Part number
3WA1106-2AB02-0AA0
$2,790.22 On request Dispatch — · From TürkiyeGet a Quote

Siemens 3WA1106-2AB02-0AA0 3WA 3-Pole 630A 55kA 690V Fixed Type Air Circuit Breaker ETU300 LSI

Rated current
630 A
Rated operational voltage
690 V AC
Poles
3P
Breaking capacity
55 (≤500) – 42 (690) kA
Other ratings in Siemens 3WA All 7 ratings ↓
Neighbouring ratings in the same series
Motor power kW Rated current In (A) Part number Stock Price
630 3WA1106-2AB02-0AA0This part On request $2,790.22
800 3WA1108-2AB02-0AA0 On request $2,853.15
1000 3WA1110-2AB02-0AA0 On request $2,434.98
1250 3WA1112-2AB02-0AA0 Critical stock $2,946.83
1600 3WA1116-2AB02-0AA0 Low stock $3,872.05
Description

About the 3WA1106-2AB02-0AA0

The Siemens 3WA1106-2AB02-0AA0 is a fixed-mounted, horizontally connected 3-pole air circuit breaker in the SENTRON 3WA series, rated at 630 A continuous current with a rated breaking capacity (Icu) of 55 kA up to 500 V (42 kA at 690 V AC). It is supplied with the ETU300 LSI electronic trip unit and 2NO+2NC auxiliary contacts factory-fitted, dimensioned for main and sub-distribution switchgear operating up to 690 V.

Certifications & Standards

  • IEC 60947-2

Selection Notes

At 630 A and frame Size I, the 3WA1106-2AB02-0AA0 carries a class breaking capacity of 55 kA (Icu, up to 500 V). Three-pole switching covers the phase conductors for standard three-phase distribution.

Fixed mounting removes the draw-out cradle and shutter mechanism, reducing panel depth and cubicle cost where the 630 A breaker does not need to be withdrawn under a live bus. The ETU300 LSI trip unit provides long-time (L), short-time (S) and instantaneous (I) protection with independent settings for time-current selectivity. The factory-fitted 2NO+2NC auxiliary contacts wire directly into PLC inputs for position and status signalling.

Specification

Full specification

108 values · Last verified 30 Oct 2026

Model 11

product brand name SENTRON
product designation Air circuit breaker
suitability for use circuit breaker
size of the circuit-breaker I
number of poles 3
position / of neutral conductor no internal N-conductor
fastening method fixed-mounted circuit breakers
design of the product AC application
type of the driving mechanism manual operating mechanism with mechanical or electrical closing
design of the electronic trip unit ETU300 LSI
Weight 44.026 kg

General technical data 3

insulation voltage / rated value 1000 V
operating voltage / at AC / at 50/60 Hz / rated value 690 V
power loss [W] / maximum 30 W

Current 9

continuous current / rated value / maximum 630 A
continuous current / rated value 630 A
operational current: at 40 °C / rated value 630 A
operational current: at 45 °C / rated value 630 A
operational current: at 50 °C / rated value 630 A
operational current: at 55 °C / rated value 630 A
operational current: at 60 °C / rated value 630 A
operational current: at 65 °C / rated value 630 A
operational current: at 70 °C / rated value 630 A
Show all 108 specifications ↓ Show less ↑85 more values in Identification, Switching capacity and short-time withstand current, according to IEC 60947-2, Electronic release unit, Basic protection functions, L: Overload protection N-conductor, S: delayed short-circuit protection ST, settings values I0t, S: delayed short-circuit protection ST, settings values I2t, G: ground fault GF, Further protective functions, Measuring functions, Communication, Service Life, Dimensions, Main connection, Auxiliary circuit, Internal accessories, Environmental conditions, Certificates, Radio Equipment, Logistics.

