Siemens 6EP3233-0TA00-0AY0 SITOP PSU3400 48V-24V 5A DC/DC Converter

SITOP PSU3400 DC/DC converter, 48V in, 24V/5A out, DIN rail, 92% efficiency.

Rated current
5 A
Motor power
10 W kW
EAN
4025515155522
Description

About the PSU3400

The Siemens 6EP3233-0TA00-0AY0 SITOP PSU3400 is a DC/DC converter that steps a 48 V DC (28-60 V range) input down to a stabilized 24 V DC output at 5 A, adjustable up to 6 A. It reaches 92% efficiency and fits a 32 mm DIN-rail footprint for battery- or 48 V-bus-fed control cabinets.

Certifications & Standards

  • CE
  • EAC
  • RCM
  • CB
  • ABS
  • DNV

Selection Notes

The 48 V DC input (28-60 V range) is what separates this PSU3400 unit from the AC-mains SITOP power supplies — choose it where the cabinet already runs a 48 V DC bus, such as a telecom-style battery system, rather than adding an AC feed. The output is adjustable 24-28 V via potentiometer, useful for compensating voltage drop on long 24 V DC runs instead of a fixed-output sibling. Two units can be connected in parallel to raise available current beyond the single-unit 5 A/6 A rating without moving to a higher-power PSU model.

Applications

48 V DC bus-fed control panels, telecom or battery-backed cabinets, and machine control needing a regulated 24 V feed from an intermediate 48 V rail.

Specification

Full specification

114 values · Last verified 01 Nov 2026

General information 4

product brand name SITOP
product type designation PSU3400
product designation Power supply SITOP DC-DC converter
type of current supply 24 V/5 A

Input 14

type of the power supply network DC voltage
voltage curve at input DC
supply voltage at AC Startup as of 36 V, derating necessary for 28 ... 36 V DC
supply voltage at DC 48 V
input voltage at DC 28 ... 60 V
wide range input No
overvoltage overload capability -
buffering time for rated value of the output current in the event of power failure minimum 5 ms
operating condition of the mains buffering at Vin = 48 V
input current: at rated input voltage 48 V 2.7 A
current limitation of inrush current at 25 °C maximum 15 A
I2t value maximum 0.12 A2·s
fuse protection type 15 A (not accessible), breaking capacity 100 A
fuse protection type in the feeder Recommended miniature circuit breaker: 16 A characteristic B or C

Output 24

voltage curve at output Controlled, isolated DC voltage
product function output voltage controlled Yes
product function output voltage stabilized Yes
output voltage at DC rated value 24 V
output voltage: at output 1 at DC rated value 24 V
output voltage: at output 1 at DC 24 V
output voltage adjustable Yes; via potentiometer
adjustable output voltage 24 ... 28 V
relative overall tolerance of the voltage 1%
relative control precision of the output voltage: on slow fluctuation of input voltage 0.1 %
residual ripple: maximum 150 mV
residual ripple: typical 70 mV
voltage peak: maximum 250 mV
voltage peak: typical 220 mV
display version for normal operation Green LED for 24 V OK
behavior of the output voltage when switching on No overshoot of Vout (soft start)
response delay maximum 0.5 s
voltage increase time of the output voltage: typical 10 ms
voltage increase time of the output voltage: maximum 20 ms
output current: rated value 5 A
output current: rated range 0 ... 6 A; 6 A up to +40°C; +60 ... +70 °C: Derating 2%/K
supplied active power typical 130 W
bridging of equipment Yes
number of parallel-switched equipment resources for increasing the power 2
Show all 114 specifications ↓ Show less ↑72 more values in Identification, Efficiency, Closed-loop control, Protection and monitoring, Safety, EMC, Standards, specifications, approvals, Standards, specifications, approvals marine classification, Ambient conditions, Connection method, Mechanical data, Accessories, Additional information, Version Classification, Logistics.

