Main Components of a PLC System: Complete Guide for Engineers
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.
The Siemens 6EP3437-7SB00-3AX0 SITOP PSU6200 is a stabilized power supply that converts 400-500 V 3-phase AC input into a regulated 24 V DC output rated at 40 A. Output voltage is adjustable from 24 to 28 V via potentiometer, control precision holds within 0.2% on input fluctuation, and a diagnostic interface with electronic NO contact reports DC-OK status for supervisory monitoring.
The 24-28 V adjustable output and up to 48 A short-term rating below 45 °C give headroom over the 40 A nameplate rating for inrush-heavy loads such as contactor banks or multiple simultaneous PLC power-ups, without over-specifying a larger unit. The unit accepts either 400-500 V 3-phase AC or 500-550 V DC input, so it covers either an AC distribution board or a DC bus without a separate model. Two units can be paralleled via DIP switch for redundancy or added output current, which is the upgrade path instead of moving to a single higher-current supply.
Sized for machine-level 24 V DC distribution on installations with 400-500 V 3-phase mains, driving PLC racks, I/O stations, and multiple 24 V field devices from one central supply with diagnostic feedback to the control system.
| product brand name | SITOP |
|---|---|
| product type designation | PSU6200 |
| product designation | Power supply SITOP PSU6200 |
| type of current supply | 24 V/40 A |
| type of the power supply network | 3-phase AC or DC |
|---|---|
| phase number | 3 |
| voltage curve at input | AC/DC |
| supply voltage at AC: minimum rated value | 400 V |
| supply voltage at AC: maximum rated value | 500 V |
| supply voltage at AC: initial value | 323 V |
| supply voltage at AC: full-scale value | 576 V |
| supply voltage at DC | 500 ... 550 V |
| input voltage at DC | 450 ... 600 V |
| line frequency | 50/60 Hz |
| buffering time for rated value of the output current in the event of power failure minimum | 18 ms |
| operating condition of the mains buffering | at Vin = 400 V |
| input current: at rated input voltage 400 V | 1.5 A |
| input current: at rated input voltage 500 V | 1.2 A |
| current limitation of inrush current at 25 °C maximum | 10 A |
| fuse protection type in the feeder | three-poled coupled circuit breaker from 4 A characteristic C to 16 A characteristic C or circuit breaker 3RV2011-1EA10 (setting 4 A) or 3RV2711- 1ED10 (UL 489) |
| voltage curve at output | Controlled, isolated DC voltage |
|---|---|
| product function output voltage controlled | Yes |
| product function output voltage stabilized | Yes |
| number of outputs | 1 |
| output voltage at DC rated value | 24 V |
| output voltage: at output 1 at DC rated value | 24 V |
| output voltage: at output 1 at DC | 24 V |
| output voltage adjustable | Yes; via potentiometer |
| adjustable output voltage | 24 ... 28 V; max. 960 W (1152 W up to 45°C) |
| relative overall tolerance of the voltage | 3% |
| relative control precision of the output voltage: on slow fluctuation of input voltage | 0.2 % |
| residual ripple: maximum | 80 mV |
| residual ripple: typical | 50 mV |
| voltage peak: maximum | 80 mV |
| voltage peak: typical | 30 mV |
| display version for normal operation | Green LED for 24 V OK |
| type of signal at output | Electronic contact (NO contact, contact rating 30 V DC/0.1 A) for DC O.K. or diagnostic interface |
| behavior of the output voltage when switching on | Overshoot of Vout < 2 % |
| response delay maximum | 0.5 s |
| voltage increase time of the output voltage: typical | 100 ms |
| output current: rated value | 40 A |
| output current: rated range | 0 ... 40 A; 48 A up to +45°C; +60 ... +70 °C: Derating 3%/K |
| supplied active power typical | 960 W |
| short-term overload current: on short-circuiting during the start-up typical | 48 A |
| short-term overload current: at short-circuit during operation typical | 48 A |
| parallel switching of outputs | can be set with DIP switch |
| bridging of equipment | Yes; switchable characteristic |
| number of parallel-switched equipment resources for increasing the power | 2 |
| Part number | 6EP3437-7SB00-3AX0 |
|---|---|
| Type designation | PSU6200 |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4025515155362 |
| ETIM class | EC002540 |
| eCl@ss | 27040701 |
| efficiency in percent | 96 % |
|---|---|
| power loss [W]: at rated output voltage for rated value of the output current typical | 40 W |
| power loss [W]: during no-load operation maximum | 4.5 W |
