 0.48 kW.

What is the HS code of UPS1600 for customs?

The tariff (HS) code on file for UPS1600 is 85044060.

What is the EAN of UPS1600?

The EAN (GTIN) of UPS1600 is 4025515154211.

Where does UPS1600 ship from, and how fast?

UPS1600 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.

Guides

Guides for power supplies

All guides for power supplies
Reviews

Customer reviews

Series

Siemens SITOP UPS1600

Brand
Siemens
Series
SITOP UPS1600
Series page →
$322.92 In stock · 13 Nov
Quote

Get a Quote

UPS1600

Genuine parts

Genuine, factory-sealed parts

Siemens · 6EP4136-3AB00-0AY0

Every part on Stoklink is new, unused and made by the manufacturer named on the page.

Condition
New and unused, in the manufacturer's factory-sealed packaging.
Sourced from
Siemens and its authorised distributors.
Warranty
The manufacturer's warranty applies.
If a part is not genuine
We refund the full amount.

Added to cart Could not add to cart