The Siemens 6EP1333-1LD01 is a SITOP PSU100D single-phase power supply that converts 100-120 V or 200-240 V AC into a stabilized 24 V DC output rated 6.25 A (150 W). It wall-mounts in a 97 x 30 x 159 mm enclosure, holds the output within 1% overall tolerance, and bridges a 30 ms mains dropout at rated load, suited to panel or field 24 V distribution needing more current than a DIN-rail unit.
At 6.25 A / 150 W and 89% efficiency, the 6EP1333-1LD01 sits below the higher-current model in the same PSU100D wall-mount family, so it fits a mid-size 24 V load without moving up to the bigger enclosure and greater weight of that unit. The output trims from 21.6 to 26.4 V via the built-in potentiometer, useful for offsetting cable drop on long 24 V field runs. Current limiting engages between 6.88 and 10.94 A, giving predictable fold-back on a dead short instead of a hard trip, and the 30 ms buffering time rides through brief mains interruptions without a separate battery module.
| product brand name | SITOP |
|---|---|
| product type designation | PSU100D |
| product designation | Power supply SITOP |
| type of current supply | 24 V/6.25 A |
| type of the power supply network | 1-phase AC |
|---|---|
| phase number | 1 |
| voltage curve at input | AC |
| supply voltage 1 at AC | 100 ... 120 V |
| supply voltage 2 at AC | 200 ... 240 V |
| input voltage 1 at AC | 90 ... 132 V |
| input voltage 2 at AC | 180 ... 264 V |
| supply voltage: at 50 Hz | 240 V |
| supply voltage: at 60 Hz | 100 V |
| line frequency | 50/60 Hz |
| wide range input | Yes |
| overvoltage overload capability | 1.25 × Vin rated, 500 ms |
| buffering time for rated value of the output current in the event of power failure minimum | 30 ms |
| operating condition of the mains buffering | at Vin = 115/230 V |
| input current: at rated input voltage 100 V | 3 A |
| input current: at rated input voltage 240 V | 1.6 A |
| current limitation of inrush current at 25 °C maximum | 60 A |
| I2t value maximum | 1.5 A2·s |
| fuse protection type | T4AL250V (internal) |
| fuse protection type in the feeder | Recommended miniature circuit breaker: from 16 A characteristic B, from 20 A characteristic B (for North America) |
| voltage curve at output | Controlled, isolated DC voltage |
|---|---|
| product function output voltage controlled | Yes |
| product function output voltage stabilized | Yes |
| output voltage at DC rated value | 24 V |
| output voltage: at output 1 at DC rated value | 24 V |
| output voltage: at output 1 at DC | 24 V |
| output voltage adjustable | Yes; via potentiometer |
| adjustable output voltage | 21.6 ... 26.4 V |
| relative overall tolerance of the voltage | 1% |
| relative control precision of the output voltage: on slow fluctuation of input voltage | 0.5 % |
| voltage peak: maximum | 200 mV |
| display version for normal operation | Green LED for 24 V OK |
| behavior of the output voltage when switching on | Overshoot of Vout < 10 % |
| response delay maximum | 0.5 s |
| voltage increase time of the output voltage: maximum | 30 ms |
| output current: rated value | 6.25 A |
| output current: rated range | 0 ... 6.25 A; +50 ... +70 °C: Derating 2.0%/K |
| supplied active power typical | 150 W |
| bridging of equipment | No |
| Part number | 6EP1333-1LD01 |
|---|---|
| Type designation | PSU100D |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4025515156208 |
| ETIM class | EC002540 |
| eCl@ss | 27040701 |
| efficiency in percent | 89 % |
|---|---|
| power loss [W]: at rated output voltage for rated value of the output current typical | 18 W |
| relative control precision of the output voltage load step of resistive load 50/100/50 % typical | 10 % |
|---|---|
| setting time: load step 50 to 100% typical | 4 ms |
| setting time: load step 100 to 50% typical | 4 ms |
| design of the overvoltage protection | < 33.6 V |
|---|---|
| property of the output short-circuit proof | Yes |
| design of short-circuit protection | Electronic shutdown, automatic restart |
| response value current limitation | 6.88 ... 10.94 A |
| enduring short circuit current RMS value: typical | 9 A |
| electrical separation between input and output | Yes |
|---|---|
| galvanic isolation | Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7) |
| operating resource protection class | Class I |
| leakage current: maximum | 0.5 mA |
| standard: for emitted interference | EN 55032 Class B |
|---|---|
| standard: for mains harmonics limitation | IEC 61000-3-2 Class A |
| standard: for interference immunity | EN 55035 |
| certificate of suitability: CE marking | Yes |
|---|---|
| certificate of suitability: UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus (UL 62368-1, CSA C22.2 NO 62368-1-14), File E151273 |
| certificate of suitability: UKCA marking | Yes |
| certificate of suitability: EAC approval | No |
| certificate of suitability: NEC Class 2 | No |
| type of certification: BIS | Yes; R-61003204 |
| type of certification: CB-certificate | Yes |
| MTBF at 25 °C | 700 000 h; according to SR-332, 100% full load (24 V, 6.25 A), input voltage: 115 V / 230 V AC |
| certificate of suitability: IECEx | No |
|---|---|
| certificate of suitability: ATEX | No |
| certificate of suitability: ULhazloc approval | No |
| certificate of suitability: FM registration | No |
| shipbuilding approval | No |
|---|---|
| Marine classification association: American Bureau of Shipping Europe Ltd. (ABS) | No |
| Marine classification association: French marine classification society (BV) | No |
| Marine classification association: Det Norske Veritas (DNV) | No |
| Marine classification association: Lloyds Register of Shipping (LRS) | No |
| Environmental Product Declaration | Yes |
|---|---|
| global warming potential [CO2 eq]: total | 570.3 kg |
| global warming potential [CO2 eq]: during manufacturing | 7.1 kg |
| global warming potential [CO2 eq]: during operation | 563 kg |
| global warming potential [CO2 eq]: after end of life | 0.11 kg |
| ambient temperature: during operation | -25 ... +70 °C; with natural convection; The device is not recommended to be placed on low thermal conductive surface (e. g. plastics). |
|---|---|
| ambient temperature: during transport | -40 ... +85 °C |
| ambient temperature: during storage | -40 ... +85 °C |
| relative humidity with condensation according to IEC 60068-2-38 maximum | 20 ... 90% without condensation |
| type of electrical connection | screw terminal |
|---|---|
| at input | L, N, PE: 1 screw terminal each for 0.75 ... 2 mm2 single-core/finely stranded |
| at output | +, -: 2 screw terminals each for 0.75 ... 2 mm2 |
| for auxiliary contacts | - |
| width × height × depth of the enclosure | 97 × 30 × 159 mm |
|---|---|
| fastening method | Wall mounting |
| DIN-rail mounting | No |
| S7 rail mounting | No |
| wall mounting | Yes |
| other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
|---|
| eClass | 16 27-04-07-01 |
|---|---|
| ETIM | 10 EC002540 |
| IDEA | 4 4130 |
| UNSPSC | 15 39-12-10-04 |
| Net weight | 0.36 kg |
|---|---|
| Country of origin | IN |
| Shipping weight | 0.86 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of PSU100D is 6.25 A.
The rated operational voltage of PSU100D is 100–120 – 200–240 V AC.
The rated motor power of PSU100D is 18 W kW.
The tariff (HS) code on file for PSU100D is 85044083.
The EAN (GTIN) of PSU100D is 4025515156208.
PSU100D ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.