The Schneider Electric RE17RMMU (model RE17R) is a Harmony Series multifunction timer relay designed for versatile timing and control applications in industrial automation and control panel environments. Rated at 8A with a wide supply voltage range of 24–240V AC/DC, this 1CO (1 changeover) output relay delivers flexible timing functions suitable for a broad spectrum of machine and process control tasks.
| Range of Product | Harmony Timer Relays |
|---|---|
| Discrete output type | Relay |
| Product or Component Type | Modular timing relay |
| Width | 0.7 in (17.5 mm) |
| Device short name | RE17R |
| Time delay type | Power on-delay, On-delay and off-delay, Interval, Off-delay, Symmetrical flashing |
| Time delay range | 6...60 min, 1...10 h, 0.1...1 s, 1...10 s, 1...10 min, 10...100 h, 6...60 s |
| nominal output current | 8 A |
| Contacts type and composition | 1 C/O |
|---|---|
| Contacts material | Cadmium free |
| Height | 3.5 in (90 mm) |
| Depth | 2.8 in (72 mm) |
| Control type | Selector switch front panel |
| [Us] rated supply voltage | 24...240 V AC 50/60 Hz, 24 V DC |
| Voltage range | 0.85...1.1 Us |
| Supply frequency | 50...60 Hz +/- 5 % |
| release of input voltage | 10 V |
| Connections - terminals | Screw terminals, 1 x 0.5...1 x 3.3 mm² 20 AWG...12 AWG) solid without cable end, Screw terminals, 2 x 0.5...2 x 2.5 mm² 20 AWG...14 AWG) solid without cable end, Screw terminals, 1 x 0.2...1 x 2.5 mm² 24 AWG...14 AWG) flexible with cable end, Screw terminals, 2 x 0.2...2 x 1.5 mm² 24 AWG...16 AWG) flexible with cable end |
| Tightening torque | 5.3…8.9 lbf.in (0.6…1 N.m) IEC 60947-1 |
| Housing material | Polycarbonate |
| Repeat accuracy | +/- 0.5 % IEC 61812-1 |
| Temperature Drift | +/- 0.05 %/°C |
| Voltage drift | +/- 0.2 %/V |
| Setting accuracy of time delay | +/- 10 % of full scale 25 °C IEC 61812-1 |
| Time delay type | Power on-delay - A- Power on-delay relay, On-delay and off-delay - Ac- On-delay and off-delay relay w/ control signal, Power on-delay - At- Power on-delay relay w/ pause/summation (Y1), Interval - B- Single interval relay w/ control signal, Interval - Bw- Double interval relay w/ control signal, Off-delay - C- Off-delay relay w/ control signal, Symmetrical flashing - D- Symmetrical flashing relay (starting pulse-off), Symmetrical flashing - Di- Symmetrical flashing relay (starting pulse-on), Interval - H- Interval relay, Interval - Ht- Interval relay w/ pause/summation (Y1) |
| control signal pulse width | 100 ms with load in parallel typical, 30 ms typical |
| Insulation resistance | 100 MOhm 500 V DC IEC 60664-1 |
| Reset time | 120 ms on de-energisation typical |
| On-load factor | 100 % |
| Power consumption in VA | 0…32 VA 240 V AC |
| Maximum power consumption in W | 0.6 W 24 V DC |
| Minimum switching current | 10 mA 5 V DC |
| Maximum switching current | 8 A AC/DC |
| Maximum switching voltage | 250 V AC |
| breaking capacity | 2000 VA |
| operating frequency | 10 Hz |
| Electrical durability | 100000 cycles resistive 8 A 250 V AC |
| Mechanical durability | 10000000 cycles |
| Dielectric strength | 2.5 kV 1 mA/1 minute 50 Hz IEC 61812-1 |
| [Uimp] rated impulse withstand voltage | 5 kV 1.2/50 µs |
| power on delay | 100 ms |
| Marking | CE |
| Creepage distance | 4 kV/3 IEC 60664-1 |
| Safety reliability data | B10d = 270000, MTTFd = 296.8 years |
