Main Components of a PLC System: Complete Guide for Engineers
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.
Once production ends, supply depends on remaining stock.
No replacement announced yet. Tell us the application and we will propose an alternative.
SITOP pure lead-acid battery module, 24V/2.5Ah, -40 to 60C, for SITOP DC UPS 6A/15A.
The Siemens 6EP1935-6MD31 is a SITOP pure lead-acid battery module rated 24 V DC / 2.5 Ah, sized for the SITOP DC UPS 6 A and 15 A modules. Unlike the standard lead-acid modules in the family, its pure-lead cells tolerate -40...+60 degC and supply up to 15 A in buffering mode and 15 A peak.
Pick this pure-lead 2.5 Ah module over the standard 3.2 Ah lead-acid module when ambient temperature swings beyond the -15...+50 degC range that standard lead-acid cells tolerate, since pure lead extends operation down to -40 degC and up to +60 degC. Its 5 A maximum charging current is also higher than the standard modules', which shortens recharge time after a discharge event. The typical service life reaches 10 years at 20 degC versus 4 years for the standard lead-acid modules, though it still falls to about 1 year at 60 degC, so replacement planning should follow the actual site temperature.
| product brand name | SITOP |
|---|---|
| product type designation | Battery module |
| product designation | Battery module 2.5 Ah |
| type of battery | maintenance-free pure lead batteries |
| product version | Extension module/battery module |
| end-of-charge voltage at DC: at -10 °C recommended | 29 V |
|---|---|
| end-of-charge voltage at DC: at 0 °C recommended | 28.6 V |
| end-of-charge voltage at DC: at 20 °C recommended | 27.9 V |
| end-of-charge voltage at DC: at 30 °C recommended | 27.5 V |
| end-of-charge voltage at DC: at 40 °C recommended | 27.2 V |
| end-of-charge voltage at DC: at 50 °C recommended | 26.8 V |
| end-of-charge voltage at DC: at 60 °C recommended | 26.4 V |
| battery capacity | 2.5 A·h |
|---|---|
| output current in buffering mode maximum | 15 A |
| peak current | 15 A |
| charging current maximum | 5 A |
| output voltage at DC rated value | 24 V |
| Part number | 6EP1935-6MD31 |
|---|---|
| Type designation | Battery module |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Phase-out announced by the manufacturer |
| EAN | 4025515150510 |
| ETIM class | EC000357 |
| eCl@ss | 27050403 |
| communication function | No |
|---|
| design of short-circuit protection | Battery fuse 15 A/32 V (solid-state circuitry blade-type fuse + support) |
|---|---|
| design of the overload protection | Valve control |
| operating resource protection class | Class III |
|---|---|
| protection class IP | IP00 |
| certificate of suitability: CE marking | Yes |
|---|---|
| certificate of suitability: UL approval | Yes; cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627 |
| certificate of suitability: EAC approval | Yes |
| certificate of suitability: ATEX | No |
|---|
| shipbuilding approval | Yes |
|---|---|
| Marine classification association: American Bureau of Shipping Europe Ltd. (ABS) | Yes |
| Marine classification association: Det Norske Veritas (DNV) | Yes |
| Environmental Product Declaration | Yes |
|---|---|
| global warming potential [CO2 eq]: total | 13.182 kg |
| global warming potential [CO2 eq]: during manufacturing | 9.579 kg |
| global warming potential [CO2 eq]: during operation | 2.021 kg |
| global warming potential [CO2 eq]: after end of life | 0.376 kg |
| ambient condition | For storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away. |
|---|---|
| ambient temperature: during operation | -40 ... +60 °C |
| ambient temperature: during transport | -40 ... +60 °C |
| ambient temperature: during storage | -40 ... +60 °C |
| relative temporary capacity loss at 20 °C in a month typical | 3% |
| service life of energy storage: typical | capacity falls to 80 % of original capacity (according to EUROBAT) |
|---|---|
| service life of energy storage: at 20 °C typical | 10 a |
| service life of energy storage: at 30 °C typical | 7 a |
| service life of energy storage: at 40 °C typical | 3 a |
| service life of energy storage: at 50 °C typical | 1.5 a |
| service life of energy storage: at 60 °C typical | 1 a |
| note | Along with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C. |
| type of electrical connection | spring-loaded terminals |
|---|---|
| for UPS module | 1 screw terminal each for 0.08 ... 2.5 mm2 for + BAT and - BAT |
| width × height × depth of the enclosure | 265 × 151 × 91 mm |
|---|---|
| installation width × mounting height | 285 mm × 171 mm |
| fastening method | snaps onto DIN rail EN 60715 35x15 or keyhole mounting for hooking in to M4 screws |
| DIN-rail mounting | Yes |
| S7 rail mounting | No |
| wall mounting | Yes |
| number of cells | 12 |
| product component included | Accessories pack with solid-state circuitry fuse 15 A |
|---|
| other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
|---|
| eClass | 16 27-05-04-03 |
|---|---|
| ETIM | 10 EC000357 |
| UNSPSC | 15 26-11-17-01 |
| Net weight | 3.8 kg |
|---|---|
| Country of origin | Austria |
| Shipping weight | 4.3 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of Battery module is 15 A.
The tariff (HS) code on file for Battery module is 85072080.
The EAN (GTIN) of Battery module is 4025515150510.
Battery module ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.