Part number
6EP1433-0AA00
Model no
PSU300E
$293.94 On request Dispatch — · From TürkiyeGet a Quote
SITOP PSU300E

Siemens 6EP1433-0AA00 SITOP PSU300E 3AC 400-500V 24V/5A DIN Rail Power Supply

SITOP PSU300E 3-phase 400-500V AC to 24V/5A DIN rail power supply, adjustable output.

Rated current
5 A
Rated operational voltage
400–500 V AC
Motor power
13 W kW
Display
Green LED for 24 V OK
EAN
4025515153412
Description

About the PSU300E

The Siemens 6EP1433-0AA00 is a SITOP PSU300E three-phase power supply that converts 400-500 V AC into a stabilized 24 V DC output rated 5 A (120 W). It mounts on a 42 mm-wide DIN rail, holds the output adjustable from 24 to 29 V via potentiometer, and bridges a 50 ms mains dropout at rated load, suited to 24 V loads fed directly from a 400 V three-phase distribution board.

Certifications & Standards

  • CE
  • EAC

Selection Notes

The 6EP1433-0AA00 draws directly from a 3-phase 400-500 V distribution board rather than the single-phase 100-230 V input used by the SITOP PSU100 series, which matters where the panel already has three-phase power and a single-phase tap would add wiring. Output is adjustable to 29 V (up to 120 W) via potentiometer, useful for compensating voltage drop on a long 24 V run or lifting the set point for downstream equipment specifying a slightly higher supply. No internal input fuse is fitted, so the recommended external protection, a 6 A characteristic B or C miniature circuit breaker or an equivalent motor-protective circuit breaker, must be installed in the feeder for the unit to be protected against an upstream fault.

Specification

Full specification

126 values · Last verified 01 Nov 2026

General information 4

product brand name SITOP
product type designation PSU300E
product designation Power supply SITOP
type of current supply 24 V/5 A

Input 19

type of the power supply network 3-phase AC
phase number 3
voltage curve at input AC
supply voltage at AC: minimum rated value 400 V
supply voltage at AC: maximum rated value 500 V
supply voltage at AC: initial value 320 V
supply voltage at AC: full-scale value 550 V
supply voltage: at 50 Hz 400 V
supply voltage: at 60 Hz 500 V
line frequency 50/60 Hz
wide range input Yes
buffering time for rated value of the output current in the event of power failure minimum 50 ms
operating condition of the mains buffering at Vin = 400 V
input current: at rated input voltage 400 V 0.36 A
input current: at rated input voltage 500 V 0.29 A
current limitation of inrush current at 25 °C maximum 15 A
I2t value maximum 0.9 A2·s
fuse protection type none
fuse protection type in the feeder Required: 3-pole connected miniature circuit breaker 6 A characteristic B or C or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489)

Output 28

voltage curve at output Controlled, isolated DC voltage
product function output voltage controlled Yes
product function output voltage stabilized Yes
output voltage at DC rated value 24 V
output voltage: at output 1 at DC rated value 24 V
output voltage: at output 1 at DC 24 V
output voltage adjustable Yes; via potentiometer
adjustable output voltage 24 ... 29 V; max. 120 W
relative overall tolerance of the voltage 3%
relative control precision of the output voltage: on slow fluctuation of input voltage 3%
residual ripple: maximum 150 mV
residual ripple: typical 35 mV
voltage peak: maximum 240 mV
voltage peak: typical 70 mV
display version for normal operation Green LED for 24 V OK
type of signal at output Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"
behavior of the output voltage when switching on Overshoot of Vout approx. 3 %
response delay maximum 0.5 s
voltage increase time of the output voltage: typical 10 ms
voltage increase time of the output voltage: maximum 100 ms
output current: rated value 5 A
output current: rated range 0 ... 5 A
supplied active power typical 120 W
short-term overload current: on short-circuiting during the start-up typical 33 A
short-term overload current: at short-circuit during operation typical 28 A
duration of overloading capability for excess current: on short-circuiting during the start-up 140 ms
duration of overloading capability for excess current: at short-circuit during operation 135 ms
bridging of equipment No
Show all 126 specifications ↓ Show less ↑75 more values in Identification, Efficiency, Closed-loop control, Protection and monitoring, Safety, EMC, Standards, specifications, approvals, Standards, specifications, approvals hazardous environments, Standards, specifications, approvals marine classification, Ambient conditions, Connection method, Mechanical data, Additional information, Logistics.

