Part number
3RW5248-6AC14
Model no
3RW52
$5,675.87 Low stock Dispatch Planned dispatch date. We aim to ship within 1 business day. Depending on warehouse workload it can take 2–3 business days. · From Türkiye

3RW5248-6AC14, Soft Starter, 315 kW, 570 A, 200 to 480V AC

Rated current
570 A
Rated operational voltage
200–480 V AC
Motor power
315 kW
Control voltage
110–250 V
Poles
3P
Display
No
EAN
4047621038285
Description

About the 3RW52

Siemens 3RW52 Soft Starter Series – Overview

Siemens 3RW52 soft starters are high-performance motor starting solutions designed for demanding industrial applications requiring precise and reliable control of three-phase asynchronous motors. The 3RW52 series focuses on reducing mechanical stress, limiting inrush current, and supporting higher motor power ratings with advanced protection functions compared to compact soft starters. With robust construction and enhanced motor protection capabilities, Siemens 3RW52 soft starters are well suited for heavy-duty applications such as large pumps, compressors, conveyors, mixers, and industrial process machinery where dependable motor starting and operational reliability are critical.


Product Description: 3RW5248-6AC14

The Siemens 3RW5248-6AC14 is a SIRIUS 3RW52 general‑performance soft starter rated for 570 A (Ie) and intended for three‑phase motor applications on 200…480 V AC mains. At standard inline connection the unit covers motors up to 315 kW at 400 V; when used in an inside‑delta configuration it supports ratings up to 560 kW at 400 V. The control supply for the device is 110…250 V AC and the starter uses three‑phase control with soft ramp-up and ramp-down capability plus adjustable current limitation — features that reduce mechanical shock and limit inrush current for large pumps, compressors, conveyors and other heavy industrial drives. This SKU includes an integrated bypass contactor to reduce heat loss during run and provides built‑in motor overload protection with thermistor input capability and analog output functionality for remote monitoring. The unit is supplied in an IP00 enclosure and is engineered for continuous industrial use at a rated ambient of 40 °C without derating.

Specification

Full specification

184 values · Last verified 30 Oct 2026

General 16

product brand name SIRIUS
product category Hybrid switching devices
product designation Soft starter
product type designation 3RW52
manufacturer's article number: of standard HMI module usable 3RW5980-0HS00
manufacturer's article number: of high feature HMI module usable 3RW5980-0HF00
manufacturer's article number: of communication module PROFINET standard usable 3RW5980-0CS00
manufacturer's article number: of communication module PROFIBUS usable 3RW5980-0CP00
manufacturer's article number: of communication module Modbus TCP usable 3RW5980-0CT00
manufacturer's article number: of communication module Ethernet/IP 3RW5980-0CE00
manufacturer's article number: of circuit breaker usable at 400 V 3VA2580-6HN32-0AA0; Type of coordination 1, Iq = 65 kA, CLASS 10
manufacturer's article number: of circuit breaker usable at 500 V 3VA2580-6HN32-0AA0; Type of coordination 1, Iq = 65 kA, CLASS 10
manufacturer's article number: of the gG fuse usable up to 690 V 2x3NA3365-6; Type of coordination 1, Iq = 65 kA
manufacturer's article number: of the gG fuse usable at inside-delta circuit up to 500 V 2x3NA3365-6; Type of coordination 1, Iq = 65 kA
manufacturer's article number: of full range R fuse link for semiconductor protection usable up to 690 V 3NE1437-2; Type of coordination 2, Iq = 65 kA
manufacturer's article number: of back-up R fuse link for semiconductor protection usable up to 690 V 3NE3340-8; Type of coordination 2, Iq = 65 kA

