IEC 60947-4-1 Standards for Contactors and Motor Starters Explained
Master AC-3 rating selection under IEC 60947-4-1 for contactors and motor starters, including utilization categories and coordination types. Shop at Stoklink.
The Schneider Electric LUCAX6ES is a TeSys U standard control unit providing adjustable thermal-magnetic motor protection from 0.15 to 0.6 A, the finest current band in the TeSys U control-unit range. Plugged into a LUB12, LUB32, or LUB38 power base, it forms a complete starter-controller with Class 10 overload tripping, phase-failure sensing, and earth-fault detection for 3-phase motors up to 0.09 kW at 400 V, controlled from a 48 V AC / 48-72 V DC supply.
The LUCAX6ES shares the LUCAX6BL's 0.15-0.6 A fine-adjustment range for small motors around 0.09 kW, wired instead for a 48 V AC or 48-72 V DC control bus. It sits between the 24 V LUCAX6BL and the 110-240 V LUCAX6FU in the same current band, so the choice among the three depends only on the panel's available control voltage. Protection behavior and the 0.09 kW rating are identical across all three.
| Range | TeSys |
|---|---|
| Range of Product | TeSys Ultra |
| Product name | TeSys Ultra |
| Device short name | LUCA |
| Product or Component Type | Standard control unit |
| Device Application | Motor control, Motor protection |
| Product Specific Application | Basic protection requirements for motor starters: overload and short-circuit |
| main function available | Manual reset, Protection against phase failure and phase imbalance, Protection against overload and short-circuit, Earth fault protection |
| Product compatibility | Power base LUB12, Power base LUB32, Power base LUB38, Power base LUB120, Power base LUB320, Power base LUB380, Reversing contactor breaker LU2B12ES, Reversing contactor breaker LU2B32ES |
| [Ue] rated operational voltage | 690 V AC |
| Network frequency | 40...60 Hz |
| Load type | 3-phase motor self-cooled |
| Utilisation category | AC-43, AC-44, AC-41 |
| Motor power kW | 0.09 kW 400...440 V AC 50/60 Hz |
| rated motor current adjustment range | 0.15…0.6 A |
| Thermal overload class | Class 10 40…60 Hz -13…158 °F (-25…70 °C) IEC 60947-6-2, Class 10 40…60 Hz -13…158 °F (-25…70 °C) UL 508 |
| Tripping threshold | 14.2 x Ir +/- 20 % |
| Phase failure sensitivity | Yes |
| [Uc] control circuit voltage | 48 V AC, 48...72 V DC |
| Control circuit voltage limits | 38.5...72 V AC 48 V in operation, 38.5...93 V DC 48...72 V in operation, 29 V AC 48 V drop-out, 29 V DC 48...72 V drop-out |
|---|---|
| Typical current consumption | 280 mA 48 V AC I maximum while closing with LUB12, 280 mA 48 V AC I maximum while closing with LUB32, 280 mA 48 V AC I maximum while closing with LUB38, 280 mA 48...72 V DC I maximum while closing with LUB12, 280 mA 48...72 V DC I maximum while closing with LUB32, 280 mA 48...72 V DC I maximum while closing with LUB38, 35 mA 48 V AC I rms sealed with LUB12, 45 mA 48 V AC I rms sealed with LUB32, 45 mA 48 V AC I rms sealed with LUB38, 35 mA 48...72 V DC I rms sealed with LUB12, 45 mA 48...72 V DC I rms sealed with LUB32, 45 mA 48...72 V DC I rms sealed with LUB38 |
| Heat dissipation | 2 W control circuit with LUB12, 3 W control circuit with LUB32, 3 W control circuit with LUB38 |
| Operating time | 35 ms opening with LUB12 control circuit, 35 ms opening with LUB32 control circuit, 35 ms opening with LUB38 control circuit, 60 ms closing with LUB12 control circuit, 60 ms closing with LUB32 control circuit, 60 ms closing with LUB38 control circuit |
