Schneider Zelio vs ABB CM: Monitoring Relay Comparison
A function-by-function comparison of Schneider Zelio Control and ABB CM monitoring relays covering three-phase supply, voltage, current, level, temperature, module width, and measurement method.
The Schneider Electric RM35TM50MW is a Harmony Series SSD1 3-phase control relay rated at 5A with a wide supply voltage range of 24–240V AC/DC, designed for reliable phase monitoring and protection in industrial automation and control panel applications. This versatile relay detects phase loss, phase imbalance, and incorrect phase sequence, safeguarding three-phase equipment from potentially damaging electrical faults. Compact and DIN-rail mountable, the RM35TM50MW is a trusted choice for engineers specifying motor and load protection solutions across diverse industrial environments.
| Range of Product | Harmony Control Relays |
|---|---|
| Relay Type | Motor temperature control relay |
| Product or Component Type | Motor temperature control relay |
| Relay name | RM35TM |
| Relay monitored parameters | Phase sequence, Motor temperature via PTC probe, Phase failure detection |
| Control Type | Without test button |
| Contacts type and composition | 2 NO |
| [Uc] control circuit voltage | 24...240 V |
| Product Specific Application | For 3-phase supply |
| [Us] rated supply voltage | 24...240 V AC/DC 50/60 Hz, non self-powered |
|---|---|
| Supply voltage limits | 20.4…264 V AC, 20.4…264 V DC |
| Supply frequency | 50/60 Hz +/- 10 % |
| Power consumption in VA | 0…4 VA 24...240 V AC |
| Measurement range | 208...480 V AC, 15...3100 Ohm |
| Measurement voltage limits | 176…528 V AC |
| Time delay type | Without |
| Reset time | 10000 ms output |
| Response time | > 50 ms (input Y1 (contact Y1-T1) and push-button) |
| Output contacts | 2 NO |
| nominal output current | 5 A |
| Maximum switching voltage | 250 V AC |
| Switching capacity in VA | 1250 VA |
| Minimum switching current | 10 mA 5 V DC |
| Maximum switching current | 5 A AC, 5 A DC |
| Electrical durability | 100000 cycles |
| Mechanical durability | 30000000 cycles |
| Control circuit frequency | 50...60 Hz +/- 10 % |
| Resistance across terminals | 602 kOhm |
| [Uc] control circuit voltage | <= 3.6 V temperature control circuit T1-T2 terminals open) |
| Short-circuit current | 0.007 A temperature sensing circuit T1-T2 terminals short circuited) |
| Maximum resistance | 1500 Ohm temperature sensor 68 °F (20 °C) |
| Tripping threshold | 3100 Ohm +/- 10 % temperature control circuit |
| Reset threshold | 1650 Ohm +/- 10 % temperature control circuit |
| Maximum power consumption in W | 0.5 W DC |
| Electromagnetic compatibility | Emission standard for industrial environments conforming to IEC 61000-6-4, Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3, Immunity for industrial environments conforming to IEC 61000-6-2 |
|---|---|
| Standards | IEC 60255-6, IEC 60034-11-2 |
| Product Certifications | GL, UL, GOST, C-tick, CSA |
| Marking | CE |
| Directives | 73/23/EEC - low voltage directive, 89/336/EEC - electromagnetic compatibility |
| Ambient Air Temperature for Storage | -40…158 °F (-40…70 °C), -40…158 °F (-40…70 °C) |
| Ambient air temperature for operation | -4…122 °F (-20…50 °C) |
| Relative humidity | 95 % 131 °F (55 °C) IEC 60068-2-30 |
| IP degree of protection | IP20 IEC 60529 terminals), IP30 IEC 60529 casing) |
| Pollution degree | 3 IEC 60664-1 |
| Overvoltage category | III conforming to IEC 60664-1 |
| Dielectric test voltage | 2 kV AC 50 Hz, 1 min |
| Insulation resistance | > 500 MOhm 500 V DC between supply and relay output IEC 60255-5 |
| [Ui] rated insulation voltage | 400 V IEC 60664-1 |
| Operating position | Any position without derating |
| Connections - terminals | Screw terminals, 1 x 0.5...1 x 4 mm² 20 AWG...11 AWG) solid without cable end, Screw terminals, 2 x 0.5...2 x 2.5 mm² 20 AWG...14 AWG) solid without cable end, Screw terminals, 1 x 0.2...1 x 2.5 mm² 24 AWG...12 AWG) flexible with cable end, Screw terminals, 2 x 0.2...2 x 1.5 mm² 24 AWG...16 AWG) flexible with cable end |
| Tightening torque | 5.3…8.9 lbf.in (0.6…1 N.m) IEC 60947-1 |
| Housing material | Polycarbonate |
| Local signalling | LED (green) for power ON, LED (yellow) for phase of relay (R2), LED (yellow) for temperature of relay (R1) |
| Mounting support | 35 mm symmetrical DIN rail conforming to IEC 60715 |
| Height | 3.5 in (90 mm), 3.5 in (88.9 mm) |
| Width | 1.4 in (35 mm), 1.4 in (35.6 mm) |
| Depth | 2.8 in (72 mm), 2.8 in (71.1 mm) |
| Net Weight | 0.209 lb(US) (0.095 kg), 0.21 lb(US) (0.10 kg) |
| Part number | RM35TM50MW |
|---|---|
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 3389119405287 |
| Warranty (in months) | 18 |
|---|
| Country of origin | ID |
|---|---|
| Shipping weight | 0.298 kg |
| Ships from | Türkiye |
| Dispatch | 11 Nov |
| Stock | Low stock |
Source: manufacturer data · Last verified: 30 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of RM35TM50MW is 5 A.
The rated operational voltage of RM35TM50MW is 24–240–DC V DC.
The tariff (HS) code on file for RM35TM50MW is 85364900.
The EAN (GTIN) of RM35TM50MW is 3389119405287.
RM35TM50MW ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.
A function-by-function comparison of Schneider Zelio Control and ABB CM monitoring relays covering three-phase supply, voltage, current, level, temperature, module width, and measurement method.
A step-by-step selection guide for phase and voltage monitoring relays, covering function match, auxiliary supply, threshold setting, output logic, and Schneider vs ABB CM...
How conductive level monitoring relays detect liquid presence, size sensitivity for the medium, and control pump up/down cycles with dry-run protection.