Siemens Air Circuit Breaker Generations: 3WA vs 3WL vs 3WT Compared
ACB Comparison of Siemens 3WA, 3WL, and 3WT generations: ratings, trip units, replacement strategy, and procurement guidance for engineers. Shop at Stoklink.
| Motor power kW | Rated current In (A) | Part number | Stock | Price |
|---|---|---|---|---|
| 630 | 3WA1106-2AB12-0AA0 | On request | $3,948.04 | |
| 800 | 3WA1108-2AB12-0AA0This part | On request | $4,095.89 | |
| 1000 | 3WA1110-2AB12-0AA0 | On request | $4,336.34 | |
| 1250 | 3WA1112-2AB12-0AA0 | On request | $4,950.23 | |
| 1600 | 3WA1116-2AB12-0AA0 | On request | $6,552.64 |
The Siemens 3WA1108-2AB12-0AA0 is a fixed-mounted, horizontally connected 4-pole air circuit breaker in the SENTRON 3WA series, rated at 800 A continuous current with a rated breaking capacity (Icu) of 55 kA up to 500 V (42 kA at 690 V AC). It is supplied with the ETU300 LSI electronic trip unit and 2NO+2NC auxiliary contacts factory-fitted, dimensioned for main and sub-distribution switchgear operating up to 690 V.
At 800 A and frame Size I, the 3WA1108-2AB12-0AA0 carries a class breaking capacity of 55 kA (Icu, up to 500 V). The fourth (neutral) pole is switched and protected with the phases, as required on TN-C-S and TT systems where the neutral must be isolated.
Fixed mounting removes the draw-out cradle and shutter mechanism, reducing panel depth and cubicle cost where the 800 A breaker does not need to be withdrawn under a live bus. The ETU300 LSI trip unit provides long-time (L), short-time (S) and instantaneous (I) protection with independent settings for time-current selectivity. The factory-fitted 2NO+2NC auxiliary contacts wire directly into PLC inputs for position and status signalling.
| product brand name | SENTRON |
|---|---|
| product designation | Air circuit breaker |
| suitability for use | circuit breaker |
| size of the circuit-breaker | I |
| number of poles | 4 |
| position / of neutral conductor | neutral left |
| fastening method | fixed-mounted circuit breakers |
| design of the product | AC application |
| type of the driving mechanism | manual operating mechanism with mechanical or electrical closing |
| design of the electronic trip unit | ETU300 LSI |
| Weight | 49.96 kg |
| insulation voltage / rated value | 1000 V |
|---|---|
| operating voltage / at AC / at 50/60 Hz / rated value | 690 V |
| power loss [W] / maximum | 45 W |
| continuous current / rated value / maximum | 800 A |
|---|---|
| continuous current / rated value | 800 A |
| operational current: at 40 °C / rated value | 800 A |
| operational current: at 45 °C / rated value | 800 A |
| operational current: at 50 °C / rated value | 800 A |
| operational current: at 55 °C / rated value | 800 A |
| operational current: at 60 °C / rated value | 800 A |
| operational current: at 65 °C / rated value | 800 A |
| operational current: at 70 °C / rated value | 800 A |
| Part number | 3WA1108-2AB12-0AA0 |
|---|---|
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| ETIM class | EC000228 |
| eCl@ss | 27370409 |
| switching capacity class of the circuit breaker | N |
|---|---|
| maximum short-circuit current breaking capacity (Icu): at 500 V / rated value | 55 kA |
| maximum short-circuit current breaking capacity (Icu): at 690 V / rated value | 42 kA |
| operating short-circuit current breaking capacity (Ics): at 500 V / rated value | 55 kA |
| operating short-circuit current breaking capacity (Ics): at 690 V / rated value | 42 kA |
| short-circuit current making capacity (Icm): at 500 V / rated value | 121 kA |
| short-circuit current making capacity (Icm): at 690 V / rated value | 88 kA |
| short-time withstand current (Icw) / at 500 V AC: for 0.5 s / rated value | 55 kA |
| short-time withstand current (Icw) / at 500 V AC: for 1 s / rated value | 50 kA |
| short-time withstand current (Icw) / at 500 V AC: for 2 s / rated value | 35 kA |
| short-time withstand current (Icw) / at 500 V AC: for 3 s / rated value | 30 kA |
| short-time withstand current (Icw) / at 690 V AC: for 0.5 s / rated value | 42 kA |
| short-time withstand current (Icw) / at 690 V AC: for 1 s / rated value | 42 kA |
| short-time withstand current (Icw) / at 690 V AC: for 2 s / rated value | 35 kA |
| short-time withstand current (Icw) / at 690 V AC: for 3 s / rated value | 30 kA |
| product feature: upgradable | No |
|---|---|
| product feature: Bluetooth and USB interface | No |
| product feature: decoder for basic protection functions | Yes |
| product feature: display and function keys | No |
| product feature: SENTRON powerconfig configuration software | No |
| product feature / for L-tripping: can be switched on/off | No |
|---|---|
| product feature / for L-tripping: selectable characteristic function | No |
| product feature / for L-tripping: decoder and infinite adjustability are selectable with eSet | No |