| Standards | EN 60947-6-2, IEC 60947-6-2, UL 60947-4-1, with phase barrier, CSA C22.2 No 60947-4-1, with phase barrier |
| Product Certifications | CE, UL, CSA, CCC, EAC, ASEFA, ATEX, Marine |
| [Ui] rated insulation voltage | 690 V IEC 60947-6-2, 600 V UL 60947-4-1, 600 V CSA C22.2 No 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 6 kV IEC 60947-6-2 |
| Safe separation of circuit | 400 V SELV between the control and auxiliary circuits IEC 60947-1, 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1 |
| Fixing mode | Plug-in (front face) |
| Width | 1.8 in (45 mm) |
| Height | 2.6 in (66 mm) |
| Depth | 2.4 in (60 mm) |
| Net Weight | 0.298 lb(US) (0.135 kg) |
| Compatibility code | LUCA |
| IP degree of protection | IP20 front panel and wired terminals IEC 60947-1, IP20 other faces IEC 60947-1, IP40 front panel outside connection zone IEC 60947-1 |
|---|---|
| Protective treatment | TH IEC 60068 |
| Ambient air temperature for operation | -13…158 °F (-25…70 °C) |
| Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) |
| Operating altitude | 6561.68 ft (2000 m) |
| Fire resistance | 1760 °F (960 °C) parts supporting live components IEC 60695-2-12, 1202 °F (650 °C) IEC 60695-2-12 |
| Shock resistance | 10 gn power poles open IEC 60068-2-27, 15 gn power poles closed IEC 60068-2-27 |
| Vibration resistance | 2 gn 5…300 Hz power poles open IEC 60068-2-6, 4 gn 5…300 Hz power poles closed IEC 60068-2-6 |
| Resistance to electrostatic discharge | 8 kV 3 in open air IEC 61000-4-2, 8 kV 4 on contact IEC 61000-4-2 |
| Non-dissipating shock wave | 1 kV serial mode IEC 60947-6-2, 2 kV common mode IEC 60947-6-2 |
| Resistance to radiated fields | 9.1 V/m (10 V/m) 3 IEC 61000-4-3 |
| Resistance to fast transients | 2 kV 3 serial link IEC 61000-4-4, 4 kV 4 all circuits except for serial link IEC 61000-4-4 |
| Immunity to radioelectric fields | 10 V IEC 61000-4-6 |
| Immunity to microbreaks | 3 ms |
| Immunity to voltage dips | 70 % / 500 ms IEC 61000-4-11 |
| Part number | LUCAX6ES |
|---|---|
| Type designation | LUCA |
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 3389110363944 |
| Warranty (in months) | 18 |
|---|
| Unit Type of Package 1 | PCE |
|---|---|
| Nbr. of units in pkg. | 1 |
| Package 1 Height | 2.008 in (5.1 cm) |
| Package 1 Width | 3.1 in (8.0 cm) |
| Package 1 Length | 3.4 in (8.7 cm) |
| Package weight(Lbs) | 4.3 oz (123.0 g) |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 23 |
| Package 2 Height | 5.9 in (15.0 cm) |
| Package 2 Width | 11.8 in (30.0 cm) |
| Package 2 Length | 15.7 in (40.0 cm) |
| Package 2 Weight | 6.903 lb(US) (3.131 kg) |
| Shipping weight | 0.135 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of LUCA is 0.6 A.
The rated operational voltage of LUCA is 48 V AC.
The tariff (HS) code on file for LUCA is 853650.
The EAN (GTIN) of LUCA is 3389110363944.
LUCA ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
Master AC-3 rating selection under IEC 60947-4-1 for contactors and motor starters, including utilization categories and coordination types. Shop at Stoklink.
Compare AC3 rating IEC contactors versus NEMA size codes, with cross-reference tables, derating formulas, and selection tips for engineers. Shop at Stoklink.
Size a contactor for a 3-phase motor using IEC 60947-4-1 methodology, AC-3 vs AC-4 categories, NEMA equivalents, and Type 2 coordination. Shop at Stoklink.