General technical data 49

starting voltage [%] 30 ... 100 %
stopping voltage [%] 50 %; non-adjustable
start-up ramp time of soft starter 0 ... 20 s
current limiting value [%] adjustable 130 ... 700 %
certificate of suitability: CE marking Yes
certificate of suitability: UL approval Yes
certificate of suitability: CSA approval Yes
product component: HMI-High Feature No
product component: is supported HMI-Standard Yes
product component: is supported HMI-High Feature Yes
product feature integrated bypass contact system Yes
number of controlled phases 3
buffering time in the event of power failure: for main current circuit 100 ms
buffering time in the event of power failure: for control circuit 100 ms
insulation voltage rated value 600 V
degree of pollution 3, acc. to IEC 60947-4-2
impulse voltage rated value 6 kV
blocking voltage of the thyristor maximum 1 600 V
service factor 1
surge voltage resistance rated value 6 kV
maximum permissible voltage for protective separation: between main and auxiliary circuit 600 V
shock resistance 15 g / 11 ms, from 12 g / 11 ms with potential contact lifting
vibration resistance 15 mm to 6 Hz; 2 g to 500 Hz
utilization category according to IEC 60947-4-2 AC 53a
reference code according to IEC 81346-2 Q
Substance Prohibitance (day/month/year) 02/15/2018
SVHC substance name Lead CAS-No. 7439-92-1 Lead monoxide (lead oxide) CAS-No. 1317-36-8 2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-one CAS-No. 71868- 10-5 Melamine CAS-No. 108-78-1 6,6'-di-tert-butyl-2,2'-methylenedi-p-cresol CAS-No. 119-47-1 Dibutylbis(pentane-2,4-dionato-O,O')tin CAS-No. 22673-19-4
product function: ramp-up (soft starting) Yes
product function: soft stopping Yes
product function: Soft Torque Yes
product function: adjustable current limitation Yes
product function: pump stop Yes
product function: intrinsic device protection Yes
product function: motor overload protection Yes; Electronic motor overload protection
product function: evaluation of thermistor motor protection No
product function: inside-delta circuit Yes
product function: auto-RESET Yes
product function: manual RESET Yes
product function: remote reset Yes; By turning off the control supply voltage
product function: communication function Yes
product function: operating measured value display Yes; Only in conjunction with special accessories
product function: error logbook Yes; Only in conjunction with special accessories
product function: via software parameterizable No
product function: via software configurable Yes
product function: PROFIenergy Yes; in connection with the PROFINET Standard communication module
product function: firmware update Yes
product function: removable terminal for control circuit Yes
product function: torque control No
product function: analog output Yes; 4 ... 20 mA (default) / 0 ... 10 V (parameterizable with High Feature HMI)

Power Electronics 31

operational current: at 40 °C rated value 570 A
operational current: at 50 °C rated value 504 A
operational current: at 60 °C rated value 460 A
operational current at inside-delta circuit: at 40 °C rated value 987 A
operational current at inside-delta circuit: at 50 °C rated value 873 A
operational current at inside-delta circuit: at 60 °C rated value 796 A
operating voltage: rated value 200 ... 480 V
operating voltage: at inside-delta circuit rated value 200 ... 480 V
relative negative tolerance of the operating voltage -15 %
relative positive tolerance of the operating voltage 10 %
relative negative tolerance of the operating voltage at inside-delta circuit -15 %
relative positive tolerance of the operating voltage at inside-delta circuit 10 %
operating power for 3-phase motors: at 230 V at 40 °C rated value 160 kW
operating power for 3-phase motors: at 230 V at inside-delta circuit at 40 °C rated value 315 kW
operating power for 3-phase motors: at 400 V at 40 °C rated value 315 kW
operating power for 3-phase motors: at 400 V at inside-delta circuit at 40 °C rated value 560 kW
Operating frequency 1 rated value 50 Hz
Operating frequency 2 rated value 60 Hz
relative negative tolerance of the operating frequency -10 %
relative positive tolerance of the operating frequency 10 %
adjustable motor current: at rotary coding switch on switch position 1 240 A
adjustable motor current: minimum 240 A
adjustable motor current: for inside-delta circuit at rotary coding switch on switch position 1 416 A
adjustable motor current: at inside-delta circuit minimum 416 A
minimum load [%] 15 %; Relative to smallest settable Ie
power loss [W] for rated value of the current at AC: at 40 °C after startup 183 W
power loss [W] for rated value of the current at AC: at 50 °C after startup 163 W
power loss [W] for rated value of the current at AC: at 60 °C after startup 153 W
power loss [W] at AC at current limitation 350%: at 40 °C during startup 10 241 W
power loss [W] at AC at current limitation 350%: at 50 °C during startup 8 500 W
power loss [W] at AC at current limitation 350%: at 60 °C during startup 7 663 W
Show all 184 specifications ↓ Show less ↑88 more values in Identification, Control circuit/ Control, Inputs/ Outputs, Installation/ mounting/ dimensions, Connections/ Terminals, Ambient conditions, Electromagnetic compatibility, Communication/ Protocol, UL/CSA ratings, Electrical Safety, Approvals Certificates, Logistics.

