SITOP PSE200U 4-channel selectivity module, 24V DC/40A in, 4x10A adjustable outputs, IP20.
The Siemens 6EP1961-2BA41 SITOP PSE200U is a 4-channel selectivity module that splits a single 24 V DC/40 A power supply into four individually protected 10 A outputs, so a fault on one branch trips only that channel instead of the whole supply. Each output's trip threshold is adjustable from 3 to 10 A via potentiometer, and a three-color LED plus a status signal per channel reports switched, manually off, or overcurrent-tripped state.
Each of the four outputs has an independently adjustable 3-10 A threshold, so branch circuits with different load currents can each be tuned to trip on their own overcurrent instead of pulling down the shared 40 A input. Compared to protecting downstream loads with a single breaker on the main feed, this module isolates only the faulted branch while the other three channels stay live — relevant when several PLC racks or I/O stations share one 24 V DC supply and an unplanned shutdown of all of them is not acceptable. The remote reset input lets a controller re-enable a tripped output without local access to the module.
Used downstream of a central 24 V DC power supply to give each PLC rack, remote I/O station, or field device group its own protected, individually resettable branch circuit.
| product brand name | SITOP |
|---|---|
| product type designation | PSE200U |
| product designation | SITOP Selectivity module |
| type of current supply | Selectivity module, 4 x 10 A Single-channel signaling |
| type of the power supply network | Controlled DC voltage |
|---|---|
| supply voltage at DC rated value | 24 V |
| input voltage at DC | 22 ... 30 V |
| overvoltage overload capability | 35 V |
| input current at rated input voltage 24 V rated value | 40 A |
| voltage curve at output | controlled DC voltage |
|---|---|
| formula for output voltage | Vin - approx. 0.2 V |
| relative overall tolerance of the voltage note | In accordance with the supplying input voltage |
| number of outputs | 4 |
| output current up to 60 °C per output rated value | 10 A |
| adjustable current response value current of the current-dependent overload release | 3 ... 10 A |
| type of response value setting | via potentiometer |
| response delay maximum | 5 s |
| product feature parallel switching of outputs | No |
| type of outputs connection | simultaneous switch-on of all outputs after power-up of the supply voltage > 20 V, delay time of 25 ms, 100 ms, or "load-optimized" via DIP switch configurable for sequential switch-on |
| Part number | 6EP1961-2BA41 |
|---|---|
| Type designation | PSE200U |
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4025515153405 |
| ETIM class | EC001440 |
| eCl@ss | 27371802 |
| efficiency in percent | 99 % |
|---|---|
| power loss [W] at rated output voltage for rated value of the output current typical | 10 W |
| switching characteristic: of the excess current | Iout = 1.0 ...1.5 x set value, switch-off after approx. 5 s |
|---|---|
| switching characteristic: of the current limitation | Iout = 1.5 x set value, switch-off after typ. 100 ms |
| switching characteristic: of the immediate switch-off | Iout > set value and Vin < 20 V, switch-off after approx. 0.5 ms |
| residual current at switch-off typical | 1 mA |
| design of the reset device/resetting mechanism | via sensor per output |
| remote reset function | non-isolated 24 V input (signal level "high" at > 15 V) |
| fuse protection type at input | 15 A per output (not accessible) |
|---|---|
| display version for normal operation | Three-color LED per output: green LED for "Output switched through"; yellow LED for "Output switched off manually"; red LED for "Output switched off due to overcurrent" |
| design of the switching contact for signaling function | Status signal output (pulse/pause signal, can be evaluated via Simatic function block) |
| galvanic isolation between input and output at switch-off | No |
|---|---|
| standard for safety | according to EN 62368-1 |
| operating resource protection class | Class III |
| protection class IP | IP20 |
| standard: for emitted interference | EN 55022 Class B |
| standard: for interference immunity | EN 61000-6-2 |
| certificate of suitability: CE marking | Yes |
|---|---|
| certificate of suitability: UL approval | Yes; UL-Recognized (UL 2367) File E328600; cULus-Listed (UL 508, CSA C22.2 No. 107.1) File E197259 |
| certificate of suitability: UKCA marking | Yes |
| certificate of suitability: EAC approval | Yes |
| type of certification: CB-certificate | Yes |
| MTBF at 40 °C | 540 979 h |
| certificate of suitability: IECEx | No |
|---|---|
| certificate of suitability: ATEX | No |
| shipbuilding approval | Yes |
|---|---|
| Marine classification association: American Bureau of Shipping Europe Ltd. (ABS) | Yes |
| Marine classification association: Det Norske Veritas (DNV) | Yes |
| Environmental Product Declaration | Yes |
|---|---|
| global warming potential [CO2 eq]: total | 283 kg |
| global warming potential [CO2 eq]: during manufacturing | 8.7 kg |
| global warming potential [CO2 eq]: during operation | 274 kg |
| global warming potential [CO2 eq]: after end of life | 0.2 kg |
| Siemens eco profile (SEP) | Siemens EcoTech |
| ambient temperature: during operation | -25 ... +60 °C; with natural convection |
|---|---|
| ambient temperature: during transport | -40 ... +85 °C |
| ambient temperature: during storage | -40 ... +85 °C |
| environmental category according to IEC 60721 | Climate class 3K3, 5 ... 95% no condensation |
| type of electrical connection | screw terminal |
|---|---|
| at input | +24 V: 2 screw terminals for 0.5 ... 16 mm2; 0 V: 2 screw terminals for 0.5 ... 4 mm2 |
| at output | Output 1 ... 4: 1 screw terminal each for 0.5 ... 4 mm2 |
| for auxiliary contacts | Remote reset: 1 screw terminal for 0.5 ... 4 mm2 |
| for signaling contact | 1 screw terminal for 0.5 ... 4 mm2 |
| width × height × depth of the enclosure | 72 × 80 × 72 mm |
|---|---|
| installation width × mounting height | 72 mm × 180 mm |
| required spacing: top | 50 mm |
| required spacing: bottom | 50 mm |
| required spacing: left | 0 mm |
| required spacing: right | 0 mm |
| fastening method | Snaps onto DIN rail EN 60715 35x7.5/15 |
| DIN-rail mounting | Yes |
| S7 rail mounting | No |
| wall mounting | No |
| housing can be lined up | Yes |
| mechanical accessories | Device identification label 20 mm × 7 mm, TI-grey 3RT2900-1SB20 |
|---|
| identification link | Yes; acc. to IEC 61406-1:2022 |
|---|
| other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
|---|
| Net weight | 0.22 kg |
|---|---|
| Country of origin | Romania |
| Shipping weight | 0.72 kg |
| Ships from | Türkiye |
| Dispatch | 13 Nov |
| Stock | In stock |
Source: manufacturer data · Last verified: 01 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of PSE200U is 10 A.
The rated operational voltage of PSE200U is 24 V AC.
The rated motor power of PSE200U is 10 W kW.
The tariff (HS) code on file for PSE200U is 85363010.
The EAN (GTIN) of PSE200U is 4025515153405.
PSE200U ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.