The Siemens 6EP3322-6SB10-0AY0 LOGO!Power supply converts a 100-240 V AC (or 110-300 V DC) wide-range input into a stabilized, adjustable 15 V DC output rated at 4 A. It reaches 88.4% efficiency, provides 40 ms buffering time on power loss, and snaps onto a 35 mm DIN rail in an IP20, Class II enclosure for direct control-cabinet mounting.
The output voltage is adjustable from 10.5 to 16.1 V via an onboard potentiometer, so this unit covers applications that need slightly above or below the nominal 15 V rail, not just a fixed 15 V. It supports parallel operation of up to two units to increase available power, which matters if a load exceeds the single-unit 60 W rating. The 40 ms power-loss buffering time is a spec to check against downstream PLC or relay hold-in requirements before assuming ride-through on brief mains dips.
Sized for LOGO! logic modules and small 15 V DC loads such as relay coils, sensors, or signal circuits in control cabinets, machine builds, and building-automation panels where DIN-rail mounting and a wide 100-240 V AC input range are needed.
| product brand name | LOGO!Power |
|---|---|
| product type designation | LOGO!Power |
| product designation | Power supply LOGO!Power |
| type of current supply | 15 V/4 A |
| type of the power supply network | 1-phase AC or DC |
|---|---|
| phase number | 1 |
| voltage curve at input | AC/DC |
| supply voltage at AC: minimum rated value | 100 V |
| supply voltage at AC: maximum rated value | 240 V |
| supply voltage at AC: initial value | 85 V |
| supply voltage at AC: full-scale value | 264 V |
| input voltage at DC | 110 ... 300 V |
| supply voltage: at 50 Hz | 240 V |
| supply voltage: at 60 Hz | 100 V |
| line frequency | 50/60 Hz |
| wide range input | Yes |
| overvoltage overload capability | 300 V AC for 1 s |
| buffering time for rated value of the output current in the event of power failure minimum | 40 ms |
| operating condition of the mains buffering | at Vin = 187 V |
| input current: at rated input voltage 120 V | 1.24 A |
| input current: at rated input voltage 230 V | 0.68 A |
| current limitation of inrush current at 25 °C maximum | 55 A |
| I2t value maximum | 3 A2·s |
| fuse protection type | internal |
| fuse protection type in the feeder | Recommended miniature circuit breaker: from 10 A characteristic B or from 6 A characteristic C |
| voltage curve at output | Controlled, isolated DC voltage |
|---|---|
| product function output voltage controlled | Yes |
| product function output voltage stabilized | Yes |
| output voltage at DC rated value | 15 V |
| output voltage: at output 1 at DC rated value | 15 V |
| output voltage: at output 1 at DC | 15 V |
| output voltage adjustable | Yes; via potentiometer |
| adjustable output voltage | 10.5 ... 16.1 V |
| relative overall tolerance of the voltage | 3% |
| relative control precision of the output voltage: on slow fluctuation of input voltage | 0.1 % |
| residual ripple: maximum | 200 mV |
| residual ripple: typical | 30 mV |
| voltage peak: maximum | 300 mV |
| voltage peak: typical | 50 mV |
| display version for normal operation | Green LED for output voltage OK |
| behavior of the output voltage when switching on | No overshoot of Vout (soft start) |
| response delay maximum | 0.5 s |
| voltage increase time of the output voltage: typical | 100 ms |
| output current: rated value | 4 A |
| output current: rated range | 0 ... 4 A; +55 ... +70 °C: Derating 2%/K |
| supplied active power typical | 60 W |
| bridging of equipment | Yes |
| number of parallel-switched equipment resources for increasing the power | 2 |
| Part number | 6EP3322-6SB10-0AY0 |
|---|---|
| Type designation | LOGO!Power |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4025515154839 |
| ETIM class | EC002540 |
| eCl@ss | 27040701 |
| efficiency in percent | 88.4 % |
|---|---|
| power loss [W]: at rated output voltage for rated value of the output current typical | 7.9 W |
| power loss [W]: during no-load operation maximum | 0.3 W |
| relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical | 0.2 % |
|---|---|
| relative control precision of the output voltage at load step of resistive load 10/90/10 % typical | 3% |
