Part number
6EP3337-8SB00-0AY0
Model no
PSU8200
$595.13 Low stock Dispatch Planned dispatch date. We aim to ship within 1 business day. Depending on warehouse workload it can take 2–3 business days. · From Türkiye
SITOP PSU8200

Siemens 6EP3337-8SB00-0AY0 SITOP PSU8200 24V DC 40A Stabilized Power Supply

SITOP PSU8200 stabilized power supply, 120/230V AC input, 24V DC/40A output, 960W.

Rated current
40 A
Rated operational voltage
120–230 V AC
Motor power
0.96 (960 W rated output) kW
Display
LED indicators (24V OK, overload, short-circuit)
EAN
4025515154747
Description

About the PSU8200

Siemens 6EP3337-8SB00-0AY0 is a SITOP PSU8200 stabilized power supply that converts 120/230 V AC input into a regulated 24 V DC output rated at 40 A (960 W), with output voltage adjustable from 24 to 28 V via potentiometer. It provides galvanic isolation, short-circuit protection, and 25 ms buffering on mains loss.

Certifications & Standards

  • CE
  • EAC
  • RCM
  • CB
  • Shipbuilding
  • ABS
  • DNV
  • EPD

Selection Notes

The 40 A / 960 W rating and adjustable 24-28 V output place this near the top of the PSU8200 power range for a single unit; two units can be paralleled to raise available power further, which matters when a cabinet's DC bus needs headroom beyond 960 W without moving to a different frame size. The 25 ms buffering time and SELV isolation make it appropriate as the primary 24 V bus feed for PLC and I/O loads rather than a battery-backed branch, since no energy storage is built into the unit itself.

Applications

Primary 24 V DC bus supply for automation cabinets with high load current such as drives, I/O racks, and relay banks; marine and offshore panels covered by ABS/DNV shipbuilding approval; and parallel-redundant power architectures for critical 24 V loads.

Specification

Full specification

140 values · Last verified 01 Nov 2026

General information 4

product brand name SITOP
product type designation PSU8200
product designation Power supply SITOP modular
type of current supply 24 V/40 A

Input 19

type of the power supply network 1-phase and 2-phase AC
phase number 1
voltage curve at input AC
supply voltage at AC Automatic selection; startup starting from Ue ≥ 90/180 V
supply voltage 120 V/230 V
input voltage 1 at AC 85 ... 132 V
input voltage 2 at AC 170 ... 264 V
supply voltage: at 50 Hz 230 V
supply voltage: at 60 Hz 120 V
line frequency 50/60 Hz
wide range input No
buffering time for rated value of the output current in the event of power failure minimum 25 ms
operating condition of the mains buffering at Vin = 230 V
input current: at rated input voltage 120 V 15 A
input current: at rated input voltage 230 V 9 A
current limitation of inrush current at 25 °C maximum 50 A
I2t value maximum 8 A2·s
fuse protection type Yes
fuse protection type in the feeder Recommended miniature circuit breaker at 1-phase operation: 16 A characteristic C; required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2421-4BA10 (120 V) or 3RV2411-1JA10 (230 V)

Output 29

voltage curve at output Controlled, isolated DC voltage
product function output voltage controlled Yes
product function output voltage stabilized Yes
output voltage at DC rated value 24 V
output voltage: at output 1 at DC rated value 24 V
output voltage: at output 1 at DC 24 V
output voltage adjustable Yes; via potentiometer
adjustable output voltage 24 ... 28 V; max. 960 W
relative overall tolerance of the voltage 3%
relative control precision of the output voltage: on slow fluctuation of input voltage 0.1 %
residual ripple: maximum 100 mV
residual ripple: typical 50 mV
voltage peak: maximum 240 mV
voltage peak: typical 220 mV
display version for normal operation Green LED for 24 V OK; LED yellow for overload; LED red for short-circuit or latching shutdown
type of signal at output Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"
behavior of the output voltage when switching on Overshoot of Vout approx. 3 %
response delay maximum 1.5 s
voltage increase time of the output voltage: typical 30 ms
output current: rated value 40 A
output current: rated range 0 ... 40 A; +60 ... +70 °C: Derating 3%/K
supplied active power typical 960 W
short-term overload current: on short-circuiting during the start-up typical 120 A
short-term overload current: at short-circuit during operation typical 120 A
duration of overloading capability for excess current: on short-circuiting during the start-up 25 ms
duration of overloading capability for excess current: at short-circuit during operation 25 ms
constant overload current: on short-circuiting during the start-up typical 60 A
bridging of equipment Yes; switchable characteristic
number of parallel-switched equipment resources for increasing the power 2
Show all 140 specifications ↓ Show less ↑88 more values in Identification, Efficiency, Closed-loop control, Protection and monitoring, Safety, EMC, Standards, specifications, approvals, Standards, specifications, approvals hazardous environments, Standards, specifications, approvals marine classification, Standards, specifications, approvals Environmental Product Declaration, Ambient conditions, Connection method, Mechanical data, Accessories, Additional information, Approvals Certificates, Logistics.