Identification 8

Part number 3WA1106-2AB02-0AA0
Brand Siemens
Condition New, factory sealed
Source Siemens and its authorised distributors
Warranty Manufacturer warranty
Lifecycle status Active, in production
ETIM class EC000228
eCl@ss 27370409

Switching capacity and short-time withstand current, according to IEC 60947-2 15

switching capacity class of the circuit breaker N
maximum short-circuit current breaking capacity (Icu): at 500 V / rated value 55 kA
maximum short-circuit current breaking capacity (Icu): at 690 V / rated value 42 kA
operating short-circuit current breaking capacity (Ics): at 500 V / rated value 55 kA
operating short-circuit current breaking capacity (Ics): at 690 V / rated value 42 kA
short-circuit current making capacity (Icm): at 500 V / rated value 121 kA
short-circuit current making capacity (Icm): at 690 V / rated value 88 kA
short-time withstand current (Icw) / at 500 V AC: for 0.5 s / rated value 55 kA
short-time withstand current (Icw) / at 500 V AC: for 1 s / rated value 50 kA
short-time withstand current (Icw) / at 500 V AC: for 2 s / rated value 35 kA
short-time withstand current (Icw) / at 500 V AC: for 3 s / rated value 30 kA
short-time withstand current (Icw) / at 690 V AC: for 0.5 s / rated value 42 kA
short-time withstand current (Icw) / at 690 V AC: for 1 s / rated value 42 kA
short-time withstand current (Icw) / at 690 V AC: for 2 s / rated value 35 kA
short-time withstand current (Icw) / at 690 V AC: for 3 s / rated value 30 kA

Electronic release unit 5

product feature: upgradable No
product feature: Bluetooth and USB interface No
product feature: decoder for basic protection functions Yes
product feature: display and function keys No
product feature: SENTRON powerconfig configuration software No

Basic protection functions 7

product feature / for L-tripping: can be switched on/off No
product feature / for L-tripping: selectable characteristic function No
product feature / for L-tripping: decoder and infinite adjustability are selectable with eSet No
set values setting current (Ir) / for L-tripping / with I2t characteristic 0.4;0.5;0.6;0.7;0.75;0.8;0.85;0.9;0.95;1
reference value setting current (Ir) / for L-tripping / with I2t characteristic x In
set values delay time (tr) / for L-tripping / with I2t characteristic 0.75;1;2;5;8;10;14;17;21;25
reference value delay time (tr) / for L-tripping / with I2t characteristic s

L: Overload protection N-conductor 4

product feature / with neutral conductor protection / can be switched on/off No
setting values setting current (InN) / for N-tripping 1
reference value setting current (InN) / for N-tripping x In
S: delayed short-circuit protection ST product feature / for S-tripping: independent of direction / can be switched on/off Yes

S: delayed short-circuit protection ST, settings values I0t 4

set values setting current (Isd) / for S-tripping / with I0t characteristic 1.5;2;2.5;3;4;5;6;8;10
reference value setting current (Isd) / for S-tripping / with I0t characteristic x Ir
set values delay time (tsd) / for S-tripping / with I0t characteristic 0.08;0.15;0.22;0.3;0.4
reference value delay time (tsd) / for S-tripping / with I0t characteristic s

S: delayed short-circuit protection ST, settings values I2t 7

set values setting current (Isd) / for S-tripping / with I2t characteristic 1.5;2;2.5;3;4;5;6;8;10
reference value setting current (Isd) / for S-tripping / with I2t characteristic x Ir
set values delay time (tsd) / for S-tripping / with I2t characteristic 0.08;0.15;0.22;0.3;0.4
product feature / for I-tripping: can be switched on/off No
product feature / for I-tripping: decoder and infinite adjustability are selectable (with eSet) No
set values setting current (Ii) / for I-tripping 1.5;2;3;4;5;6;8;10;12;15
reference value setting current (Ii) / for I-tripping x In