| relative control precision of the output voltage at load step of resistive load 10/90/10 % typical | 2% |
|---|---|
| setting time: load step 10 to 90% typical | 2 ms |
| setting time: load step 90 to 10% typical | 10 ms |
| setting time: maximum | 10 ms |
| design of the overvoltage protection | < 32 V |
|---|---|
| property of the output short-circuit proof | Yes |
| design of short-circuit protection | Shutdown and periodic restart attempts |
| typical | 48 A |
| overcurrent overload capability: in normal operation | overload capability 150 % Iout rated up to 5 s/min |
| galvanic isolation between input and output | Yes |
|---|---|
| galvanic isolation | Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7) |
| operating resource protection class | Class I |
| leakage current: maximum | 3.5 mA |
| protection class IP | IP20 |
| standard: for emitted interference | EN 55022 Class B |
|---|---|
| standard: for mains harmonics limitation | EN 61000-3-2 |
| standard: for interference immunity | EN 61000-6-2 |
| certificate of suitability: CE marking | Yes |
|---|---|
| certificate of suitability: UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 |
| certificate of suitability: UKCA marking | Yes |
| certificate of suitability: EAC approval | Yes |
| certificate of suitability: Regulatory Compliance Mark (RCM) | Yes |
| certificate of suitability: NEC Class 2 | No |
| certificate of suitability: SEMI F47 | Yes |
| type of certification: BIS | Yes; R-41183539 |
| type of certification: CB-certificate | Yes |
| certificate of suitability: IECEx | No |
|---|---|
| certificate of suitability: ATEX | No |
| certificate of suitability: ULhazloc approval | No |
| certificate of suitability: FM registration | No |
| shipbuilding approval | Yes |
|---|---|
| Marine classification association: American Bureau of Shipping Europe Ltd. (ABS) | Yes |
| Marine classification association: French marine classification society (BV) | No |
| Marine classification association: Det Norske Veritas (DNV) | Yes |
| Marine classification association: Lloyds Register of Shipping (LRS) | No |
| Environmental Product Declaration | Yes |
|---|---|
| global warming potential [CO2 eq]: total | 1 067.6 kg |
| global warming potential [CO2 eq]: during manufacturing | 53.9 kg |
| global warming potential [CO2 eq]: during operation | 1 012.1 kg |
| global warming potential [CO2 eq]: after end of life | 0.89 kg |
| Siemens eco profile (SEP) | Siemens EcoTech |
| ambient temperature: during operation | -30 ... +70 °C; with natural convection a monotonically increasing start-up from -25 °C, safe start-up from -40 °C |
|---|---|
| ambient temperature: during transport | -40 ... +85 °C |
| ambient temperature: during storage | -40 ... +85 °C |
| environmental category according to IEC 60721 | Climate class 3K3, 5 ... 95% no condensation |
| type of electrical connection | push-in terminals |
|---|---|
| at input | L1, L2, L3, PE: push-in for 0.5 ... 10 mm2 |
| at output | +1, +2, -1, -2, -3: push-in for 0.75 ... 16 mm2 |
| for auxiliary contacts | 13, 14 (alarm signal): 1 push-in terminal each for 0.2 ... 1.5 mm2 |
| width × height × depth of the enclosure | 95 × 135 × 155 mm |
|---|---|
| installation width × mounting height | 95 mm × 225 mm |
| required spacing: top | 45 mm |
| required spacing: bottom | 45 mm |
| required spacing: left | 0 mm |
| required spacing: right | 0 mm |
| fastening method | Snaps onto DIN rail EN 60715 35x7.5/15 |
| DIN-rail mounting | Yes |
| S7 rail mounting | No |
| wall mounting | No |
| housing can be lined up | Yes |
| electrical accessories | Buffer module, redundancy module |
|---|---|
| mechanical accessories | Identification labels SIMATIC ET 200SP 6ES7193-6LF30-0AW0 |
| identification link | Yes; acc. to IEC 61406-1:2022 |
|---|
| other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
|---|
| Environmental Product Declaration: global warming potential [CO2 eq] / during manufacturing | 53.9 kg |
|---|
| Net weight | 1.7 kg |
|---|---|
| Package dimensions | 187 × 214 × 126 mm |
| Country of origin | Romania |
| Shipping weight | 2.2 kg |
| Ships from | Türkiye |
| Dispatch | 13 Nov |
| Stock | Low stock |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of PSU6200 is 40 A.
The rated operational voltage of PSU6200 is 400–500 V AC.
The rated motor power of PSU6200 is 0.96 kW.
The tariff (HS) code on file for PSU6200 is 85044083.
The EAN (GTIN) of PSU6200 is 4025515155362.
PSU6200 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.