Identification 10

Part number 6EP3233-0TA00-0AY0
Type designation PSU3400
Brand Siemens
Condition New, factory sealed
Source Siemens and its authorised distributors
Warranty Manufacturer warranty
Lifecycle status Active, in production
EAN 4025515155522
ETIM class EC002540
eCl@ss 27040701

Efficiency 3

efficiency in percent 92 %
power loss [W]: at rated output voltage for rated value of the output current typical 10 W
power loss [W]: during no-load operation maximum 1.5 W

Closed-loop control 4

relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical 0.3 %
relative control precision of the output voltage load step of resistive load 50/100/50 % typical 2%
setting time: load step 50 to 100% typical 1 ms
setting time: load step 100 to 50% typical 1 ms

Protection and monitoring 5

design of the overvoltage protection Ua < 35 V
property of the output short-circuit proof Yes
design of short-circuit protection Electronic shutdown, automatic restart
typical 6.5 A
display version for overload and short circuit LED yellow for "overload"

Safety 4

galvanic isolation between input and output Yes
galvanic isolation Output voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7)
operating resource protection class Class III
protection class IP IP20

EMC 3

standard: for emitted interference EN 61000-6-3
standard: for mains harmonics limitation not applicable
standard: for interference immunity EN 61000-6-2

Standards, specifications, approvals 8

certificate of suitability: CE marking Yes
certificate of suitability: UL approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
certificate of suitability: EAC approval Yes
certificate of suitability: Regulatory Compliance Mark (RCM) Yes
certificate of suitability: NEC Class 2 No
type of certification: CB-certificate Yes
MTBF at 40 °C 1 965 061 h
standards, specifications, approvals hazardous environments certificate of suitability: IECEx No

Standards, specifications, approvals marine classification 5

shipbuilding approval Yes
Marine classification association: American Bureau of Shipping Europe Ltd. (ABS) Yes
Marine classification association: French marine classification society (BV) No
Marine classification association: Det Norske Veritas (DNV) Yes
Marine classification association: Lloyds Register of Shipping (LRS) No

Ambient conditions 4

ambient temperature: during operation -25 ... +70 °C; with natural convection
ambient temperature: during transport -40 ... +85 °C
ambient temperature: during storage -40 ... +85 °C
environmental category according to IEC 60721 Climate class 3K3, 5 ... 95% no condensation

Connection method 3

type of electrical connection screw terminal
at input L, N, FE: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded
at output +, -: 2 screw terminals each for 0.5 ... 2.5 mm2

Mechanical data 11

width × height × depth of the enclosure 32 × 100 × 100 mm
installation width × mounting height 32 mm × 200 mm
required spacing: top 50 mm
required spacing: bottom 50 mm
required spacing: left 0 mm
required spacing: right 0 mm
fastening method Snaps onto DIN rail EN 60715 35x7.5/15
DIN-rail mounting Yes
S7 rail mounting No
wall mounting No
housing can be lined up Yes

Accessories 1

electrical accessories Buffer module

Additional information 1

other information Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

Version Classification 4

eClass 16 27-04-07-01
ETIM 10 EC002540
IDEA 4 4130
UNSPSC 15 39-12-10-04

Logistics 6

Net weight 0.32 kg
Country of origin HU
Shipping weight 0.82 kg
Ships from Türkiye
Dispatch —
Stock On request

Source: manufacturer data · Last verified: 01 Nov 2026

Documents

Documents for 6EP3233-0TA00-0AY0

No documents are on file for this part yet.

Ask us for the datasheet
Certifications

Certifications and standards

  • CE
  • EAC
  • CE marking
  • EAC approval
  • Regulatory Compliance Mark (RCM)
  • CB-certificate
  • shipbuilding approval
  • American Bureau of Shipping Europe Ltd. (ABS)
  • Det Norske Veritas (DNV)
Quick answers

Questions about the PSU3400

What is the rated current of PSU3400?

The rated current of PSU3400 is 5 A.

What motor power is PSU3400 rated for?

The rated motor power of PSU3400 is 10 W kW.

What is the HS code of PSU3400 for customs?

The tariff (HS) code on file for PSU3400 is 85044095.

What is the EAN of PSU3400?

The EAN (GTIN) of PSU3400 is 4025515155522.

Where does PSU3400 ship from, and how fast?

PSU3400 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.

Guides

Guides for power supplies

All guides for power supplies
Reviews

Customer reviews

Series

Siemens SITOP PSU3400

Brand
Siemens
Series
SITOP PSU3400
Series page →
$216.32 On request
Get a Quote
Quote

Get a Quote

PSU3400

Genuine parts

Genuine, factory-sealed parts

Siemens · 6EP3233-0TA00-0AY0

Every part on Stoklink is new, unused and made by the manufacturer named on the page.

Condition
New and unused, in the manufacturer's factory-sealed packaging.
Sourced from
Siemens and its authorised distributors.
Warranty
The manufacturer's warranty applies.
If a part is not genuine
We refund the full amount.

Added to cart Could not add to cart

View cart