Identification 10

Part number 3RW5248-6AC14
Type designation 3RW52
Brand Siemens
Condition New, factory sealed
Source Siemens and its authorised distributors
Warranty Manufacturer warranty
Lifecycle status Active, in production
EAN 4047621038285
ETIM class EC000640
eCl@ss 27370907

Control circuit/ Control 15

type of voltage of the control supply voltage AC
control supply voltage at AC: at 50 Hz 110 ... 250 V
control supply voltage at AC: at 60 Hz 110 ... 250 V
relative negative tolerance of the control supply voltage at AC at 50 Hz -15 %
relative positive tolerance of the control supply voltage at AC at 50 Hz 10 %
control supply voltage frequency 50 ... 60 Hz
relative negative tolerance of the control supply voltage frequency -10 %
relative positive tolerance of the control supply voltage frequency 10 %
control supply current in standby mode rated value 30 mA
holding current in bypass operation rated value 100 mA
inrush current by closing the bypass contacts maximum 2.2 A
inrush current peak at application of control supply voltage maximum 12.2 A
duration of inrush current peak at application of control supply voltage 2.2 ms
design of the overvoltage protection Varistor
design of short-circuit protection for control circuit 4 A gG fuse (Icu=1 kA), 6 A quick-acting fuse (Icu=1 kA), C1 miniature circuit breaker (Icu= 600 A), C6 miniature circuit breaker (Icu= 300 A); Is not part of scope of supply

Inputs/ Outputs 7

number of digital inputs 1
number of digital outputs 3
not parameterizable 2
digital output version 2 normally-open contacts (NO) / 1 changeover contact (CO)
number of analog outputs 1
switching capacity current of the relay outputs: at AC-15 at 250 V rated value 3 A
switching capacity current of the relay outputs: at DC-13 at 24 V rated value 1 A

Installation/ mounting/ dimensions 11

mounting position with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
fastening method screw fixing
height 393 mm
width 210 mm
depth 203 mm
required spacing with side-by-side mounting: forwards 10 mm
required spacing with side-by-side mounting: backwards 0 mm
required spacing with side-by-side mounting: upwards 100 mm
required spacing with side-by-side mounting: downwards 75 mm
required spacing with side-by-side mounting: at the side 5 mm
weight without packaging 10.6 kg

Connections/ Terminals 12

type of electrical connection: for main current circuit busbar connection
type of electrical connection: for control circuit screw-type terminals
width of connection bar maximum 45 mm
type of connectable conductor cross-sections: for DIN cable lug for main contacts stranded 2x (50 ... 240 mm2)
type of connectable conductor cross-sections: for control circuit solid 1x (0.5 ... 4.0 mm2), 2x (0.5 ... 2.5 mm2)
type of connectable conductor cross-sections: for AWG cables for control circuit solid 1x (20 ... 12), 2x (20 ... 14)
wire length: between soft starter and motor maximum 800 m
wire length: at the digital inputs at AC maximum 100 m
tightening torque: for main contacts with screw-type terminals 14 ... 24 N·m
tightening torque: for auxiliary and control contacts with screw-type terminals 0.8 ... 1.2 N·m
tightening torque [lbf·in]: for main contacts with screw-type terminals 124 ... 210 lbf·in
tightening torque [lbf·in]: for auxiliary and control contacts with screw-type terminals 7 ... 10.3 lbf·in

