IEC 60947-4-1 Standards for Contactors and Motor Starters Explained
Master AC-3 rating selection under IEC 60947-4-1 for contactors and motor starters, including utilization categories and coordination types. Shop at Stoklink.
The Schneider Electric LUCL12FU is a TeSys U magnetic control unit giving short-circuit protection only, adjustable from 3 to 12 A. Plugged into a LUB12, LUB32, or LUB38 power base, it is intended for installations where an upstream variable speed drive or soft starter already provides motor overload protection, completing a disconnect/short-circuit function for 3-phase motors up to 5.5 kW at 400 V, controlled from a 110-240 V AC / 110-220 V DC supply.
The LUCL12FU matches the LUCL12B's 3-12 A short-circuit-only range for downstream-of-drive applications but is wired for a 110-240 V AC / 110-220 V DC control supply, avoiding a separate step-down transformer where the panel's control circuit already runs at mains voltage. As with the rest of the LUCL family, it omits the thermal curve entirely, so it must only be paired with a motor already protected by a VSD or soft starter upstream. Use the 24 V LUCL12B instead on a 24 V control bus.
| Range | TeSys |
|---|---|
| Range of product | TeSys Ultra |
| Product name | TeSys Ultra |
| Device short name | LUCL |
| Product or component type | Magnetic control unit |
| Device application | Motor control, Motor protection |
| Product specific application | Protection of variable speed drive or soft startsoft stop unit |
| main function available | Manual reset, Short-circuit protection |
| Product compatibility | Power base LUB12, Power base LUB32, Power base LUB38, Power base LUB120, Power base LUB320, Power base LUB380, Reversing contactor breaker LU2B12FU, Reversing contactor breaker LU2B32FU, Reversing contactor breaker LU2B38FU |
| [Ue] rated operational voltage | 690 V AC |
| Network frequency | 40...60 Hz |
| Load type | 3-phase motor - cooling: self-cooled |
| Utilisation category | AC-44, AC-41, AC-43 |
| Motor power kW | 5.5 kW at 400...440 V AC 50/60 Hz, 5.5 kW at 500 V AC 50/60 Hz, 9 kW at 690 V AC 50/60 Hz |
| rated motor current adjustment range | 3…12 A |
| Tripping threshold | 14.2 x Ir +/- 20 % |
| [Uc] control circuit voltage | 110...240 V AC, 110...220 V DC |
| Control circuit voltage limits | 88...264 V for AC circuit 110...240 V in operation, 88...242 V for DC circuit 110...220 V in operation, 55 V for AC circuit 110...240 V drop-out, 55 V for DC circuit 110...220 V drop-out |
|---|---|
| Typical current consumption | 280 mA at 110...240 V AC I maximum while closing with LUB12, 280 mA at 110...240 V AC I maximum while closing with LUB32, 280 mA at 110...240 V AC I maximum while closing with LUB38, 280 mA at 110...220 V DC I maximum while closing with LUB12, 280 mA at 110...220 V DC I maximum while closing with LUB32, 280 mA at 110...220 V DC I maximum while closing with LUB38, 35 mA at 110...240 V AC I rms sealed with LUB12, 25 mA at 110...240 V AC I rms sealed with LUB32, 25 mA at 110...240 V AC I rms sealed with LUB38, 35 mA at 110...220 V DC I rms sealed with LUB12, 25 mA at 110...220 V DC I rms sealed with LUB32, 25 mA at 110...220 V DC I rms sealed with LUB38 |
| Heat dissipation | 2 W for control circuit with LUB12, 3 W for control circuit with LUB32, 3 W for control circuit with LUB38 |
| Operating time | 35 ms opening with LUB12 for control circuit, 35 ms opening with LUB32 for control circuit, 35 ms opening with LUB38 for control circuit, 50 ms closing with LUB12 for control circuit, 50 ms closing with LUB32 for control circuit, 50 ms closing with LUB38 for control circuit |
| Standards | EN 60947-6-2, IEC 60947-6-2, UL 60947-4-1, with phase barrier, CSA C22.2 No 60947-4-1, with phase barrier |
| Product certifications | CE, EAC, ATEX |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-6-2, 600 V conforming to UL 60947-4-1, 600 V conforming to CSA C22.2 No 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-6-2 |
| Safe separation of circuit | 400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1, 400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1 |
| Fixing mode | Plug-in (front face) |
| Width | 45 mm |
| Height | 66 mm |
| Depth | 60 mm |
| Net weight | 0.135 kg |
| Compatibility code | LUCL |
| IP degree of protection | IP20 front panel and wired terminals conforming to IEC 60947-1, IP20 other faces conforming to IEC 60947-1, IP40 front panel outside connection zone conforming to IEC 60947-1 |
|---|---|
| Protective treatment | TH conforming to IEC 60068 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Operating altitude | 2000 m |
| Fire resistance | 960 °C parts supporting live components conforming to IEC 60695-2-12, 650 °C conforming to IEC 60695-2-12 |
| Shock resistance | 10 gn power poles open conforming to IEC 60068-2-27, 15 gn power poles closed conforming to IEC 60068-2-27 |
| Vibration resistance | 2 gn, 5…300 Hz, power poles open conforming to IEC 60068-2-6, 4 gn, 5…300 Hz, power poles closed conforming to IEC 60068-2-6 |
| Resistance to electrostatic discharge | 8 kV level 3 in open air conforming to IEC 61000-4-2, 8 kV level 4 on contact conforming to IEC 61000-4-2 |
| Non-dissipating shock wave | 1 kV serial mode conforming to IEC 60947-6-2, 2 kV common mode conforming to IEC 60947-6-2 |
| Resistance to radiated fields | 10 V/m 3 conforming to IEC 61000-4-3 |
| Resistance to fast transients | 2 kV class 3 serial link conforming to IEC 61000-4-4, 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4 |
| Immunity to radioelectric fields | 10 V conforming to IEC 61000-4-6 |
| Immunity to microbreaks | 3 ms |
| Immunity to voltage dips | 70 % / 500 ms conforming to IEC 61000-4-11 |
| Part number | LUCL12FU |
|---|---|
| Type designation | LUCL |
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| Warranty (in months) | 18 |
|---|
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.5 cm |
| Package 1 Width | 8.0 cm |
| Package 1 Length | 10.2 cm |
| Package 1 Weight | 132.0 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 23 |
| Package 2 Height | 15.0 cm |
| Package 2 Width | 30.0 cm |
| Package 2 Length | 40.0 cm |
| Package 2 Weight | 3.485 kg |
| Shipping weight | 0.135 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of LUCL is 12 A.
The rated operational voltage of LUCL is 110–240 V AC.
The tariff (HS) code on file for LUCL is 853650.
LUCL ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
Master AC-3 rating selection under IEC 60947-4-1 for contactors and motor starters, including utilization categories and coordination types. Shop at Stoklink.
Compare AC3 rating IEC contactors versus NEMA size codes, with cross-reference tables, derating formulas, and selection tips for engineers. Shop at Stoklink.
Size a contactor for a 3-phase motor using IEC 60947-4-1 methodology, AC-3 vs AC-4 categories, NEMA equivalents, and Type 2 coordination. Shop at Stoklink.