SITOP SEL1400 4-channel selectivity module, 24V DC/40A input, 4x adjustable 2-10A outputs.
The Siemens SITOP SEL1400 (6EP4437-7EB00-3CX0) is a 4-channel selectivity module that splits a 24 V DC, 40 A input into four individually adjustable outputs rated up to 10 A each, with current thresholds set from 2 to 10 A per channel.
Each of the 4 outputs has an independently adjustable 2 - 10 A threshold, so one module protects branch circuits of different current ratings from a single 40 A / 24 V feed without oversizing every channel to the largest load. The 3-stage switch-off (overcurrent at approx. 5 s, current limiting at approx. 100 ms, immediate cutoff at approx. 0.5 ms) trips selectively ahead of the upstream supply's own protection, isolating a faulted branch before the whole 24 V bus drops.
Splits a single 24 V DC feed from a SITOP power supply into 4 individually protected branch circuits in a control cabinet, isolating a shorted sensor or actuator line without taking down the whole 24 V bus.
| product brand name | SITOP |
|---|---|
| product type designation | SEL1400 |
| product designation | SITOP Selectivity module |
| type of current supply | selectivity module, 4 x 2 ... 10 A com. sign. contact or diagnostics monitor |
| type of the power supply network | Controlled DC voltage |
|---|---|
| supply voltage at DC rated value | 24 V |
| input voltage at DC | 20.4 ... 30 V |
| overvoltage overload capability | 35 V |
| input current at rated input voltage 24 V rated value | 40 A |
| voltage curve at output | controlled DC voltage |
|---|---|
| formula for output voltage | Vin - approx. 0.2 V |
| relative overall tolerance of the voltage note | In accordance with the supplying input voltage |
| number of outputs | 4 |
| output current up to 60 °C per output rated value | 10 A; +60 ... +70 °C: Derating 2%/K |
| adjustable current response value current of the current-dependent overload release | 2 ... 10 A |
| type of response value setting | via potentiometer |
| response delay maximum | 5 s |
| product feature parallel switching of outputs | Yes |
| type of outputs connection | switch-on of all outputs after power-up of the supply voltage > 20 V, delay time of 25 ms, 200 ms, 500 ms, or "load-optimized" via DIP switch configurable for sequential switch-on |
| Part number | 6EP4437-7EB00-3CX0 |
|---|---|
| Type designation | SEL1400 |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4025515155287 |
| ETIM class | EC001440 |
| eCl@ss | 27371802 |
| efficiency in percent | 98 % |
|---|---|
| power loss [W] at rated output voltage for rated value of the output current typical | 10 W |
| switching characteristic: of the excess current | Iout = 1.0 ...1.5 x set value, switch-off after approx. 5 s |
|---|---|
| switching characteristic: of the current limitation | Iout = 1.5 x set value, switch-off after typ. 100 ms |
| switching characteristic: of the immediate switch-off | Iout > set value and Vin < 20 V, switch-off after approx. 0.5 ms |
| design of the reset device/resetting mechanism | via sensor per output |
| remote reset function protection and monitoring | non-isolated 24 V input (signal level "high" at > 15 V) |
| fuse protection type at input | 15 A per output (not accessible) |
| display version for normal operation | Three-color LED per output: green LED for "Output switched through"; yellow LED for "Output switched off manually"; red LED for "Output switched off due to overcurrent" |
| design of the switching contact for signaling function | Floating common signal contact or status signal output (pulse/pause signal that can be evaluated via SIMATIC function block) |
| galvanic isolation between input and output at switch-off | No |
|---|---|
| standard for safety | according to EN 62368-1 |
| operating resource protection class | Class III |
| protection class IP | IP20 |
| standard: for emitted interference | EN 61000-6-3 |
| standard: for interference immunity | EN 61000-6-2 |
| certificate of suitability: CE marking | Yes |
|---|---|
| certificate of suitability: UL approval | Yes; UL-Recognized (UL 2367) File E328600; cULus-Listed (UL 508, CSA C22.2 No. 107.1) File E197259 |
| certificate of suitability: UKCA marking | Yes |
| certificate of suitability: EAC approval | Yes |
| type of certification: CB-certificate | Yes |
| certificate of suitability: IECEx | No |
|---|---|
| certificate of suitability: ATEX | No |
| shipbuilding approval | Yes |
|---|---|
| Marine classification association: Det Norske Veritas (DNV) | Yes |
| Environmental Product Declaration | Yes |
|---|---|
| global warming potential [CO2 eq]: total | 287.5 kg |
| global warming potential [CO2 eq]: during manufacturing | 13.1 kg |
| global warming potential [CO2 eq]: during operation | 274 kg |
| global warming potential [CO2 eq]: after end of life | 0.3 kg |
| Siemens eco profile (SEP) | Siemens EcoTech |
| ambient temperature: during operation | -40 ... +70 °C; with natural convection |
|---|---|
| ambient temperature: during transport | -40 ... +85 °C |
| ambient temperature: during storage | -40 ... +85 °C |
| environmental category according to IEC 60721 | Climate class 3K3, 5 ... 95% no condensation |
| type of electrical connection | Push-in |
|---|---|
| at input | 24V1, 24V2: push-in for 0.5 ... 16 mm2; 0V1, 0V2: push-in for 0.5 ... 4 mm2 |
| at output | Output 1 ... 4: push-in for 0.5 ... 4 mm2 |
| for auxiliary contacts | RST: push-in for 0.2 ... 1.5 mm2 |
| for signaling contact | 13, 14: push-in for 0.2 ... 1.5 mm2 |
| width × height × depth of the enclosure | 45 × 135 × 125 mm |
|---|---|
| installation width × mounting height | 45 mm × 225 mm |
| required spacing: top | 45 mm |
| required spacing: bottom | 45 mm |
| required spacing: left | 0 mm |
| required spacing: right | 0 mm |
| fastening method | Snaps onto DIN rail EN 60715 35x7.5/15 |
| DIN-rail mounting | Yes |
| S7 rail mounting | No |
| wall mounting | No |
| housing can be lined up | Yes |
| identification link | Yes; acc. to IEC 61406-1:2022 |
|---|
| other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
|---|
| Net weight | 0.3 kg |
|---|---|
| Country of origin | Romania |
| Shipping weight | 0.8 kg |
| Ships from | Türkiye |
| Dispatch | 13 Nov |
| Stock | In stock |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of SEL1400 is 10 A.
The rated operational voltage of SEL1400 is 24 V AC.
The rated motor power of SEL1400 is 10 W kW.
The tariff (HS) code on file for SEL1400 is 85363010.
The EAN (GTIN) of SEL1400 is 4025515155287.
SEL1400 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.