Ambient conditions 6

installation altitude at height above sea level maximum 5 000 m
ambient temperature: during operation -25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
ambient temperature: during storage and transport -40 ... +80 °C
environmental category: during operation according to IEC 60721 3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
environmental category: during storage according to IEC 60721 1K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must not get inside the devices), 1M4
environmental category: during transport according to IEC 60721 2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)

Electromagnetic compatibility 1

EMC emitted interference acc. to IEC 60947-4-2: Class A

Communication/ Protocol 5

communication module is supported: PROFINET standard Yes
communication module is supported: EtherNet/IP Yes
communication module is supported: Modbus RTU Yes
communication module is supported: Modbus TCP Yes
communication module is supported: PROFIBUS Yes

UL/CSA ratings 11

of the fuse: usable for Standard Faults up to 575/600 V according to UL Type: Class J / L, max. 1600 A; Iq = 30 kA
of the fuse: usable for High Faults up to 575/600 V according to UL Type: Class J / L, max. 1200 A; Iq = 100 kA
of the fuse: usable for Standard Faults at inside-delta circuit up to 575/600 V according to UL Type: Class J / L, max. 1600 A; Iq = 30 kA
of the fuse: usable for High Faults at inside-delta circuit up to 575/600 V according to UL Type: Class J / L, max. 1200 A; Iq = 100 kA
operating power [hp] for 3-phase motors: at 200/208 V at 50 °C rated value 150 hp
operating power [hp] for 3-phase motors: at 220/230 V at 50 °C rated value 200 hp
operating power [hp] for 3-phase motors: at 460/480 V at 50 °C rated value 400 hp
operating power [hp] for 3-phase motors: at 200/208 V at inside-delta circuit at 50 °C rated value 300 hp
operating power [hp] for 3-phase motors: at 220/230 V at inside-delta circuit at 50 °C rated value 350 hp
operating power [hp] for 3-phase motors: at 460/480 V at inside-delta circuit at 50 °C rated value 750 hp
contact rating of auxiliary contacts according to UL R300-B300

Electrical Safety 2

protection class IP on the front according to IEC 60529 IP00; IP20 with cover
touch protection on the front according to IEC 60529 finger-safe, for vertical contact from the front with cover

Approvals Certificates 1

Environmental Product Declaration: global warming potential [CO2 eq] / during manufacturing 84.2 kg

Logistics 7

Net weight 9.899 kg
Package dimensions 501 × 323 × 343 mm
Country of origin CZ
Shipping weight 10.899 kg
Ships from Türkiye
Dispatch 12 Nov
Stock Low stock

Source: manufacturer data · Last verified: 30 Oct 2026

Documents

Documents for 3RW5248-6AC14

No documents are on file for this part yet.

Ask us for the datasheet
Quick answers

Questions about the 3RW52

What is the rated current of 3RW52?

The rated current of 3RW52 is 570 A.

Which supply voltage is 3RW52 rated for?

The rated operational voltage of 3RW52 is 200–480 V AC.

What motor power is 3RW52 rated for?

The rated motor power of 3RW52 is 315 kW.

Which control voltage does 3RW52 need?

The control voltage range of 3RW52 is 110–250 V.

What is the HS code of 3RW52 for customs?

The tariff (HS) code on file for 3RW52 is 853710.

What is the EAN of 3RW52?

The EAN (GTIN) of 3RW52 is 4047621038285.

Where does 3RW52 ship from, and how fast?

3RW52 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.

Guides

Guides for soft starters

All guides for soft starters
Reviews

Customer reviews

Series

Siemens SIRIUS 3RW52

Brand
Siemens
Series
SIRIUS 3RW52
Series page →
Series

Other series in Siemens SIRIUS 3RW Soft Starters

$5,675.87 Low stock · 12 Nov
Quote

Get a Quote

3RW52

Genuine parts

Genuine, factory-sealed parts

Siemens · 3RW5248-6AC14

Every part on Stoklink is new, unused and made by the manufacturer named on the page.

Condition
New and unused, in the manufacturer's factory-sealed packaging.
Sourced from
Siemens and its authorised distributors.
Warranty
The manufacturer's warranty applies.
If a part is not genuine
We refund the full amount.

Added to cart Could not add to cart