Identification 10

Part number 6EP1433-0AA00
Type designation PSU300E
Brand Siemens
Condition New, factory sealed
Source Siemens and its authorised distributors
Warranty Manufacturer warranty
Lifecycle status Active, in production
EAN 4025515153412
ETIM class EC002540
eCl@ss 27040701

Efficiency 2

efficiency in percent 90 %
power loss [W]: at rated output voltage for rated value of the output current typical 13 W

Closed-loop control 8

relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical 3%
relative control precision of the output voltage load step of resistive load 50/100/50 % typical 5%
setting time: load step 50 to 100% typical 1 ms
setting time: load step 100 to 50% typical 1 ms
relative control precision of the output voltage at load step of resistive load 10/90/10 % typical 1%
setting time: load step 10 to 90% typical 1 ms
setting time: load step 90 to 10% typical 1 ms
setting time: maximum 30 ms

Protection and monitoring 5

design of the overvoltage protection < 60 V
property of the output short-circuit proof Yes
design of short-circuit protection Electronic shutdown, automatic restart
typical 11 A
enduring short circuit current RMS value: maximum 7.5 A

Safety 4

electrical separation between input and output Yes
galvanic isolation Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7)
operating resource protection class Class I
protection class IP IP20

EMC 3

standard: for emitted interference EN 55022 Class A
standard: for mains harmonics limitation EN 61000-3-2
standard: for interference immunity EN 61000-6-2

Standards, specifications, approvals 6

certificate of suitability: CE marking Yes
certificate of suitability: UL approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
certificate of suitability: EAC approval Yes
certificate of suitability: NEC Class 2 No
type of certification: CB-certificate No
MTBF at 40 °C 2 389 441 h

Standards, specifications, approvals hazardous environments 4

certificate of suitability: IECEx No
certificate of suitability: ATEX No
certificate of suitability: ULhazloc approval No
certificate of suitability: FM registration No

Standards, specifications, approvals marine classification 5

shipbuilding approval No
Marine classification association: American Bureau of Shipping Europe Ltd. (ABS) No
Marine classification association: French marine classification society (BV) No
Marine classification association: Det Norske Veritas (DNV) No
Marine classification association: Lloyds Register of Shipping (LRS) No

Ambient conditions 4

ambient temperature: during operation 0 ... 60 °C; with natural convection
ambient temperature: during transport -40 ... +85 °C
ambient temperature: during storage -40 ... +85 °C
environmental category according to IEC 60721 Climate class 3K3, 5 ... 95% no condensation

Connection method 6

type of electrical connection screw terminal
at input L1, L2, L3, PE: Removable screw terminal for 0.5 ... 2.5 mm2 single-core/finely stranded
at output +, -: 2 screw terminals each for 0.5 ... 2.5 mm2
for auxiliary contacts 13, 14 (alarm signal): 1 screw terminal each for 0.5 ... 2.5 mm2
removable terminal at input Yes
removable terminal at output Yes

Mechanical data 11

width × height × depth of the enclosure 42 × 125 × 125 mm
installation width × mounting height 42 mm × 225 mm
required spacing: top 50 mm
required spacing: bottom 50 mm
required spacing: left 0 mm
required spacing: right 0 mm
fastening method Snaps onto DIN rail EN 60715 35x7.5/15
DIN-rail mounting Yes
S7 rail mounting No
wall mounting No
housing can be lined up Yes

Additional information 1

other information Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

Logistics 6

Net weight 0.6 kg
Country of origin Romania
Shipping weight 1.1 kg
Ships from Türkiye
Dispatch —
Stock On request

Source: manufacturer data · Last verified: 01 Nov 2026

Documents

Documents for 6EP1433-0AA00

No documents are on file for this part yet.

Ask us for the datasheet
Certifications

Certifications and standards

  • CE
  • EAC
  • CE marking
  • EAC approval
Quick answers

Questions about the PSU300E

What is the rated current of PSU300E?

The rated current of PSU300E is 5 A.

Which supply voltage is PSU300E rated for?

The rated operational voltage of PSU300E is 400–500 V AC.

What motor power is PSU300E rated for?

The rated motor power of PSU300E is 13 W kW.

What is the HS code of PSU300E for customs?

The tariff (HS) code on file for PSU300E is 85044083.

What is the EAN of PSU300E?

The EAN (GTIN) of PSU300E is 4025515153412.

Where does PSU300E ship from, and how fast?

PSU300E ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.

Guides

Guides for power supplies

All guides for power supplies
Reviews

Customer reviews

Series

Siemens SITOP PSU300E

Brand
Siemens
Series
SITOP PSU300E
$293.94 On request
Get a Quote
Quote

Get a Quote

PSU300E

Genuine parts

Genuine, factory-sealed parts

Siemens · 6EP1433-0AA00

Every part on Stoklink is new, unused and made by the manufacturer named on the page.

Condition
New and unused, in the manufacturer's factory-sealed packaging.
Sourced from
Siemens and its authorised distributors.
Warranty
The manufacturer's warranty applies.
If a part is not genuine
We refund the full amount.

Added to cart Could not add to cart