Schneider Electric LUCL05B TeSys Ultra Standard Control Unit 1.25-5 A 24 V AC Coil Motor Starter Module
Schneider Electric LUCL05B TeSys Ultra Standard Control Unit 1.25-5 A 24 V AC Coil Motor Starter Module
Get Quote
- Description
The Schneider Electric LUCL05B is a TeSys Ultra magnetic control unit that plugs into an LUB12, LUB32, or LUB38 power base to form a TeSys U starter-controller for 3-phase motors up to 1.5 kW at 400 V. It covers an adjustable rated current In of 1.25-5 A and provides short-circuit protection only, tripping at 14.2 x In, for use downstream of a motor drive or soft starter that already handles overload protection.
Technical Specifications
| Reference | LUCL05B |
| Brand | Schneider Electric |
| Range | TeSys Ultra |
| Product Type | Magnetic control unit |
| Compatible Power Bases | LUB12, LUB32, LUB38 |
| Rated Current Adjustment Range (In) | 1.25-5 A |
| Motor Power (400 V AC) | 1.5 kW |
| Protection Function | Short-circuit protection only (overload handled by VSD or soft starter) |
| Tripping Threshold (Overcurrent) | 14.2 x In +/- 20% |
| Control Circuit Voltage (Uc) | 24 V AC |
| Rated Operational Voltage (Ue) | 690 V AC |
| Rated Insulation Voltage (Ui) | 690 V |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Reset | Manual |
| Fixing Mode | Plug-in (front face) |
| IP Degree | IP20 front panel / IP40 outside connection zone |
| Dimensions (H x W x D) | 66 x 45 x 60 mm |
| Net Weight | 0.135 kg |
Certifications & Standards
- CE
- EAC
- ATEX
- EN 60947-6-2
- IEC 60947-6-2
- UL 60947-4-1
- CSA C22.2 No 60947-4-1
Selection Notes
Unlike the LUCB advanced control units, the LUCL05B drops thermal overload protection entirely and only handles short-circuit tripping, because it is meant to sit behind a variable speed drive or soft starter that already protects the motor from overload. Pick the LUCL12BL sibling instead if the motor current exceeds 5 A, or an LUCB unit if the installation needs standalone overload protection without an external drive.
Applications
TeSys U starter-controllers paired with a variable speed drive or soft starter for 3-phase motors up to 1.5 kW at 400 V, where the drive's own overload algorithm makes a second thermal relay redundant.