The Schneider Electric LUCB05BL is a TeSys U advanced control unit providing adjustable thermal-magnetic motor protection from 1.25 to 5 A plus diagnostic outputs. Plugged into an advanced LUB120, LUB320, or LUB380 power base, it forms a starter-controller with Class 10 overload tripping, phase-failure sensing, earth-fault detection, a thermal-alarm signal via a LUFDA or LULC module, and a test pushbutton for 3-phase motors up to 1.5 kW at 400 V, controlled from a 24 V DC supply.
The LUCB05BL is the DC-coil version of the LUCB05B, same 1.25-5 A range with the thermal-alarm output routed through either a local LUFDA module or a remote LULC module. It pairs naturally with the LU2B12BL/LU2B32BL/LU2B38BL DC-coil reversing bases where diagnostics are also wanted on a reversing circuit. Use the plain LUCA05BL instead if the alarm output is not needed.
| Range | TeSys |
|---|---|
| Range of Product | TeSys Ultra |
| Product name | TeSys Ultra |
| Device short name | LUCB |
| Product or Component Type | Advanced control unit |
| Device Application | Motor control, Motor protection |
| Product Specific Application | Basic protection and advanced functions, communication |
| main function available | Protection against overload and short-circuit, Manual reset, Earth fault protection, Protection against phase failure and phase imbalance |
| Product compatibility | Power base LUB12, Power base LUB32, Power base LUB38, Power base LUB120, Power base LUB320, Power base LUB380, Reversing contactor breaker LU2B12BL, Reversing contactor breaker LU2B32BL, Reversing contactor breaker LU2B38BL |
| [Ue] rated operational voltage | 690 V AC |
| Network frequency | 40...60 Hz |
| Load type | 3-phase motor self-cooled |
| Utilisation category | AC-44, AC-41, AC-43 |
| Motor power kW | 1.5 kW 400...440 V AC 50/60 Hz, 2.2 kW 500 V AC 50/60 Hz, 3 kW 690 V AC 50/60 Hz |
| rated motor current adjustment range | 1.25…5 A |
| Thermal overload class | Class 10 40…60 Hz -13…158 °F (-25…70 °C) IEC 60947-6-2, Class 10 40…60 Hz -13…158 °F (-25…70 °C) UL 508 |
| Tripping threshold | 14.2 x Ir +/- 20 % |
| Phase failure sensitivity | Yes |
| [Uc] control circuit voltage | 24 V DC |
| Control circuit voltage limits | 20...27 V DC 24 V in operation, 14.5 V DC 24 V drop-out |
|---|---|
| Typical current consumption | 130 mA 24 V DC I maximum while closing with LUB12, 220 mA 24 V DC I maximum while closing with LUB32, 220 mA 24 V DC I maximum while closing with LUB38, 60 mA 24 V DC I rms sealed with LUB12, 80 mA 24 V DC I rms sealed with LUB32, 80 mA 24 V DC I rms sealed with LUB38 |
| Heat dissipation | 2 W control circuit with LUB12, 3 W control circuit with LUB32, 3 W control circuit with LUB38 |
| Operating time | 35 ms opening with LUB12 control circuit, 35 ms opening with LUB32 control circuit, 35 ms opening with LUB38 control circuit, 70 ms closing with LUB12 control circuit, 70 ms closing with LUB32 control circuit, 70 ms closing with LUB38 control circuit |
| Reset | Manual reset |
| Standards | EN 60947-6-2, IEC 60947-6-2, UL 60947-4-1, with phase barrier, CSA C22.2 No 60947-4-1, with phase barrier |
| Product Certifications | CE, UL, CSA, CCC, EAC, ASEFA, ATEX, Marine |
| [Ui] rated insulation voltage | 690 V IEC 60947-6-2, 600 V UL 60947-4-1, 600 V CSA C22.2 No 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 6 kV IEC 60947-6-2 |
| Safe separation of circuit | 400 V SELV between the control and auxiliary circuits IEC 60947-1, 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1 |
| Fixing mode | Plug-in (front face) |
| Width | 1.8 in (45 mm) |
| Height | 2.6 in (66 mm) |
| Depth | 2.4 in (60 mm) |
| Compatibility code | LUCB |
| IP degree of protection | IP20 front panel and wired terminals IEC 60947-1, IP20 other faces IEC 60947-1, IP40 front panel outside connection zone IEC 60947-1 |
|---|---|
| Protective treatment | TH IEC 60068 |
| Ambient air temperature for operation | -13…158 °F (-25…70 °C) |
| Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) |
| Operating altitude | 6561.68 ft (2000 m) |
| Fire resistance | 1760 °F (960 °C) parts supporting live components IEC 60695-2-12, 1202 °F (650 °C) IEC 60695-2-12 |
| Shock resistance | 10 gn power poles open IEC 60068-2-27, 15 gn power poles closed IEC 60068-2-27 |
| Vibration resistance | 2 gn 5…300 Hz power poles open IEC 60068-2-6, 4 gn 5…300 Hz power poles closed IEC 60068-2-6 |
| Resistance to electrostatic discharge | 8 kV 3 in open air IEC 61000-4-2, 8 kV 4 on contact IEC 61000-4-2 |
| Resistance to radiated fields | 9.1 V/m (10 V/m) 3 IEC 61000-4-3 |
| Resistance to fast transients | 2 kV 3 serial link IEC 61000-4-4, 4 kV 4 all circuits except for serial link IEC 61000-4-4 |
| Immunity to radioelectric fields | 10 V IEC 61000-4-6 |
| Immunity to microbreaks | 3 ms |
| Immunity to voltage dips | 70 % / 500 ms IEC 61000-4-11 |
| Part number | LUCB05BL |
|---|---|
| Type designation | LUCB |
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 3389110364088 |
| Warranty (in months) | 18 |
|---|
| Country of origin | FR |
|---|---|
| Shipping weight | 0.113 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of LUCB is 5 A.
The tariff (HS) code on file for LUCB is 853650.
The EAN (GTIN) of LUCB is 3389110364088.
LUCB ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
Master AC-3 rating selection under IEC 60947-4-1 for contactors and motor starters, including utilization categories and coordination types. Shop at Stoklink.
Compare AC3 rating IEC contactors versus NEMA size codes, with cross-reference tables, derating formulas, and selection tips for engineers. Shop at Stoklink.
Size a contactor for a 3-phase motor using IEC 60947-4-1 methodology, AC-3 vs AC-4 categories, NEMA equivalents, and Type 2 coordination. Shop at Stoklink.