Siemens 6EP1961-2BA21 SITOP PSE200U 24V DC 4x10A Power Supply Selectivity Module

Siemens 6EP1961-2BA21 SITOP PSE200U selectivity module, 4x10A outputs, 24V DC, adjustable 3-10A threshold.

Rated current
10 A
Rated operational voltage
24 V AC
Motor power
10 W kW
Display
3-color LED per output (green/yellow/red)
EAN
4025515152668
Description

About the PSE200U

The Siemens 6EP1961-2BA21 SITOP PSE200U is a 4-channel selectivity module that splits a 24 V DC, 40 A input into four individually protected 10 A outputs with a current threshold adjustable from 3 to 10 A per channel. A common signaling contact reports overload status, and each channel switches off within about 5 seconds of exceeding its set threshold.

Certifications & Standards

  • CE
  • UKCA
  • EAC
  • CB
  • ABS
  • DNV
  • EPD

Selection Notes

The 3-10 A per-channel threshold, set individually by potentiometer, lets each of the four branch circuits trip before a fault pulls down the shared 24 V bus - choose the DIP-switch load-optimized sequential switch-on mode when downstream loads have high inrush current, such as several PLC power supplies powering up together, rather than the simultaneous mode. The 99% efficiency and 10 W typical power loss keep cabinet heat load low even with all four channels near their 10 A rating. The common signal contact wires a single alarm back to the PLC instead of monitoring four channels individually.

Applications

Selective load distribution downstream of a single 24 V DC power supply, separating PLC, HMI, I/O, and sensor or actuator branch circuits so a short on one branch does not take down the whole 24 V bus.

Specification

Full specification

92 values · Last verified 01 Nov 2026

General information 4

product brand name SITOP
product type designation PSE200U
product designation SITOP Selectivity module
type of current supply Selectivity module, 4 x 10 A Common signal contact

Input 5

type of the power supply network Controlled DC voltage
supply voltage at DC rated value 24 V
input voltage at DC 22 ... 30 V
overvoltage overload capability 35 V
input current at rated input voltage 24 V rated value 40 A

Output 10

voltage curve at output controlled DC voltage
formula for output voltage Vin - approx. 0.2 V
relative overall tolerance of the voltage note In accordance with the supplying input voltage
number of outputs 4
output current up to 60 °C per output rated value 10 A
adjustable current response value current of the current-dependent overload release 3 ... 10 A
type of response value setting via potentiometer
response delay maximum 5 s
product feature parallel switching of outputs No
type of outputs connection simultaneous switch-on of all outputs after power-up of the supply voltage > 20 V, delay time of 25 ms, 100 ms, or "load-optimized" via DIP switch configurable for sequential switch-on
Show all 92 specifications ↓ Show less ↑73 more values in Identification, Efficiency, Switch-off characteristic, Protection and monitoring, Safety, Standards, specifications, approvals, Standards, specifications, approvals hazardous environments, Standards, specifications, approvals marine classification, Standards, specifications, approvals Environmental Product Declaration, Ambient conditions, Connection method, Mechanical data, Accessories, Further information internet links, Additional information, Logistics.

Identification 10

Part number 6EP1961-2BA21
Type designation PSE200U
Brand Siemens
Condition New, factory sealed
Source Siemens and its authorised distributors
Warranty Manufacturer warranty
Lifecycle status Active, in production
EAN 4025515152668
ETIM class EC001440
eCl@ss 27371802

Efficiency 2

efficiency in percent 99 %
power loss [W] at rated output voltage for rated value of the output current typical 10 W

Switch-off characteristic 6

switching characteristic: of the excess current Iout = 1.0 ...1.5 x set value, switch-off after approx. 5 s
switching characteristic: of the current limitation Iout = 1.5 x set value, switch-off after typ. 100 ms
switching characteristic: of the immediate switch-off Iout > set value and Vin < 20 V, switch-off after approx. 0.5 ms
residual current at switch-off typical 1 mA
design of the reset device/resetting mechanism via sensor per output
remote reset function non-isolated 24 V input (signal level "high" at > 15 V)

Protection and monitoring 3

fuse protection type at input 15 A per output (not accessible)
display version for normal operation Three-color LED per output: green LED for "Output switched through"; yellow LED for "Output switched off manually"; red LED for "Output switched off due to overcurrent"
design of the switching contact for signaling function Common signal contact (changeover contact, rating 0.1 A/24 V DC)

Safety 6

galvanic isolation between input and output at switch-off No
standard for safety according to EN 62368-1
operating resource protection class Class III
protection class IP IP20
standard: for emitted interference EN 55022 Class B
standard: for interference immunity EN 61000-6-2

