Part number
6EP1333-7CA10
Model no
PSU100P
$437.81 On request Dispatch — · From TürkiyeGet a Quote
SITOP PSU100P

Siemens 6EP1333-7CA10 SITOP PSU100P IP67 24V/5A M12 Field Power Supply

SITOP PSU100P IP67 24V/5A field power supply, M12 L-coded output, 120/230V AC input.

Rated current
5 A
Rated operational voltage
120–230 V AC
Motor power
12.9 W kW
Display
Green LED: 24 V OK; red LED flashing: overload/short-circuit
EAN
4025515156338
Description

About the PSU100P

The Siemens 6EP1333-7CA10 is a SITOP PSU100P power supply built for IP67 field mounting outside the control cabinet. It takes 120 V or 230 V AC with automatic range selection and delivers a stabilized 24 V DC output rated 5 A (133 W) through an M12 L-coded output connector, with a 7/8-inch input plug and a separate M12 alarm connector for the 24 V OK signal.

Certifications & Standards

  • CE
  • EAC

Selection Notes

The IP67 rating and M12/7/8-inch plug connectors let the 6EP1333-7CA10 mount directly on a machine frame or outside a cabinet, where the DIN-rail and wall-mount SITOP models need an enclosure. At 5 A / 133 W it sits below the higher-current variant in the same connectorized PSU100P family, so it fits a single field device or a small distributed I/O drop rather than a full remote panel. The relay contact on the alarm connector reports the 24 V OK status without running a separate signal back to the control cabinet, and the 90% efficiency keeps self-heating low inside a sealed enclosure where convection cooling is limited.

Specification

Full specification

125 values · Last verified 01 Nov 2026

General information 4

product brand name SITOP
product type designation PSU100P
product designation Power supply SITOP
type of current supply 24 V/5 A

Input 20

type of the power supply network 1-phase AC
phase number 1
voltage curve at input AC
supply voltage at AC Automatic range selection
supply voltage 120 V/230 V
input voltage 1 at AC 85 ... 132 V
input voltage 2 at AC 170 ... 264 V
supply voltage: at 50 Hz 230 V
supply voltage: at 60 Hz 120 V
line frequency 50/60 Hz
wide range input No
overvoltage overload capability Implemented internally with varistor
buffering time for rated value of the output current in the event of power failure minimum 40 ms
operating condition of the mains buffering at Vin = 120/230 V
input current: at rated input voltage 120 V 2.25 A
input current: at rated input voltage 230 V 1.24 A
current limitation of inrush current at 25 °C maximum 15 A
I2t value maximum 0.6 A2·s
fuse protection type T 3.15 A
fuse protection type in the feeder Recommended miniature circuit breaker: from 6 A characteristic C/B

Output 26

voltage curve at output Controlled, isolated DC voltage
product function output voltage controlled Yes
product function output voltage stabilized Yes
output voltage at DC rated value 24 V
output voltage: at output 1 at DC rated value 24 V
output voltage: at output 1 at DC 24 V
output voltage adjustable No
relative overall tolerance of the voltage 3%
relative control precision of the output voltage: on slow fluctuation of input voltage 0.1 %
residual ripple: maximum 50 mV
voltage peak: maximum 100 mV
display version for normal operation Green LED: 24 V OK; red LED flashing: "overload/short-circuit"
type of signal at output Relay contact (NO contact, rating 30 V AC/ 0.5 A; 30 V DC/1 A) for 24 V OK
behavior of the output voltage when switching on Overshoot of Vout < 3 %
response delay maximum 1.5 s
voltage increase time of the output voltage: typical 22 ms
voltage increase time of the output voltage: maximum 100 ms
output current: rated value 5 A
output current: rated range 0 ... 5 A
supplied active power typical 133 W
short-term overload current: on short-circuiting during the start-up typical 20 A
short-term overload current: at short-circuit during operation typical 20 A
duration of overloading capability for excess current: on short-circuiting during the start-up 50 ms
duration of overloading capability for excess current: at short-circuit during operation 50 ms
bridging of equipment Yes; Symmetric wiring required
number of parallel-switched equipment resources for increasing the power 2
Show all 125 specifications ↓ Show less ↑75 more values in Identification, Efficiency, Closed-loop control, Protection and monitoring, Safety, EMC, Standards, specifications, approvals, Standards, specifications, approvals hazardous environments, Standards, specifications, approvals marine classification, Ambient conditions, Connection method, Mechanical data, Version Classification, Logistics.