| Mounting position | Any position in relation to normal vertical mounting plane |
| Mounting support | 35 mm DIN rail conforming to IEC 60715 |
| Local signalling | LED indicator on steady: relay energised, no timing in progress, LED indicator 80 % ON and 20 % OFF flashing: timing in progress, LED indicator 5 % ON and 95 % OFF pulsing: relay de-energised, no timing in progress (except function Di-D, Li-L) |
| Function available | A- Power on-delay relay-1 C/O, Ac- On-delay and off-delay relay w/ control signal-1 C/O, At- Power on-delay relay w/ pause/summation (Y1)-1 C/O, B- Single interval relay w/ control signal-1 C/O, Bw- Double interval relay w/ control signal-1 C/O, C- Off-delay relay w/ control signal-1 C/O, D- Symmetrical flashing relay (starting pulse-off)-1 C/O, Di- Symmetrical flashing relay (starting pulse-on)-1 C/O, H- Interval relay-1 C/O, Ht- Interval relay w/ pause/summation (Y1)-1 C/O |
| Net Weight | 0.15 lb(US) (0.07 kg) |
| Number of functions | 10 |
| Functionality | Multifunction |
| Compatibility code | RE17 |
| Immunity to microbreaks | 20 ms |
|---|---|
| Standards | 2006/95/EC, 2004/108/EC, IEC 61812-1, IEC 61000-6-2, IEC 61000-6-3, IEC 61000-6-4, IEC 61000-6-1 |
| Product Certifications | CSA, GL, cULus |
| Ambient Air Temperature for Storage | -22…140 °F (-30…60 °C) |
| Ambient Air Temperature for Operation | -4…140 °F (-20…60 °C) |
| IP degree of protection | IP20 IEC 60529 terminal block), IP40 IEC 60529 housing), IP50 IEC 60529 front panel) |
| Vibration resistance | 20 m/s² (f= 10…150 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn 11 ms IEC 60068-2-27 |
| Relative Humidity | 93 % without condensation IEC 60068-2-30 |
| Electromagnetic compatibility | Electrostatic discharge immunity test 6 kV in contact) level 3 IEC 61000-4-2, Electrostatic discharge immunity test 8 kV in air) level 3 IEC 61000-4-2, Susceptibility to electromagnetic fields 10 V/m 80 MHz to 1 GHz) level 3 IEC 61000-4-3, Electrical fast transient/burst immunity test 1 kV capacitive connecting clip) level 3 IEC 61000-4-4, Electrical fast transient/burst immunity test 2 kV direct) level 3 IEC 61000-4-4, 1.2/50 µs shock waves immunity test 1 kV differential mode) level 3 IEC 61000-4-5, 1.2/50 µs shock waves immunity test 2 kV common mode) level 3 IEC 61000-4-5, Conducted RF disturbances 10 V 0.15...80 MHz) level 3 IEC 61000-4-6, Voltage dips and interruptions immunity test 0 % 1 cycle) IEC 61000-4-11, Voltage dips and interruptions immunity test 70 % 25/30 cycles) IEC 61000-4-11, Conducted and radiated emissionsclass B EN 55022 |
| Part number | RE17RMMU |
|---|---|
| Type designation | RE17R |
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 3606480552755 |
| Warranty (in months) | 18 |
|---|
| Country of origin | ID |
|---|---|
| Shipping weight | 0.07 kg |
| Ships from | Türkiye |
| Dispatch | 9 Nov |
| Stock | In stock |
Source: manufacturer data · Last verified: 30 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of RE17R is 8 A.
The rated operational voltage of RE17R is 24–240–DC V DC.
The tariff (HS) code on file for RE17R is 85364900.
The EAN (GTIN) of RE17R is 3606480552755.
RE17R ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.
Learn how to wire a contactor for star delta motor starting with IEC 60947 circuits, timer logic, and safe sizing practices for engineers. Shop...