Main Components of a PLC System: Complete Guide for Engineers
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.
The Siemens 6EP1321-1LD01 is a SITOP PSU100D stabilized power supply converting 100-240 V AC single-phase input into a regulated, adjustable 12 V DC output at up to 3 A. It reaches 86% efficiency, holds output within 1% overall tolerance, rides through a 16 ms mains interruption at rated load, and mounts directly to the wall in an 82 x 29 x 99 mm enclosure.
The 16 ms buffering time and 45 A inrush rating let the PSU100D ride through short mains dips without dropping the 12 V rail, and the potentiometer-adjustable output (10.8-13.2 V) allows compensating for cable voltage drop on longer runs to the load. Choose this 3 A rating over the lighter PSU100D variants when the connected load's steady-state current stays under 3 A; the electronic short-circuit protection auto-restarts once the fault clears, so no manual reset is needed after a transient short.
| product brand name | SITOP |
|---|---|
| product type designation | PSU100D |
| product designation | Power supply SITOP |
| type of current supply | 12 V/3 A |
| type of the power supply network | 1-phase AC |
|---|---|
| phase number | 1 |
| voltage curve at input | AC |
| supply voltage at AC: minimum rated value | 100 V |
| supply voltage at AC: maximum rated value | 240 V |
| supply voltage at AC: initial value | 90 V |
| supply voltage at AC: full-scale value | 264 V |
| supply voltage: at 50 Hz | 240 V |
| supply voltage: at 60 Hz | 100 V |
| line frequency | 50/60 Hz |
| wide range input | Yes |
| overvoltage overload capability | 1.25 × Vin rated, 500 ms |
| buffering time for rated value of the output current in the event of power failure minimum | 16 ms |
| operating condition of the mains buffering | at Vin = 115/230 V |
| input current: at rated input voltage 100 V | 0.85 A |
| input current: at rated input voltage 240 V | 0.5 A |
| current limitation of inrush current at 25 °C maximum | 45 A |
| I2t value maximum | 1.5 A2·s |
| fuse protection type | T3.15AL250V (internal) |
| fuse protection type in the feeder | Recommended miniature circuit breaker: from 16 A characteristic B, from 20 A characteristic B (for North America) |
| voltage curve at output | Controlled, isolated DC voltage |
|---|---|
| product function output voltage controlled | Yes |
| product function output voltage stabilized | Yes |
| output voltage at DC rated value | 12 V |
| output voltage: at output 1 at DC rated value | 12 V |
| output voltage: at output 1 at DC | 12 V |
| output voltage adjustable | Yes; via potentiometer |
| adjustable output voltage | 10.8 ... 13.2 V |
| relative overall tolerance of the voltage | 1% |
| relative control precision of the output voltage: on slow fluctuation of input voltage | 0.5 % |
| voltage peak: maximum | 120 mV |
| display version for normal operation | Green LED for 12 V OK |
| behavior of the output voltage when switching on | Overshoot of Vout < 10 % |
| response delay maximum | 1 s |
| voltage increase time of the output voltage: maximum | 30 ms |
| output current: rated value | 3 A |
| output current: rated range | 0 ... 3 A; +50 ... +70 °C: Derating 2.0%/K |
| supplied active power typical | 35 W |
| bridging of equipment | No |
| Part number | 6EP1321-1LD01 |
|---|---|
| Type designation | PSU100D |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4025515156178 |
| ETIM class | EC002540 |
| eCl@ss | 27040701 |
| efficiency in percent | 86 % |
|---|---|
| power loss [W]: at rated output voltage for rated value of the output current typical | 5.7 W |
| relative control precision of the output voltage load step of resistive load 50/100/50 % typical | 10 % |
|---|---|
| setting time: load step 50 to 100% typical | 4 ms |
| setting time: load step 100 to 50% typical | 4 ms |
| design of the overvoltage protection | < 17.4 V |
|---|---|
| property of the output short-circuit proof | Yes |
| design of short-circuit protection | Electronic shutdown, automatic restart |
| response value current limitation | 3.3 ... 5.25 A |
| enduring short circuit current RMS value: typical | 4 A |
| electrical separation between input and output | Yes |
|---|---|
| galvanic isolation | Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7) |
| operating resource protection class | Class I |
| leakage current: maximum | 0.5 mA |
| standard: for emitted interference | EN 55032 Class B |
|---|---|
| standard: for mains harmonics limitation | IEC 61000-3-2 |
| standard: for interference immunity | EN 55035 |
| certificate of suitability: CE marking | Yes |
|---|---|
| certificate of suitability: UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus (UL 62368-1, CSA C22.2 NO 62368-1-14), File E151273 |
| certificate of suitability: UKCA marking | Yes |
| certificate of suitability: EAC approval | No |
| certificate of suitability: NEC Class 2 | No |
| type of certification: BIS | Yes; R-61003204 |
| type of certification: CB-certificate | Yes |
| MTBF at 25 °C | 700 000 h; according to SR-332, 100% full load (12 V, 3 A), input voltage: 115 V / 230 V AC |
| certificate of suitability: IECEx | No |
|---|---|
| certificate of suitability: ATEX | No |
| certificate of suitability: ULhazloc approval | No |
| certificate of suitability: FM registration | No |
| shipbuilding approval | No |
|---|---|
| Marine classification association: American Bureau of Shipping Europe Ltd. (ABS) | No |
| Marine classification association: French marine classification society (BV) | No |
| Marine classification association: Det Norske Veritas (DNV) | No |
| Marine classification association: Lloyds Register of Shipping (LRS) | No |
| Environmental Product Declaration | Yes |
|---|---|
| global warming potential [CO2 eq]: total | 181.8 kg |
| global warming potential [CO2 eq]: during manufacturing | 3.4 kg |
| global warming potential [CO2 eq]: during operation | 178.3 kg |
| global warming potential [CO2 eq]: after end of life | 0.05 kg |
| ambient temperature: during operation | -25 ... +70 °C; with natural convection; The device is not recommended to be placed on low thermal conductive surface (e. g. plastics). |
|---|---|
| ambient temperature: during transport | -40 ... +85 °C |
| ambient temperature: during storage | -40 ... +85 °C |
| relative humidity with condensation according to IEC 60068-2-38 maximum | 20 ... 90% without condensation |
| type of electrical connection | screw terminal |
|---|---|
| at input | L, N, PE: 1 screw terminal each for 0.75 ... 2 mm2 single-core/finely stranded |
| at output | +, -: 1 screw terminal each for 0.75 ... 2 mm2 |
| for auxiliary contacts | - |
| width × height × depth of the enclosure | 82 × 29 × 99 mm |
|---|---|
| fastening method | Wall mounting |
| DIN-rail mounting | No |
| S7 rail mounting | No |
| wall mounting | Yes |
| other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
|---|
| eClass | 16 27-04-07-01 |
|---|---|
| ETIM | 10 EC002540 |
| IDEA | 4 4130 |
| UNSPSC | 15 39-12-10-04 |
| Net weight | 0.17 kg |
|---|---|
| Country of origin | IN |
| Shipping weight | 0.67 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of PSU100D is 3 A.
The rated operational voltage of PSU100D is 100–240 V AC.
The rated motor power of PSU100D is 35 W kW.
The tariff (HS) code on file for PSU100D is 85044083.
The EAN (GTIN) of PSU100D is 4025515156178.
PSU100D ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.