Identification 10

Part number 6EP1333-7CA10
Type designation PSU100P
Brand Siemens
Condition New, factory sealed
Source Siemens and its authorised distributors
Warranty Manufacturer warranty
Lifecycle status Active, in production
EAN 4025515156338
ETIM class EC002540
eCl@ss 27040701

Efficiency 2

efficiency in percent 90 %
power loss [W]: at rated output voltage for rated value of the output current typical 12.9 W

Closed-loop control 3

relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical 0.2 %
relative control precision of the output voltage load step of resistive load 50/100/50 % typical 1%
setting time: maximum 2 ms

Protection and monitoring 7

design of the overvoltage protection < 29 V
property of the output short-circuit proof Yes
design of short-circuit protection Electronic shutdown, automatic restart
typical 5.5 A
enduring short circuit current RMS value: maximum 6 A
enduring short circuit current RMS value: typical 5 A
display version for overload and short circuit Red LED flashing for "overload/short-circuit"

Safety 6

electrical separation between input and output Yes
galvanic isolation Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7)
operating resource protection class Class I
leakage current: maximum 3.5 mA
leakage current: typical 1 mA
protection class IP IP67

EMC 3

standard: for emitted interference EN 55022 Class B
standard: for mains harmonics limitation EN 61000-3-2
standard: for interference immunity EN 61000-6-2

Standards, specifications, approvals 6

certificate of suitability: CE marking Yes
certificate of suitability: UL approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1)
certificate of suitability: EAC approval Yes
certificate of suitability: NEC Class 2 No
type of certification: CB-certificate No
MTBF at 40 °C 1 500 000 h

Standards, specifications, approvals hazardous environments 4

certificate of suitability: IECEx No
certificate of suitability: ATEX No
certificate of suitability: ULhazloc approval No
certificate of suitability: FM registration No

Standards, specifications, approvals marine classification 5

shipbuilding approval No
Marine classification association: American Bureau of Shipping Europe Ltd. (ABS) No
Marine classification association: French marine classification society (BV) No
Marine classification association: Det Norske Veritas (DNV) No
Marine classification association: Lloyds Register of Shipping (LRS) No

Ambient conditions 4

ambient temperature: during operation -25 ... +60 °C; with natural convection
ambient temperature: during transport -40 ... +85 °C
ambient temperature: during storage -40 ... +85 °C
environmental category according to IEC 60721 3K6 without direct sunlight

Connection method 6

type of electrical connection screw terminal
at input L1, N, PE: Plug connector 7/8" (counterpart see "Operating Instructions (compact)")
at output +, -: Plug connector M12-L coded (counterpart see "Operating Instructions (compact)")
for auxiliary contacts Alarm signals: M12 plug-in connector 4-pin
removable terminal at input Yes
removable terminal at output Yes

Mechanical data 11

width × height × depth of the enclosure 120 × 181 × 60.5 mm
installation width × mounting height 120 mm × 170 mm
required spacing: top 50 mm
required spacing: bottom 0 mm
required spacing: left 0 mm
required spacing: right 0 mm
fastening method Wall mounting
DIN-rail mounting No
S7 rail mounting No
wall mounting Yes
housing can be lined up Yes

Version Classification 2

eClass 16 27-04-07-01
ETIM 10 EC002540

Logistics 6

Net weight 1.1 kg
Country of origin HU
Shipping weight 1.6 kg
Ships from Türkiye
Dispatch —
Stock On request

Source: manufacturer data · Last verified: 01 Nov 2026

Documents

Documents for 6EP1333-7CA10

No documents are on file for this part yet.

Ask us for the datasheet
Certifications

Certifications and standards

  • CE
  • EAC
  • CE marking
  • EAC approval
Quick answers

Questions about the PSU100P

What is the rated current of PSU100P?

The rated current of PSU100P is 5 A.

Which supply voltage is PSU100P rated for?

The rated operational voltage of PSU100P is 120–230 V AC.

What motor power is PSU100P rated for?

The rated motor power of PSU100P is 12.9 W kW.

What is the HS code of PSU100P for customs?

The tariff (HS) code on file for PSU100P is 85044083.

What is the EAN of PSU100P?

The EAN (GTIN) of PSU100P is 4025515156338.

Where does PSU100P ship from, and how fast?

PSU100P ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.

Guides

Guides for power supplies

All guides for power supplies
Reviews

Customer reviews

Series

Siemens SITOP PSU100P

Brand
Siemens
Series
SITOP PSU100P
$437.81 On request
Get a Quote
Quote

Get a Quote

PSU100P

Genuine parts

Genuine, factory-sealed parts

Siemens · 6EP1333-7CA10

Every part on Stoklink is new, unused and made by the manufacturer named on the page.

Condition
New and unused, in the manufacturer's factory-sealed packaging.
Sourced from
Siemens and its authorised distributors.
Warranty
The manufacturer's warranty applies.
If a part is not genuine
We refund the full amount.

Added to cart Could not add to cart

View cart