Main Components of a PLC System: Complete Guide for Engineers
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.
Once production ends, supply depends on remaining stock.
No replacement announced yet. Tell us the application and we will propose an alternative.
SITOP DC UPS module, 24V DC / 15A output, serial interface, 96.2% efficiency, IP20.
The Siemens 6EP1931-2EC31 is a SITOP DC UPS module rated 24 V DC / 15 A output, drawing 22...29 V DC / 16 A at the input, that bridges mains power cuts with a connected battery module. It reaches 96.2% efficiency at rated output and adds a serial interface for status and configuration on top of floating relay contacts.
This is the 15 A member of the SITOP DC UPS family with a serial interface, useful where the supervising controller already polls status over RS-232/RS-485 instead of USB. Choose the USB-interface 15 A variant if the host is a PC, or the 6 A or 40 A variants in the same family when the load current differs. The 96.2% efficiency and 14 W power loss at rated output keep enclosure heat load low compared to the 6 A module scaled up, and the 1 s startup delay should be accounted for when sequencing downstream 24 V loads.
Bridges the 24 V DC control supply for PLCs, remote I/O, and HMI panels through short mains interruptions until standby generators start or the supply recovers, using a separately ordered battery module for energy storage.
| product brand name | SITOP |
|---|---|
| product type designation | DC UPS |
| type of current supply | DC UPS 24 V/15 A |
| voltage curve at input | DC |
|---|---|
| supply voltage at DC rated value | 24 V |
| input voltage at DC | 22 ... 29 V |
| adjustable response value voltage for buffer connection preset | 22.5 V |
| adjustable response value voltage for buffer connection | 22 ... 25.5 V; Adjustable in 0.5 V increments |
| input current at rated input voltage 24 V rated value | 15 A; + approx. 1 A with empty battery |
| type of energy storage | with batteries |
|---|---|
| product function DC-UPS modularly expandable | Yes |
| design of the mains power cut bridging-connection | Dependent on connected battery and load current, see selection table battery module and mains buffering times as well as the relevant important information notes! |
| Part number | 6EP1931-2EC31 |
|---|---|
| Type designation | DC UPS |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Phase-out announced by the manufacturer |
| EAN | 4025515151050 |
| ETIM class | EC000382 |
| eCl@ss | 27040705 |
| output voltage: in normal operation at DC rated value | 24 V |
|---|---|
| output voltage: in buffering mode at DC rated value | 24 V |
| formula for output voltage | Vin - approx. 0.5 V |
| startup delay time typical | 1 s |
| voltage increase time of the output voltage typical | 60 ms |
| output voltage in buffering mode at DC | 19 ... 28.5 V |
| output current: rated value | 15 A |
| output current: in normal operation | 0 ... 15 A |
| output current: in buffering mode | 0 ... 15 A |
| peak current | 15.7 A |
| property of the output short-circuit proof | Yes |
| charging current | 0.35 A, 0.7 A |
| efficiency in percent: at rated output voltage for rated value of the output current typical | 96.2 % |
|---|---|
| efficiency in percent: in case of operation on rechargeable battery typical | 96 % |
| power loss [W]: at rated output voltage for rated value of the output current typical | 14 W |
| power loss [W]: in case of operation on rechargeable battery typical | 15 W |
| supplied active power typical | 360 W |
| product function: reverse polarity protection against energy storage unit polarity reversal | Yes |
|---|---|
| product function: reverse polarity protection against input voltage polarity reversal | Yes |
| display version: for normal operation | Normal operation: LED green (OK), floating changeover contact "Bat/OK" to setting "OK" ("OK" means: Voltage of the supplying power supply unit is greater than cut-in threshold set at the DC UPS module); Lack of buffer standby: LED red (alarm), floating changeover contact "Alarm/Bat" to setting "Alarm"; Battery replacement required: LED red (alarm) flashing with approx. 0.25 Hz, floating changeover contact "Alarm/Bat" switching with approx. 0.25 Hz; Energy storage > 85%: LED green (Bat > 85%), floating NOcontact "Bat > 85" closed; Permissible contact current capacity: DC 60 V/1 A or AC 30 V /1 A |
| display version: in buffering mode | Buffered mode: LED yellow (Bat), floating changeover contact "OK/Bat" to setting "Bat"; Prewarning battery voltage 85%: LED green (Bat > 85%), floating NO contact "Bat > 85" closed |
| product component PC interface | Yes |
|---|---|
| product function communication function | No |
| design of the interface | serial |
| electrical separation between input and output | No |
|---|---|
| operating resource protection class | Class III |
| protection class IP | IP20 |
| standard: for emitted interference | EN 55022 Class B |
| standard: for interference immunity | EN 61000-6-2 |
| certificate of suitability: CE marking | Yes |
|---|---|
| certificate of suitability: UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 |
| certificate of suitability: EAC approval | Yes |
| MTBF at 40 °C | 725 689 h |
| shipbuilding approval | Yes |
|---|---|
| Marine classification association: American Bureau of Shipping Europe Ltd. (ABS) | Yes |
| Marine classification association: Det Norske Veritas (DNV) | Yes |
| Environmental Product Declaration | Yes |
|---|---|
| global warming potential [CO2 eq]: total | 399.2 kg |
| global warming potential [CO2 eq]: during manufacturing | 18.5 kg |
| global warming potential [CO2 eq]: during operation | 380.3 kg |
| global warming potential [CO2 eq]: after end of life | 0.34 kg |
| ambient temperature: during operation | -25 ... +60 °C; with natural convection |
|---|---|
| ambient temperature: during transport | -40 ... +85 °C |
| ambient temperature: during storage | -40 ... +85 °C |
| environmental category according to IEC 60721 | Climate class 3K3, 5 ... 95% no condensation |
| type of electrical connection | screw terminal |
|---|---|
| at input | 24 V DC: 2 screw terminals for 1 ... 4 mm2/17 ... 11 AWG |
| at output | 24 V DC: 4 screw terminals for 1 ... 4 mm2/17 ... 11 AWG |
| for rechargeable battery module | 24 V DC: 2 screw terminals for 1 ... 4 mm2/17 ... 11 AWG |
| for control circuit and status message | 10 screw terminals for 0.5 ... 2.5 mm2/20 ... 13 AWG |
| width × height × depth of the enclosure | 50 × 125 × 125 mm |
|---|---|
| installation width × mounting height | 50 mm × 225 mm |
| required spacing: top | 50 mm |
| required spacing: bottom | 50 mm |
| required spacing: left | 0 mm |
| required spacing: right | 0 mm |
| fastening method | Snaps onto DIN rail EN 60715 35x7.5/15 |
| DIN-rail mounting | Yes |
| S7 rail mounting | No |
| wall mounting | No |
| housing can be lined up | Yes |
| electrical accessories | Battery module |
|---|
| other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
|---|
| Net weight | 0.45 kg |
|---|---|
| Country of origin | Romania |
| Shipping weight | 0.95 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of DC UPS is 15 A.
The rated operational voltage of DC UPS is 24 V AC.
The rated motor power of DC UPS is 96.2 % kW.
The tariff (HS) code on file for DC UPS is 85044060.
The EAN (GTIN) of DC UPS is 4025515151050.
DC UPS ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.