How to Select and Size a Soft Starter for a Motor
How to size a soft starter correctly by full-load current, IEC 60947-4-2 duty class, starting torque against the load, control method, wiring topology and...
Last orders until 31 Mar 2027. After that date, supply depends on remaining stock. Date announced by Schneider Electric for Türkiye, where we source this part.
No replacement announced yet. Tell us the application and we will propose an alternative.
Schneider Electric ATS22 soft starters are compact and reliable motor starting solutions designed for smooth acceleration and deceleration of asynchronous motors in standard industrial applications. The ATS22 series focuses on reducing mechanical stress, limiting starting current, and simplifying motor starting without advanced digital control requirements. With a proven design and straightforward configuration, ATS22 soft starters are commonly used for pumps, fans, compressors, conveyors, and general-purpose machinery where controlled motor starting is required.
The Schneider ATS22D62S6 is an Altistart 22 motor soft starter rated for a nominal operational current of 62 A (at 40 °C) and designed to control three-phase asynchronous motors. Its motor power ratings are specified as 15 kW at 230 V and 30 kW at 400 V, making it suitable for small to medium industrial motors in the indicated voltage classes. The ATS22D62S6 supports supply voltages across the 230–600 V range and offers torque-control (current-limited) starting to reduce mechanical stress and limit inrush current during motor acceleration. Typical applications include pumps, fans, compressors and conveyors where a controlled start/stop and reduced mechanical wear are required. Standout, verified features for this SKU include an internal bypass switch to reduce heat and losses after start, integrated motor overload protection with PTC input support, and compatibility with configuration tools and communications (Modbus / serial interface) for faster setup and diagnostics.
| Range of Product | Altistart 22 |
|---|---|
| Product or Component Type | Soft starter |
| Product destination | Asynchronous motors |
| Product Specific Application | Pumps and fans |
| Component name | ATS22 |
| Phase | 3 phase |
| [Us] rated supply voltage | 230...600 V - 15...10 % |
| Motor power kW | 15 kW 230 V, 30 kW 400 V, 30 kW 440 V, 37 kW 500 V |
| Factory setting current | 52 A |
| Power dissipation in W | 59 W for standard applications |
| Utilisation category | AC-53A |
| Type of start | Start with torque control (current limited to 3.5 In) |
| IcL starter rating | 62 A connection in the motor supply line for standard applications |
| IP Degree of Protection | IP20 |
| Assembly style | With heat sink |
|---|---|
| Function Available | Internal bypass |
| Supply voltage limits | 195…660 V |
| Supply frequency | 50...60 Hz - 10...10 % |
| Network Frequency | 45...66 Hz |
| Device connection | In the motor supply line |
| [Uc] control circuit voltage | 230 V - 15...10 % 50/60 Hz |
| Control circuit consumption | 20 W |
| Discrete output number | 2 |
| Discrete output type | Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O, Relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O |
| Minimum switching current | 100 mA 12 V DC relay outputs) |
| Maximum switching current | 5 A 250 V AC resistive 1 relay outputs, 5 A 30 V DC resistive 1 relay outputs, 2 A 250 V AC inductive 0.4 20 ms relay outputs, 2 A 30 V DC inductive 7 ms relay outputs |
| Discrete input number | 3 |
| Discrete input type | LI1, LI2, LI3) logic, 5 mA 4.3 kOhm |
| Discrete input voltage | 24 V <= 30 V |
| Discrete input logic | Positive logic LI1, LI2, LI3 11 V, >= 5 mA |
| Output current | 0.4...1 Icl adjustable |
| PTC probe input | 750 Ohm |
| Communication Port Protocol | Modbus |
| Connector Type | 1 RJ45 |
| Communication data link | Serial |
| Physical interface | RS485 multidrop |
| Transmission Rate | 4800, 9600 or 19200 bps |
| Installed device | 31 |
| Protection type | Phase failure line, Thermal protection motor, Thermal protection starter |
| Marking | CE |
| Type of cooling | Forced convection |
| Operating position | Vertical +/- 10 degree |
| Height | 11.6 in (295 mm) |
| Width | 5.7 in (145 mm) |
| Depth | 8.1 in (207 mm) |
| Net Weight | 26.5 lb(US) (12 kg) |
| Motor power range AC-3 | 30…50 kW 480…500 V 3 phase, 15…25 kW 200…240 V 3 phase, 30…50 kW 380…440 V 3 phase |
| Motor starter type | Soft starter |
| Electromagnetic compatibility | Conducted and radiated emissions level A conforming to IEC 60947-4-2, Damped oscillating waves level 3 conforming to IEC 61000-4-12, Electrostatic discharge level 3 conforming to IEC 61000-4-2, Immunity to electrical transients level 4 conforming to IEC 61000-4-4, Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3, Voltage/current impulse level 3 conforming to IEC 61000-4-5 |
|---|---|
| Standards | IEC 60947-4-2 |
| Product Certifications | CCC, UL, CSA, GOST, C-tick |
| Vibration resistance | 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6, 1.5 mm (f= 2…13 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn 11 ms IEC 60068-2-27 |
| Noise level | 45 dB |
| Pollution degree | Level 2 IEC 60664-1 |
| Relative humidity | 0…95 % without condensation or dripping water IEC 60068-2-3 |
| Ambient air temperature for operation | 14…104 °F (-10…40 °C) (without derating), 104…140 °F (40…60 °C) (with current derating 2.2 % per °C) |
| Ambient Air Temperature for Storage | -13…158 °F (-25…70 °C) |
| Operating altitude | <= 3280.84 ft (1000 m) without derating, > 3280.84... 1000...< 2000 m) with current derating of 2.2 % per additional 100 m |
| Part number | ATS22D62S6 |
|---|---|
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Phase-out announced by the manufacturer |
| Last order date | 31 Mar 2027 · as announced for Türkiye, our sourcing market |
| EAN | 3606480167300 |
| Warranty (in months) | 18 |
|---|
| Country of origin | FR |
|---|---|
| Shipping weight | 12.0 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of ATS22D62S6 is 62 A.
The rated operational voltage of ATS22D62S6 is 230–600 V AC.
The rated motor power of ATS22D62S6 is 30 kW.
The control voltage range of ATS22D62S6 is 110–250 V.
The tariff (HS) code on file for ATS22D62S6 is 853710.
The EAN (GTIN) of ATS22D62S6 is 3606480167300.
ATS22D62S6 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
How to size a soft starter correctly by full-load current, IEC 60947-4-2 duty class, starting torque against the load, control method, wiring topology and...
A side-by-side comparison of soft starters and autotransformer (Korndorfer) starters covering torque, supply-side current, transition type, maintenance, cost, and load fit.
Explore the different types of soft starters, from analog to digital and solid-state models, with key features for industrial motor control. Shop at Stoklink.