Standards, specifications, approvals 6

certificate of suitability: CE marking Yes
certificate of suitability: UL approval Yes; UL-Recognized (UL 2367) File E328600; cULus-Listed (UL 508, CSA C22.2 No. 107.1) File E197259
certificate of suitability: UKCA marking Yes
certificate of suitability: EAC approval Yes
type of certification: CB-certificate Yes
MTBF at 40 °C 540 979 h

Standards, specifications, approvals hazardous environments 2

certificate of suitability: IECEx No
certificate of suitability: ATEX No

Standards, specifications, approvals marine classification 3

shipbuilding approval Yes
Marine classification association: American Bureau of Shipping Europe Ltd. (ABS) Yes
Marine classification association: Det Norske Veritas (DNV) Yes

Standards, specifications, approvals Environmental Product Declaration 6

Environmental Product Declaration Yes
global warming potential [CO2 eq]: total 283 kg
global warming potential [CO2 eq]: during manufacturing 8.7 kg
global warming potential [CO2 eq]: during operation 274 kg
global warming potential [CO2 eq]: after end of life 0.2 kg
Siemens eco profile (SEP) Siemens EcoTech

Ambient conditions 4

ambient temperature: during operation -25 ... +60 °C; with natural convection
ambient temperature: during transport -40 ... +85 °C
ambient temperature: during storage -40 ... +85 °C
environmental category according to IEC 60721 Climate class 3K3, 5 ... 95% no condensation

Connection method 5

type of electrical connection screw terminal
at input +24 V: 2 screw terminals for 0.5 ... 16 mm2; 0 V: 2 screw terminals for 0.5 ... 4 mm2
at output Output 1 ... 4: 1 screw terminal each for 0.5 ... 4 mm2
for auxiliary contacts Remote reset: 1 screw terminal for 0.5 ... 4 mm2
for signaling contact 3 screw terminals for 0.5 ... 4 mm2

Mechanical data 11

width × height × depth of the enclosure 72 × 80 × 72 mm
installation width × mounting height 72 mm × 180 mm
required spacing: top 50 mm
required spacing: bottom 50 mm
required spacing: left 0 mm
required spacing: right 0 mm
fastening method Snaps onto DIN rail EN 60715 35x7.5/15
DIN-rail mounting Yes
S7 rail mounting No
wall mounting No
housing can be lined up Yes

Accessories 1

mechanical accessories Device identification label 20 mm × 7 mm, TI-grey 3RT2900-1SB20

Additional information 1

other information Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

Logistics 6

Net weight 0.22 kg
Country of origin Romania
Shipping weight 0.72 kg
Ships from Türkiye
Dispatch 13 Nov
Stock Low stock

Source: manufacturer data · Last verified: 01 Nov 2026

Documents

Documents for 6EP1961-2BA21

No documents are on file for this part yet.

Ask us for the datasheet
Certifications

Certifications and standards

  • CE
  • DNV
  • EAC
  • CE marking
  • UKCA marking
  • EAC approval
  • CB-certificate
  • shipbuilding approval
  • American Bureau of Shipping Europe Ltd. (ABS)
  • Det Norske Veritas (DNV)
  • Environmental Product Declaration
Quick answers

Questions about the PSE200U

What is the rated current of PSE200U?

The rated current of PSE200U is 10 A.

Which supply voltage is PSE200U rated for?

The rated operational voltage of PSE200U is 24 V AC.

What motor power is PSE200U rated for?

The rated motor power of PSE200U is 10 W kW.

What is the HS code of PSE200U for customs?

The tariff (HS) code on file for PSE200U is 85363010.

What is the EAN of PSE200U?

The EAN (GTIN) of PSE200U is 4025515152668.

Where does PSE200U ship from, and how fast?

PSE200U ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.

Guides

Guides for power supplies

All guides for power supplies
Reviews

Customer reviews

Series

Siemens SITOP PSE200U

Brand
Siemens
Series
SITOP PSE200U
Series page →
$173.88 Low stock · 13 Nov
Quote

Get a Quote

PSE200U

Genuine parts

Genuine, factory-sealed parts

Siemens · 6EP1961-2BA21

Every part on Stoklink is new, unused and made by the manufacturer named on the page.

Condition
New and unused, in the manufacturer's factory-sealed packaging.
Sourced from
Siemens and its authorised distributors.
Warranty
The manufacturer's warranty applies.
If a part is not genuine
We refund the full amount.

Added to cart Could not add to cart

View cart