About the 3SK1
The Siemens 3SK1111-2AW20 is a safety relay from the SENTRON/SIRIUS 3SK1 series. SIRIUS safety relay Basic unit Standard series Relay enabling circuits 3 NO contacts plus Relay signaling circuit 1 NC contact Us = 110 - 240 V AC/DC 50/60 Hz Spring-type terminal (push-in). Supplied by Stoklink for industrial and commercial low-voltage applications.
Certifications & Standards
- IEC 60947-5
Applications & Use Cases
The Siemens 3SK1111-2AW20 is used in industrial control panels, distribution boards and automation systems. As part of the Siemens 3SK1 range it integrates with compatible SENTRON/SIRIUS components for a coordinated low-voltage installation. Genuine Siemens product supplied by Stoklink with fast dispatch from Türkiye.
Specification
Full specification
General 6
| product brand name | SIRIUS |
|---|---|
| product category | Safety relays |
| product designation | safety relays |
| design of the product | Relay enabling circuits |
| product type designation | 3SK1 |
| product line | Standard basic unit |
Product Function 20
| product function parameterizable | Sensor floating / monitored start / automatic start |
|---|---|
| product function: automatic start | Yes |
| product function: light barrier monitoring | No |
| product function: protective door monitoring | Yes |
| product function: magnetically operated switch monitoring NC-NO | No |
| product function: laser scanner monitoring | No |
| product function: light array monitoring | No |
| product function: EMERGENCY OFF function | Yes |
| product function: monitored start-up | Yes |
| product function: pressure-sensitive mat monitoring | No |
| product feature cross-circuit-proof | Yes |
| suitability for interaction press control | No |
| suitability for operation device connector 3ZY12 | No |
| suitability for use: monitoring of floating sensors | Yes |
| suitability for use: monitoring of non-floating sensors | No |
| suitability for use: position switch monitoring | Yes |
| suitability for use: EMERGENCY-OFF circuit monitoring | Yes |
| suitability for use: opto-electronic protection device monitoring | No |
| suitability for use: magnetically operated switch monitoring | No |
| suitability for use: safety-related circuits | Yes |
General technical data 14
| certificate of suitability UL approval | Yes |
|---|---|
| product feature protective coating on printed-circuit board | No |
| power loss [W] maximum | 2.5 W |
| insulation voltage rated value | 300 V |
| degree of pollution | 3 |
| overvoltage category | 3 |
| surge voltage resistance rated value | 4 000 V |
| protection class IP of the enclosure | IP20 |
| shock resistance | 10 g / 11 ms |
| vibration resistance according to IEC 60068-2-6 | 5 ... 500 Hz: 0.75 mm |
| operating frequency maximum | 360 1/h |
| reference code according to IEC 81346-2 | F |
| Substance Prohibitance (day/month/year) | 11/05/2012 |
| SVHC substance name | Lead CAS-No. 7439-92-1 Lead monoxide (lead oxide) CAS-No. 1317-36-8 2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-one CAS-No. 71868- 10-5 Melamine CAS-No. 108-78-1 6,6'-di-tert-butyl-2,2'-methylenedi-p-cresol CAS-No. 119-47-1 4,4'-isopropylidenediphenol (Bisphenol A, BPA) CAS-No. 80-05-7 |
Show all 143 specifications ↓ Show less ↑103 more values in Identification, Ambient conditions, Electromagnetic compatibility, Safety related data, IEC 62061, ISO 13849, IEC 61508, Electrical Safety, Short-circuit protection, Inputs, Outputs, Times, Control circuit/ Control, Installation/ mounting/ dimensions, Connections/ Terminals, Logistics.
Identification 10
| Part number | 3SK1111-2AW20 |
|---|---|
| Type designation | 3SK1 |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4011209913530 |
| ETIM class | EC001449 |
| eCl@ss | 27371819 |
Ambient conditions 6
| installation altitude at height above sea level maximum | 4 000 m |
|---|---|
| note | Derating, see Product Notification 109792701 |
| ambient temperature: during operation | -25 ... +60 °C |
| ambient temperature: during storage | -40 ... +80 °C |
| relative humidity during operation | 10 ... 95 % |
| air pressure according to SN 31205 | 900 ... 1 060 hPa |
Electromagnetic compatibility 2
| installation environment regarding EMC | This product is suitable for Class A environments only. In household environments, this device can cause unwanted radio interference. The user is required to implement appropriate measures in this case. |
|---|---|
| EMC emitted interference | IEC 60947-5-1, Class A |
IEC 62061 5
| SIL Claim Limit (subsystem) according to EN 62061 | 3 |
|---|---|
| Safety Integrity Level (SIL): according to IEC 62061 | SIL 3 |
| Safety Integrity Level (SIL): at single-channel evaluation according to IEC 62061 | 1 |
| Safety Integrity Level (SIL): at 2-channel evaluation according to IEC 62061 | 3 |
| PFHD with high demand rate according to IEC 62061 | 0,0000000015 |
ISO 13849 7
| category according to EN ISO 13849-1 | 4 |
|---|---|
| performance level (PL): according to ISO 13849-1 | PL e |
| performance level (PL): at single-channel evaluation according to ISO 13849-1 | c |
| performance level (PL): at 2-channel evaluation according to ISO 13849-1 | e |
| category: according to ISO 13849-1 | 4 |
| category: at 2-channel evaluation according to ISO 13849-1 | 4 |
| overdimensioning according to ISO 13849-2 necessary | No |
IEC 61508 12
| Safety Integrity Level (SIL): according to IEC 61508 | 3 |