G: ground fault GF 1

product feature / for G-tripping: selectable characteristic function No

Further protective functions 1

protection function: maintenance mode DAS+ Yes

Measuring functions 1

measurement function: current measurement Yes

Communication 1

communication function No

Service Life 4

mechanical service life (operating cycles): without support / typical 15000
mechanical service life (operating cycles): with support / typical 30000
electrical endurance (operating cycles): at 690 V / without support / typical 10000
electrical endurance (operating cycles): at 690 V / with support / typical 30000

Dimensions 3

height 437 mm
width 320 mm
depth 357 mm

Main connection 1

arrangement of electrical connectors / for main current circuit main connection on the rear, horizontal

Auxiliary circuit 4

design of the auxiliary switch 2 NO + 2 NC
number of NC contacts / for auxiliary contacts 2
number of NO contacts / for auxiliary contacts 2
number of CO contacts / for auxiliary contacts 0

Internal accessories 4

product component: undervoltage release No
product component: voltage trigger No
product component: trip indicator Yes
product component: motor drive No

Environmental conditions 5

protection class IP / on the front IP20
ambient temperature / during operation: minimum -40 °C
ambient temperature / during operation: maximum 70 °C
ambient temperature / during storage: minimum -40 °C
ambient temperature / during storage: maximum 80 °C

Certificates 1

reference code / according to IEC 81346-2 Q

Radio Equipment 3

Type Approval Certi-ficate Test Certificates Maritime application
Miscellaneous Special Test Certific- Miscellaneous ate
Maritime application other

Logistics 6

Net weight 31.026 kg
Country of origin CZ
Shipping weight 36.026 kg
Ships from Türkiye
Dispatch —
Stock On request

Source: manufacturer data · Last verified: 30 Oct 2026

Documents

Documents for 3WA1106-2AB02-0AA0

No documents are on file for this part yet.

Ask us for the datasheet
Other ratings

All 7 ratings in Siemens 3WA

Siemens Siemens 3WA series page →
Other ratings in the same series
Motor power Rated current Part number Model no Stock Dispatch Price Add to cart
630 A 3WA1106-2AB02-0AA0 This part 3WA On request — $2,790.22 Quote
800 A 3WA1108-2AB02-0AA0 3WA On request — $2,853.15 Quote
1000 A 3WA1110-2AB02-0AA0 3WA On request — $2,434.98 Quote
1250 A 3WA1112-2AB02-0AA0 3WA Critical stock $2,946.83
1600 A 3WA1116-2AB02-0AA0 3WA Low stock $3,872.05
2000 A 3WA1120-2AB02-0AA0 3WA On request — $4,186.39 Quote
2500 A 3WA1125-2AB02-0AA0 3WA On request — $5,191.12 Quote
Certifications

Certifications and standards

  • IEC 60947-2
Quick answers

Questions about the 3WA1106-2AB02-0AA0

What is the rated current of 3WA1106-2AB02-0AA0?

The rated current of 3WA1106-2AB02-0AA0 is 630 A.

Which supply voltage is 3WA1106-2AB02-0AA0 rated for?

The rated operational voltage of 3WA1106-2AB02-0AA0 is 690 V AC.

Where does 3WA1106-2AB02-0AA0 ship from, and how fast?

3WA1106-2AB02-0AA0 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.

Guides

Guides for ACB

All guides for ACB
Reviews

Customer reviews

Series

Siemens Siemens 3WA

Brand
Siemens
Series
Siemens 3WA
Rated current
630–2500 A
Supply voltage
690 V AC
Ratings listed
7
Series page →
Series

Other series in Air Circuit Breakers (ACB)

$2,790.22 On request
Get a Quote
Quote

Get a Quote

Genuine parts

Genuine, factory-sealed parts

Siemens · 3WA1106-2AB02-0AA0

Every part on Stoklink is new, unused and made by the manufacturer named on the page.

Condition
New and unused, in the manufacturer's factory-sealed packaging.
Sourced from
Siemens and its authorised distributors.
Warranty
The manufacturer's warranty applies.
If a part is not genuine
We refund the full amount.

Added to cart Could not add to cart