Identification 10

Part number 6EP3337-8SB00-0AY0
Type designation PSU8200
Brand Siemens
Condition New, factory sealed
Source Siemens and its authorised distributors
Warranty Manufacturer warranty
Lifecycle status Active, in production
EAN 4025515154747
ETIM class EC002540
eCl@ss 27040701

Efficiency 3

efficiency in percent 92 %
power loss [W]: at rated output voltage for rated value of the output current typical 82 W
power loss [W]: during no-load operation maximum 6.8 W

Closed-loop control 8

relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical 1%
relative control precision of the output voltage load step of resistive load 50/100/50 % typical 1.9 %
setting time: load step 50 to 100% typical 2 ms
setting time: load step 100 to 50% typical 2 ms
relative control precision of the output voltage at load step of resistive load 10/90/10 % typical 3.8 %
setting time: load step 10 to 90% typical 1 ms
setting time: load step 90 to 10% typical 1 ms
setting time: maximum 1 ms

Protection and monitoring 7

design of the overvoltage protection < 32 V
property of the output short-circuit proof Yes
design of short-circuit protection Alternatively, constant current characteristic approx. 41 A or latching shutdown
typical 41 A
overcurrent overload capability: in normal operation 250% Iout rated up to 25 ms, 150% Iout rated up to 5 s/min
enduring short circuit current RMS value: typical 41 A
display version for overload and short circuit LED yellow for "overload", LED red for "latching shutdown" or "short-circuit"

Safety 6

galvanic isolation between input and output Yes
galvanic isolation Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7)
operating resource protection class Class I
leakage current: maximum 0.1 mA
leakage current: typical 0.1 mA
protection class IP IP20

EMC 3

standard: for emitted interference EN 55022 Class B
standard: for mains harmonics limitation -
standard: for interference immunity EN 61000-6-2

Standards, specifications, approvals 8

certificate of suitability: CE marking Yes
certificate of suitability: UL approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
certificate of suitability: EAC approval Yes
certificate of suitability: Regulatory Compliance Mark (RCM) Yes
certificate of suitability: NEC Class 2 No
type of certification: BIS Yes; R-41183539
type of certification: CB-certificate Yes
MTBF at 40 °C 838 156 h

Standards, specifications, approvals hazardous environments 4

certificate of suitability: IECEx No
certificate of suitability: ATEX No
certificate of suitability: ULhazloc approval No
certificate of suitability: FM registration No

Standards, specifications, approvals marine classification 5

shipbuilding approval Yes
Marine classification association: American Bureau of Shipping Europe Ltd. (ABS) Yes
Marine classification association: French marine classification society (BV) No
Marine classification association: Det Norske Veritas (DNV) Yes
Marine classification association: Lloyds Register of Shipping (LRS) No

Standards, specifications, approvals Environmental Product Declaration 5

Environmental Product Declaration Yes
global warming potential [CO2 eq]: total 2 152.1 kg
global warming potential [CO2 eq]: during manufacturing 74.1 kg
global warming potential [CO2 eq]: during operation 2 076.5 kg
global warming potential [CO2 eq]: after end of life 0.62 kg

Ambient conditions 4

ambient temperature: during operation -25 ... +70 °C; with natural convection
ambient temperature: during transport -40 ... +85 °C
ambient temperature: during storage -40 ... +85 °C
environmental category according to IEC 60721 Climate class 3K3, 5 ... 95% no condensation

Connection method 4

type of electrical connection screw terminal
at input L, N, PE: 1 screw terminal each for 0.2 ... 4 mm2 single-core/finely stranded
at output +, -: 2 screw terminals each for 0.5 ... 10 mm2
for auxiliary contacts 13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm2

Mechanical data 11

width × height × depth of the enclosure 145 × 145 × 150 mm
installation width × mounting height 150 mm × 225 mm
required spacing: top 40 mm
required spacing: bottom 40 mm
required spacing: left 0 mm
required spacing: right 0 mm
fastening method Snaps onto DIN rail EN 60715 35x15
DIN-rail mounting Yes
S7 rail mounting No
wall mounting No
housing can be lined up Yes

Accessories 2

electrical accessories Buffer module, redundancy module
mechanical accessories Device identification label 20 mm × 7 mm, TI-grey 3RT2900-1SB20

Additional information 1

other information Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

Approvals Certificates 1

Environmental Product Declaration: global warming potential [CO2 eq] / during manufacturing 74.1 kg

Logistics 6

Net weight 3.1 kg
Country of origin Romania
Shipping weight 3.6 kg
Ships from Türkiye
Dispatch 13 Nov
Stock Low stock

Source: manufacturer data · Last verified: 01 Nov 2026

Documents

Documents for 6EP3337-8SB00-0AY0

No documents are on file for this part yet.

Ask us for the datasheet
Certifications

Certifications and standards

  • DNV
  • CE marking
  • EAC approval
  • Regulatory Compliance Mark (RCM)
  • CB-certificate
  • shipbuilding approval
  • American Bureau of Shipping Europe Ltd. (ABS)
  • Det Norske Veritas (DNV)
  • Environmental Product Declaration
Quick answers

Questions about the PSU8200

What is the rated current of PSU8200?

The rated current of PSU8200 is 40 A.

Which supply voltage is PSU8200 rated for?

The rated operational voltage of PSU8200 is 120–230 V AC.

What motor power is PSU8200 rated for?

The rated motor power of PSU8200 is 0.96 (960 W rated output) kW.

What is the HS code of PSU8200 for customs?

The tariff (HS) code on file for PSU8200 is 85044083.

What is the EAN of PSU8200?

The EAN (GTIN) of PSU8200 is 4025515154747.

Where does PSU8200 ship from, and how fast?

PSU8200 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.

Guides

Guides for power supplies

All guides for power supplies
Reviews

Customer reviews

Series

Siemens SITOP PSU8200

Brand
Siemens
Series
SITOP PSU8200
$595.13 Low stock · 13 Nov
Quote

Get a Quote

PSU8200

Genuine parts

Genuine, factory-sealed parts

Siemens · 6EP3337-8SB00-0AY0

Every part on Stoklink is new, unused and made by the manufacturer named on the page.

Condition
New and unused, in the manufacturer's factory-sealed packaging.
Sourced from
Siemens and its authorised distributors.
Warranty
The manufacturer's warranty applies.
If a part is not genuine
We refund the full amount.

Added to cart Could not add to cart