| setting time: load step 10 to 90% typical | 1 ms |
| setting time: load step 90 to 10% typical | 1 ms |
| design of the overvoltage protection | < 60 V |
|---|---|
| property of the output short-circuit proof | Yes |
| design of short-circuit protection | Constant current characteristic |
| typical | 5 A |
| overcurrent overload capability: when switching on | 150% Iout rated typ. 200 ms |
| overcurrent overload capability: in normal operation | overload capability 150% Iout rated typ. 200 ms |
| enduring short circuit current RMS value: maximum | 5 A |
| measuring point for output current | Yes; 45 mV =^ 4 A |
| electrical separation between input and output | Yes |
|---|---|
| galvanic isolation | Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7) |
| operating resource protection class | Class II (without protective conductor) |
| protection class IP | IP20 |
| standard: for emitted interference | EN 55022 Class B |
|---|---|
| standard: for mains harmonics limitation | not applicable |
| standard: for interference immunity | EN 61000-6-2 |
| certificate of suitability: CE marking | Yes |
|---|---|
| certificate of suitability: UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus- Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310) |
| certificate of suitability: EAC approval | Yes |
| certificate of suitability: NEC Class 2 | Yes; according to UL1310, File E151273 |
| certificate of suitability: SEMI F47 | Yes |
| type of certification: CB-certificate | Yes |
| MTBF at 40 °C | 2 566 680 h |
| certificate of suitability: IECEx | No |
|---|---|
| certificate of suitability: ATEX | No |
| certificate of suitability: ULhazloc approval | No |
| certificate of suitability: FM registration | No |
| shipbuilding approval | Yes |
|---|---|
| Marine classification association: American Bureau of Shipping Europe Ltd. (ABS) | Yes |
| Marine classification association: French marine classification society (BV) | Yes |
| Marine classification association: Det Norske Veritas (DNV) | Yes |
| Marine classification association: Lloyds Register of Shipping (LRS) | Yes |
| Environmental Product Declaration | Yes |
|---|---|
| global warming potential [CO2 eq]: total | 220 kg |
| global warming potential [CO2 eq]: during manufacturing | 3.8 kg |
| global warming potential [CO2 eq]: during operation | 216 kg |
| global warming potential [CO2 eq]: after end of life | 0.14 kg |
| Siemens eco profile (SEP) | Siemens EcoTech |
| ambient temperature: during operation | -25 ... +70 °C; with natural convection |
|---|---|
| ambient temperature: during transport | -40 ... +85 °C |
| ambient temperature: during storage | -40 ... +85 °C |
| environmental category according to IEC 60721 | Climate class 3K3, 5 ... 95% no condensation |
| type of electrical connection | screw terminal |
|---|---|
| at input | L, N: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded |
| at output | +, -: 1 screw terminal each for 0.5 ... 2.5 mm2 |
| for auxiliary contacts | - |
| width × height × depth of the enclosure | 54 × 90 × 53 mm |
|---|---|
| installation width × mounting height | 54 mm × 130 mm |
| required spacing: top | 20 mm |
| required spacing: bottom | 20 mm |
| required spacing: left | 0 mm |
| required spacing: right | 0 mm |
| fastening method | Snaps onto DIN rail EN 60715 35x7.5/15, direct mounting in different mounting positions |
| DIN-rail mounting | Yes |
| S7 rail mounting | No |
| wall mounting | Yes |
| housing can be lined up | Yes |
| other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
|---|
| Environmental Product Declaration: global warming potential [CO2 eq] / during manufacturing | 3.8 kg |
|---|
| Net weight | 0.2 kg |
|---|---|
| Country of origin | Romania |
| Shipping weight | 0.7 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of LOGO!Power is 4 A.
The rated operational voltage of LOGO!Power is 100–240 V AC.
The rated motor power of LOGO!Power is 7.9 W kW.
The tariff (HS) code on file for LOGO!Power is 85044083.
The EAN (GTIN) of LOGO!Power is 4025515154839.
LOGO!Power ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.