- Home
- All Products
- Schneider Electric RE17LCBM Harmony RE17L 0.7A Off-Delay 24-240V AC Timer Relay Schneider Electric RE17LCBM Harmony RE17L 0.7A Off-Delay 24-240V AC Timer Relay
Schneider Electric RE17LCBM Harmony RE17L 0.7A Off-Delay 24-240V AC Timer Relay
Schneider Electric RE17LCBM Harmony RE17L 0.7A Off-Delay 24-240V AC Timer Relay
Get Quote
- Description
The Schneider Electric RE17LCBM is a Harmony RE17L single-function timer relay providing off-delay timing from 0.1 seconds to 100 hours with a solid-state 0.7 A output. It accepts a universal 24-240 V AC 50/60 Hz supply and mounts on 35 mm DIN rail. The selector-switch front panel sets the delay range and value directly, without any programming step.
Technical Specifications
| Reference | RE17LCBM |
| Brand | Schneider Electric |
| Range | Harmony Timer Relays |
| Series | RE17L |
| Product Type | Modular timing relay |
| Functionality | Off-delay timing (single function) |
| Time Delay Range | 0.1 s - 100 h (8 selectable ranges) |
| Nominal Output Current | 0.7 A |
| Discrete Output Type | Solid state |
| Rated Supply Voltage (Us) | 24...240 V AC 50/60 Hz |
| Voltage Range | 0.85...1.1 Us |
| Setting Accuracy of Time Delay | +/- 10% of full scale |
| Repeat Accuracy | +/- 0.5% |
| Maximum Output Current | 20 A |
| Maximum Switching Voltage | 250 V AC |
| Rated Impulse Withstand Voltage (Uimp) | 5 kV |
| IP Degree of Protection | IP20 (terminals) / IP40 (housing) / IP50 (front panel) |
| Mounting Support | 35 mm DIN rail |
| Ambient Air Temperature (Operation) | -20...60 C |
| Width | 17.5 mm |
| Net Weight | 0.068 kg |
| Safety Reliability Data | MTTFd = 353.8 years, B10d = 320000 |
Certifications & Standards
- CE
- CSA
- GL
- cULus
- 2004/108/EC
- 2006/95/EC
- IEC 61812-1
- IEC 61000-6-1
- IEC 61000-6-2
- IEC 61000-6-3
- IEC 61000-6-4
Selection Notes
RE17L is a single-function relay (off-delay only), which is what separates it from the RE22 and RE48 multifunction Harmony timer relays that offer several timing modes on one part. Its 0.7 A solid-state output is sized to drive PLC inputs or small interposing relay coils directly rather than switching contactor coils, where the 20 A make rating still leaves headroom for inrush. The 0.85-1.1 Us voltage tolerance across a 24-240 V AC range lets one SKU cover most control-voltage installations without a voltage-specific variant.