- Home
- All Products
- Schneider Electric GZ1LE05 Easy TeSys Power 3P 1 A ≥100 kA Magnetic Motor Protection Circuit Breaker (MPCB) Schneider Electric GZ1LE05 Easy TeSys Power 3P 1 A ≥100 kA Magnetic Motor Protection Circuit Breaker (MPCB)
Schneider Electric GZ1LE05 Easy TeSys Power 3P 1 A ≥100 kA Magnetic Motor Protection Circuit Breaker (MPCB)
Schneider Electric GZ1LE05 Easy TeSys Power 3P 1 A ≥100 kA Magnetic Motor Protection Circuit Breaker (MPCB)
Get Quote
- Description
The Schneider Electric GZ1LE05 is a 3-pole Easy TeSys Power motor circuit breaker with a fixed magnetic-only trip set at 1 A, giving a breaking capacity (Icu) of ≥100 kA at 400/415 V. It is DIN-rail mounted, operated by a push-button, and conforms to IEC 60947-2 and IEC 60947-4-1 for direct motor protection.
Technical Specifications
| Reference | GZ1LE05 |
| Brand | Schneider Electric |
| Range | Easy TeSys Power |
| Device short name | GZ1LE |
| Device application | Motor |
| Trip unit technology | Magnetic |
| Poles | 3P |
| Utilisation category | AC-3 (IEC 60947-2) |
| [In] rated current | 1 A |
| Magnetic tripping current | 13 A |
| Breaking capacity (Icu) at 400/415 V | ≥100 kA |
| Ics rated service breaking capacity (400/415 V) | 100% |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 6 kV |
| Power dissipation | 2.5 W per pole |
| Mounting | DIN rail, by clips or screws |
| Control type | Push-button |
| Connections - terminals | Screw clamp, 1-6 mm² solid / 1-4 mm² flexible with cable end |
| Dimensions (H x W x D) | 89 x 44.5 x 78 mm |
| Net weight | 0.25 kg |
| IP degree of protection | IP20 |
| Ambient air temperature (operation) | -20 to 60°C |
| Operating altitude | 2000 m |
Certifications & Standards
- CB Scheme
- CCC
- CE
- EAC
- EN/IEC 60947-1
- EN/IEC 60947-2
- EN/IEC 60947-4-1
- GB/T 14048.1
- GB/T 14048.2
- GB/T 14048.4
- EN/IEC 60335-1
- EN/IEC 60335-2-40
Selection Notes
The GZ1LE05 has no thermal adjustment dial, so it only protects against short-circuit and severe overcurrent at the fixed 1 A magnetic threshold; it is specified where the motor already has separate thermal/overload protection (for example in a starter with a dedicated overload relay) and only short-circuit breaking is required from the breaker itself. For the next rating up, the GZ1LE06 is fixed at 1.6 A. Where the motor needs its thermal protection built into the breaker, the equivalent GZ1E series in the same frame adds the adjustable thermal-magnetic trip.