- Home
- All Products
- Schneider Electric GV2LE14 TeSys Deca GV2LE 10 A Manual Starter and Protector Schneider Electric GV2LE14 TeSys Deca GV2LE 10 A Manual Starter and Protector
Schneider Electric GV2LE14 TeSys Deca GV2LE 10 A Manual Starter and Protector
Get Quote
- Description
The Schneider Electric GV2LE14 is a TeSys Deca GV2LE manual motor circuit breaker rated at 10 A, giving magnetic-only short-circuit protection to a 3-phase motor branch. A toggle handle provides local on/off/trip control, and the breaker carries a 100 kA breaking capacity (Icu) at 400/415 V. Because the trip unit is magnetic only, it is normally combined with a separate thermal overload relay.
Technical Specifications
| Reference | GV2LE14 |
| Brand | Schneider Electric |
| Range | TeSys Deca |
| Device short name | GV2LE |
| Product type | Motor circuit breaker |
| GTIN | 3389110516975 |
| Poles | 3P |
| Trip unit technology | Magnetic |
| Control type | Toggle |
| Line rated current | 10 A |
| Magnetic tripping current | 149 A |
| [Ith] conventional free-air thermal current | 10 A |
| [Ue] rated operational voltage | 690 V AC |
| [Ui] rated insulation voltage | 690 V AC |
| [Uimp] rated impulse withstand voltage | 6 kV |
| Breaking capacity (Icu) at 400/415 V | 100 kA |
| Rated service breaking capacity (Ics) at 400/415 V | 100% |
| Motor power at 400/415 V | 3 kW |
| Motor power at 690 V | 5.5–7.5 kW |
| IP degree of protection | IP20 |
| IK degree of protection | IK04 |
| Mounting | 35 mm DIN rail, or panel-screwed with adaptor plate |
| Dimensions (W x H x D) | 45 x 89 x 78.5 mm |
| Net weight | 0.33 kg |
| Ambient air temperature, operation | -20…60 °C |
Certifications & Standards
- CB Scheme
- CE
- UKCA
- CCC
- cULus
- EAC
- LROS (Lloyd's Register of Shipping)
- BV
- RINA
- DNV-GL
- EN/IEC 60947-2
- EN/IEC 60947-4-1
- UL 60947-4-1
- CSA C22.2 No 60947-4-1
- IEC/EN 60335-2-40 Annex JJ
Selection Notes
The GV2LE trip unit is magnetic only, with a fixed 149 A instantaneous trip point set for the 10 A line rating — it carries no thermal overload element, so pair it with a TeSys LRD-type thermal relay, or use it ahead of a soft starter or drive that already provides overload protection. Its 100 kA breaking capacity at 400/415 V and 690 V toggle rating cover the full 3–7.5 kW motor power range this reference is rated for, so choosing between GV2LE variants comes down to the required line current, not the breaking capacity. The screw-clamp power terminals take 1–6 mm² solid conductor, which sets the practical upper wiring size for the 10 A circuit; the IK04 impact rating and -20…60 °C operating range are the same across the GV2LE line, so they do not factor into which current rating to pick.
Applications
Manual disconnect and short-circuit protection ahead of a contactor, soft starter, or variable frequency drive on a 3-phase motor branch circuit, in panels where a separate device provides continuous-current overload protection. The 690 V insulation and impulse withstand rating (Ui, Uimp) allow the same reference to be used on 400/415 V branch circuits with margin, or on circuits run closer to its 690 V operational limit where the breaking capacity drops to 3 kA.