| set values setting current (Ir) / for L-tripping / with I2t characteristic | 0.4;0.5;0.6;0.7;0.75;0.8;0.85;0.9;0.95;1 |
| reference value setting current (Ir) / for L-tripping / with I2t characteristic | x In |
| set values delay time (tr) / for L-tripping / with I2t characteristic | 0.75;1;2;5;8;10;14;17;21;25 |
| reference value delay time (tr) / for L-tripping / with I2t characteristic | s |
| product feature / with neutral conductor protection / can be switched on/off | No |
|---|---|
| setting values setting current (InN) / for N-tripping | 1 |
| reference value setting current (InN) / for N-tripping | x In |
| S: delayed short-circuit protection ST product feature / for S-tripping: independent of direction / can be switched on/off | Yes |
| set values setting current (Isd) / for S-tripping / with I0t characteristic | 1.5;2;2.5;3;4;5;6;8;10 |
|---|---|
| reference value setting current (Isd) / for S-tripping / with I0t characteristic | x Ir |
| set values delay time (tsd) / for S-tripping / with I0t characteristic | 0.08;0.15;0.22;0.3;0.4 |
| reference value delay time (tsd) / for S-tripping / with I0t characteristic | s |
| set values setting current (Isd) / for S-tripping / with I2t characteristic | 1.5;2;2.5;3;4;5;6;8;10 |
|---|---|
| reference value setting current (Isd) / for S-tripping / with I2t characteristic | x Ir |
| set values delay time (tsd) / for S-tripping / with I2t characteristic | 0.08;0.15;0.22;0.3;0.4 |
| product feature / for I-tripping: can be switched on/off | No |
| product feature / for I-tripping: decoder and infinite adjustability are selectable (with eSet) | No |
| set values setting current (Ii) / for I-tripping | 1.5;2;3;4;5;6;8;10;12;15 |
| reference value setting current (Ii) / for I-tripping | x In |
| product feature / for G-tripping: selectable characteristic function | No |
|---|
| protection function: maintenance mode DAS+ | Yes |
|---|
| measurement function: current measurement | Yes |
|---|
| communication function | No |
|---|
| mechanical service life (operating cycles): without support / typical | 15000 |
|---|---|
| mechanical service life (operating cycles): with support / typical | 30000 |
| electrical endurance (operating cycles): at 690 V / without support / typical | 10000 |
| electrical endurance (operating cycles): at 690 V / with support / typical | 30000 |
| height | 437 mm |
|---|---|
| width | 410 mm |
| depth | 357 mm |
| arrangement of electrical connectors / for main current circuit | main connection on the rear, horizontal |
|---|
| design of the auxiliary switch | 2 NO + 2 NC |
|---|---|
| number of NC contacts / for auxiliary contacts | 2 |
| number of NO contacts / for auxiliary contacts | 2 |
| number of CO contacts / for auxiliary contacts | 0 |
| product component: undervoltage release | No |
|---|---|
| product component: voltage trigger | No |
| product component: trip indicator | Yes |
| product component: motor drive | No |
| protection class IP / on the front | IP20 |
|---|---|
| ambient temperature / during operation: minimum | -40 °C |
| ambient temperature / during operation: maximum | 70 °C |
| ambient temperature / during storage: minimum | -40 °C |
| ambient temperature / during storage: maximum | 80 °C |
| reference code / according to IEC 81346-2 | Q |
|---|
| Environment General Product Approval | Radio Equipment |
|---|---|
| General Product Approval EMV Type Approval Certi- Test Certificates | ficate |
| Net weight | 36.96 kg |
|---|---|
| Country of origin | CZ |
| Shipping weight | 41.96 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheet| Motor power | Rated current | Part number | Model no | Stock | Dispatch | Price | Add to cart |
|---|---|---|---|---|---|---|---|
| 630 A | 3WA1106-2AB12-0AA0 | 3WA | On request | — | $3,948.04 | Quote | |
| 800 A | 3WA1108-2AB12-0AA0 This part | 3WA | On request | — | $4,095.89 | Quote | |
| 1000 A | 3WA1110-2AB12-0AA0 | 3WA | On request | — | $4,336.34 | Quote | |
| 1250 A | 3WA1112-2AB12-0AA0 | 3WA | On request | — | $4,950.23 | Quote | |
| 1600 A | 3WA1116-2AB12-0AA0 | 3WA | On request | — | $6,552.64 | Quote | |
| 2000 A | 3WA1120-2AB12-0AA0 | 3WA | Critical stock | $6,930.52 | |||
| 2500 A | 3WA1125-2AB12-0AA0 | 3WA | On request | — | $8,147.19 | Quote |
The rated current of 3WA1108-2AB12-0AA0 is 800 A.
The rated operational voltage of 3WA1108-2AB12-0AA0 is 690 V AC.
3WA1108-2AB12-0AA0 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
ACB Comparison of Siemens 3WA, 3WL, and 3WT generations: ratings, trip units, replacement strategy, and procurement guidance for engineers. Shop at Stoklink.
Compare 1600-2500A ACB platforms: ABB Emax 2, Schneider MTZ2, Siemens 3WL2 on breaking capacity, trip units, endurance and lifecycle cost. Shop at Stoklink.
ABB Emax 2 air circuit breaker selection, sizing, trip units, selectivity, and maintenance guide for 630 to 6300 A LV switchgear engineers. Shop at...