|---|---|
| Safety Integrity Level (SIL): at single-channel evaluation according to IEC 61508 | 1 |
| Safety Integrity Level (SIL): at 2-channel evaluation according to IEC 61508 | 3 |
| safety device type according to IEC 61508-2 | Type A |
| PFHD with high demand rate according to IEC 61508 | 0.0000000015 |
| PFDavg with low demand rate according to IEC 61508 | 0.000001 |
| Safe failure fraction (SFF) | 99 % |
| hardware fault tolerance: according to IEC 61508 | 1 |
| hardware fault tolerance: at single-channel evaluation according to IEC 61508 | 0 |
| hardware fault tolerance: at 2-channel evaluation according to IEC 61508 | 1 |
| T1 value: of service life according to IEC 61508 | 20 a |
| T1 value: for proof test interval or service life according to IEC 61508 | 20 a |
Electrical Safety 1
| touch protection against electrical shock | finger-safe |
|---|
Short-circuit protection 3
| design of the fuse link: for short-circuit protection of the NO contacts of the relay | gL/gG: 6A or circuit breaker type A: 3A or circuit breaker type B: 2A or circuit |
|---|---|
| outputs required | breaker type C: 1A |
| for short circuit protection of the NC contacts of the relay | Diazed or Neozed fuses, operating class gL/gG: 6 A or MCB type A: 2 A or |
Inputs 5
| design of input: cascading input/functional switching | No |
|---|---|
| design of input: feedback input | Yes |
| design of input: start input | Yes |
| pulse duration of the sensor input minimum | 150 ms |
| number of sensor inputs 1-channel or 2-channel | 1 |
Outputs 9
| as NC contact: for signaling function instantaneous contact | 1 |
|---|---|
| as NO contact: safety-related instantaneous contact | 3 |
| as NO contact: safety-related delayed switching | 0 |
| mechanical service life (operating cycles) typical | 10 000 000 |
| thermal current of the switching element with contacts maximum | 5 A |
| switching capacity current of the NO contacts of the relay outputs at DC-13: at 24 V | 5 A |
| switching capacity current of the NC contacts of the relay outputs at DC-13: at 24 V | 1 A |
| total current maximum | 12 A |
| operational current at 17 V minimum | 5 mA |
Times 13
| make time with automatic start: typical | 110 ms |
|---|---|
| make time with automatic start: at DC maximum | 130 ms |
| make time with automatic start: at AC maximum | 130 ms |
| make time with automatic start after power failure: typical | 110 ms |
| make time with automatic start after power failure: maximum | 130 ms |
| make time with monitored start: typical | 15 ms |
| make time with monitored start: maximum | 15 ms |
| backslide delay time after opening of the safety circuits typical | 10 ms |
| backslide delay time in the event of power failure: typical | 200 ms |
| backslide delay time in the event of power failure: maximum | 300 ms |
| recovery time after opening of the safety circuits typical | 10 ms |
| recovery time after power failure typical | 0.32 s |
| pulse duration: of the ON pushbutton input minimum | 0.015 s |
Control circuit/ Control 7
| type of voltage of the control supply voltage | AC/DC |
|---|---|
| control supply voltage at AC: at 50 Hz rated value | 110 ... 240 V |
| control supply voltage at AC: at 60 Hz rated value | 110 ... 240 V |
| control supply voltage frequency: 1 rated value | 50 Hz |
| control supply voltage frequency: 2 rated value | 60 Hz |
| control supply voltage at DC rated value | 110 ... 240 V |
| operating range factor control supply voltage rated value of magnet coil at DC: initial value | 0.85 |
Installation/ mounting/ dimensions 6
| mounting position | any |
|---|---|
| fastening method | screw and snap-on mounting |
| height | 100 mm |
| width | 22.5 mm |
| depth | 121.6 mm |
| required spacing: for grounded parts at the side | 5 mm |
Connections/ Terminals 6
| type of electrical connection | spring-loaded terminal (push-in) |
|---|---|
| wire length: for total of all sensor circuits with Cu 1.5 mm2 and 150 nF/km maximum | 2 000 m |
| type of connectable conductor cross-sections: solid | 1x (0.5 ... 1.5 mm2), 2x (0.5 ... 1.5 mm2) |
| type of connectable conductor cross-sections: finely stranded with core end processing | 1x (0.5 ... 1.0 mm2), 2x (0.5 ... 1.0 mm2) |
| type of connectable conductor cross-sections: for AWG cables solid | 1x (20 ... 16), 2x (20 ... 16) |
| type of electrical connection plug-in socket | No |
Logistics 6
| Net weight | 0.217 kg |
|---|---|
| Package dimensions | 159 × 105 × 38 mm |
| Country of origin | DE |
| Shipping weight | 0.717 kg |
| Dispatch | 25 Nov |
| Stock | Low stock |
Source: manufacturer data · Last verified: 31 Oct 2026
Documents
Documents for 3SK1111-2AW20 1
-
Datasheet
ProductDownload PDF: Product data sheet 3SK1111-2AW20
Product data sheet 3SK1111-2AW20
Certifications
Certifications and standards
- IEC 60947-5
Quick answers
Questions about the 3SK1
What is the rated current of 3SK1?
The rated current of 3SK1 is 5 A.
Which control voltage does 3SK1 need?
The control voltage range of 3SK1 is 110–240–DC V.
What is the HS code of 3SK1 for customs?
The tariff (HS) code on file for 3SK1 is 85371098.
What is the EAN of 3SK1?
The EAN (GTIN) of 3SK1 is 4011209913530.
How is 3SK1 delivered, and how fast?
3SK1 ships worldwide by express courier, with tracking. Shipping and import duties calculated at checkout · nothing to pay on delivery. Stock items are dispatched within 1–2 business days.