- Home
- All Products
- Schneider Electric LUCAX6B TeSys U Standard Control Unit 0.15-0.6 A 24 V AC Motor Starter Module Schneider Electric LUCAX6B TeSys U Standard Control Unit 0.15-0.6 A 24 V AC Motor Starter Module
Schneider Electric LUCAX6B TeSys U Standard Control Unit 0.15-0.6 A 24 V AC Motor Starter Module
Schneider Electric LUCAX6B TeSys U Standard Control Unit 0.15-0.6 A 24 V AC Motor Starter Module
Get Quote
- Description
The Schneider Electric LUCAX6B is a TeSys U standard control unit with an adjustable motor current range of 0.15-0.6 A, inserted into a compatible power base to form a starter controller for 3-phase motors up to 0.09 kW at 400-440 V AC. It provides Class 10 thermal overload protection, phase-failure sensing, and a 24 V AC control coil.
Technical Specifications
| Reference | LUCAX6B |
| Brand | Schneider Electric |
| Range | TeSys |
| Product Name | TeSys Ultra |
| GTIN | 3389110363883 |
| Product or Component Type | Standard control unit |
| Device Application | Motor control, motor protection |
| Product Compatibility | Power base LUB12, LUB32, LUB38, LUB120, LUB320, LUB380 |
| Reversing Power Base Compatibility | Reversing power base LU2B12B, LU2B32B |
| Rated Operational Voltage (Ue) | 690 V AC |
| Utilisation Category | AC-41, AC-43, AC-44 |
| Motor Power | 0.09 kW at 400-440 V AC |
| Rated Motor Current Adjustment Range (Ir) | 0.15-0.6 A |
| Thermal Overload Class | Class 10 |
| Tripping Threshold | 14.2 x Ir ± 20% |
| Phase Failure Sensitivity | Yes |
| Control Circuit Voltage (Uc) | 24 V AC |
| Fixing Mode | Plug-in (front face) |
| Dimensions (W x H x D) | 45 x 66 x 60 mm |
| Rated Insulation Voltage (Ui) | 690 V |
| Ambient Air Temperature, Operation | -25...70 °C |
Certifications & Standards
- CE
- UL
- CSA
- CCC
- EAC
- ASEFA
- ATEX
- Marine
- EN 60947-6-2
- IEC 60947-6-2
- UL 60947-4-1
- CSA C22.2 No 60947-4-1
Selection Notes
Set Ir within the 0.15-0.6 A window to match the motor's full-load current; Class 10 tripping at 14.2 x Ir covers standard-duty starts without needing a slower overload class. This standard control unit covers basic overload, short-circuit, phase-failure and earth-fault protection without a remote diagnostic output - pick it over the advanced control unit in this current range when the panel doesn't need a thermal-alarm signal or local test push button.