Main Components of a PLC System: Complete Guide for Engineers
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.
The Siemens 6EP1333-7CA10 is a SITOP PSU100P power supply built for IP67 field mounting outside the control cabinet. It takes 120 V or 230 V AC with automatic range selection and delivers a stabilized 24 V DC output rated 5 A (133 W) through an M12 L-coded output connector, with a 7/8-inch input plug and a separate M12 alarm connector for the 24 V OK signal.
The IP67 rating and M12/7/8-inch plug connectors let the 6EP1333-7CA10 mount directly on a machine frame or outside a cabinet, where the DIN-rail and wall-mount SITOP models need an enclosure. At 5 A / 133 W it sits below the higher-current variant in the same connectorized PSU100P family, so it fits a single field device or a small distributed I/O drop rather than a full remote panel. The relay contact on the alarm connector reports the 24 V OK status without running a separate signal back to the control cabinet, and the 90% efficiency keeps self-heating low inside a sealed enclosure where convection cooling is limited.
| product brand name | SITOP |
|---|---|
| product type designation | PSU100P |
| product designation | Power supply SITOP |
| type of current supply | 24 V/5 A |
| type of the power supply network | 1-phase AC |
|---|---|
| phase number | 1 |
| voltage curve at input | AC |
| supply voltage at AC | Automatic range selection |
| supply voltage | 120 V/230 V |
| input voltage 1 at AC | 85 ... 132 V |
| input voltage 2 at AC | 170 ... 264 V |
| supply voltage: at 50 Hz | 230 V |
| supply voltage: at 60 Hz | 120 V |
| line frequency | 50/60 Hz |
| wide range input | No |
| overvoltage overload capability | Implemented internally with varistor |
| buffering time for rated value of the output current in the event of power failure minimum | 40 ms |
| operating condition of the mains buffering | at Vin = 120/230 V |
| input current: at rated input voltage 120 V | 2.25 A |
| input current: at rated input voltage 230 V | 1.24 A |
| current limitation of inrush current at 25 °C maximum | 15 A |
| I2t value maximum | 0.6 A2·s |
| fuse protection type | T 3.15 A |
| fuse protection type in the feeder | Recommended miniature circuit breaker: from 6 A characteristic C/B |
| voltage curve at output | Controlled, isolated DC voltage |
|---|---|
| product function output voltage controlled | Yes |
| product function output voltage stabilized | Yes |
| output voltage at DC rated value | 24 V |
| output voltage: at output 1 at DC rated value | 24 V |
| output voltage: at output 1 at DC | 24 V |
| output voltage adjustable | No |
| relative overall tolerance of the voltage | 3% |
| relative control precision of the output voltage: on slow fluctuation of input voltage | 0.1 % |
| residual ripple: maximum | 50 mV |
| voltage peak: maximum | 100 mV |
| display version for normal operation | Green LED: 24 V OK; red LED flashing: "overload/short-circuit" |
| type of signal at output | Relay contact (NO contact, rating 30 V AC/ 0.5 A; 30 V DC/1 A) for 24 V OK |
| behavior of the output voltage when switching on | Overshoot of Vout < 3 % |
| response delay maximum | 1.5 s |
| voltage increase time of the output voltage: typical | 22 ms |
| voltage increase time of the output voltage: maximum | 100 ms |
| output current: rated value | 5 A |
| output current: rated range | 0 ... 5 A |
| supplied active power typical | 133 W |
| short-term overload current: on short-circuiting during the start-up typical | 20 A |
| short-term overload current: at short-circuit during operation typical | 20 A |
| duration of overloading capability for excess current: on short-circuiting during the start-up | 50 ms |
| duration of overloading capability for excess current: at short-circuit during operation | 50 ms |
| bridging of equipment | Yes; Symmetric wiring required |
| number of parallel-switched equipment resources for increasing the power | 2 |
| Part number | 6EP1333-7CA10 |
|---|---|
| Type designation | PSU100P |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4025515156338 |
| ETIM class | EC002540 |
| eCl@ss | 27040701 |
| efficiency in percent | 90 % |
|---|---|
| power loss [W]: at rated output voltage for rated value of the output current typical | 12.9 W |
| relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical | 0.2 % |
|---|---|
| relative control precision of the output voltage load step of resistive load 50/100/50 % typical | 1% |
| setting time: maximum | 2 ms |
| design of the overvoltage protection | < 29 V |
|---|---|
| property of the output short-circuit proof | Yes |
| design of short-circuit protection | Electronic shutdown, automatic restart |
| typical | 5.5 A |
| enduring short circuit current RMS value: maximum | 6 A |
| enduring short circuit current RMS value: typical | 5 A |
| display version for overload and short circuit | Red LED flashing for "overload/short-circuit" |
| electrical separation between input and output | Yes |
|---|---|
| galvanic isolation | Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7) |
| operating resource protection class | Class I |
| leakage current: maximum | 3.5 mA |
| leakage current: typical | 1 mA |
| protection class IP | IP67 |
| standard: for emitted interference | EN 55022 Class B |
|---|---|
| standard: for mains harmonics limitation | EN 61000-3-2 |
| standard: for interference immunity | EN 61000-6-2 |
| certificate of suitability: CE marking | Yes |
|---|---|
| certificate of suitability: UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1) |
| certificate of suitability: EAC approval | Yes |
| certificate of suitability: NEC Class 2 | No |
| type of certification: CB-certificate | No |
| MTBF at 40 °C | 1 500 000 h |
| certificate of suitability: IECEx | No |
|---|---|
| certificate of suitability: ATEX | No |
| certificate of suitability: ULhazloc approval | No |
| certificate of suitability: FM registration | No |
| shipbuilding approval | No |
|---|---|
| Marine classification association: American Bureau of Shipping Europe Ltd. (ABS) | No |
| Marine classification association: French marine classification society (BV) | No |
| Marine classification association: Det Norske Veritas (DNV) | No |
| Marine classification association: Lloyds Register of Shipping (LRS) | No |
| ambient temperature: during operation | -25 ... +60 °C; with natural convection |
|---|---|
| ambient temperature: during transport | -40 ... +85 °C |
| ambient temperature: during storage | -40 ... +85 °C |
| environmental category according to IEC 60721 | 3K6 without direct sunlight |
| type of electrical connection | screw terminal |
|---|---|
| at input | L1, N, PE: Plug connector 7/8" (counterpart see "Operating Instructions (compact)") |
| at output | +, -: Plug connector M12-L coded (counterpart see "Operating Instructions (compact)") |
| for auxiliary contacts | Alarm signals: M12 plug-in connector 4-pin |
| removable terminal at input | Yes |
| removable terminal at output | Yes |
| width × height × depth of the enclosure | 120 × 181 × 60.5 mm |
|---|---|
| installation width × mounting height | 120 mm × 170 mm |
| required spacing: top | 50 mm |
| required spacing: bottom | 0 mm |
| required spacing: left | 0 mm |
| required spacing: right | 0 mm |
| fastening method | Wall mounting |
| DIN-rail mounting | No |
| S7 rail mounting | No |
| wall mounting | Yes |
| housing can be lined up | Yes |
| eClass | 16 27-04-07-01 |
|---|---|
| ETIM | 10 EC002540 |
| Net weight | 1.1 kg |
|---|---|
| Country of origin | HU |
| Shipping weight | 1.6 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of PSU100P is 5 A.
The rated operational voltage of PSU100P is 120–230 V AC.
The rated motor power of PSU100P is 12.9 W kW.
The tariff (HS) code on file for PSU100P is 85044083.
The EAN (GTIN) of PSU100P is 4025515156338.
PSU100P ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.