How to Size a Contactor for Capacitor Bank Switching: Complete Engineering Guide
Size AC-6b contactors for capacitor bank switching correctly: avoid weld failures with proven IEC 60947-4-1 sizing methods and kvar checks. Shop at Stoklink.
The Schneider Electric BLRCH377A452B52 is a VarPlus Can HDuty power factor correction capacitor rated 37.7 kvar at 525 V, 50 Hz (45.2 kvar at 60 Hz). Built with a metallized polypropylene film dielectric and a 1.8× In continuous overcurrent rating for networks with up to 20% harmonic content, it connects through a clamptite terminal in a 136 mm diameter, IP20 enclosure weighing 3.2 kg.
HDuty (heavy duty) construction gives the BLRCH377A452B52 a 1.8× In continuous overcurrent capacity, so it stays within rating on networks where variable-speed drives or rectifiers push harmonic distortion toward the 20% ceiling — a standard-duty capacitor sized only for the fundamental would overheat under the same load. At 525 V the unit delivers 37.7 kvar on a 50 Hz network or 45.2 kvar on a 60 Hz network from the same can, useful when the same bank design serves both European and North American sites. Pick this variant to match bus voltage directly rather than relying on a transformer tap; the 136 mm x 242 mm can and clamptite terminal keep the footprint compact for panel-mounted power factor correction banks.
| Range | PowerLogic |
|---|---|
| Range of product | PowerLogic |
| Product or component type | Heavy duty capacitor |
| Product name | PowerLogic PFC Capacitor |
| Network frequency | 50/60 Hz |
| Series name | HDuty |
| Network harmonic content | <= 20 % |
| Electrical parameters | 37.7 kvar 525 V 50 Hz, 45.2 kvar 525 V 60 Hz |
| Maximum permissible voltage | 1.1 x Un (8 hours over 24 hours) |
| continuous overcurrent capacity | 1.8 x In |
| Rated voltage | 525 V AC 50/60 Hz |
| Dielectric losses | < 0.2 W/kvar |
|---|---|
| Power losses | < 0.5 W/kVAr |
| Capacitance tolerance | - 5 % to 10 % |
| Voltage test | 2.15 x Un AC between terminals for 10 s, <= 660 V - 3 kV AC between terminal and container for 10 s, >= 660 V - 6 kV AC between terminal and container for 10 s |
| Inrush current | 250 x In |
| Maximum switching operation per year | 7000 |
| Service life in hours | 130000 h |
| Dielectric material | Metallized polypropylene film with Zn/Al alloy, special resistivity & profile, special edge (wave cut) |
| Impregnation material | Non-PCB dry PUR resin, Biodegradable |
| Type of installation | Indoor installation |
| Connections - terminals | ClampTite terminal |
| Mounting mode | Upright/horizontal |
| Diameter | 136 mm |
| Height | 242 mm |
| Net weight | 3.2 kg |
| Standards | IEC 60831-2, IEC 60831-1 |
|---|---|
| IP degree of protection | IP20 |
| Operating altitude | 2000 m |
| Temperature class | D |
| Ambient air temperature for operation | -25…55 °C |
| Relative humidity | 95 % |
| Part number | BLRCH377A452B52 |
|---|---|
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| Warranty (in months) | 24 |
|---|
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 19.300 cm |
| Package 1 Width | 18.700 cm |
| Package 1 Length | 31.000 cm |
| Package 1 Weight | 3.898 kg |
| Unit Type of Package 2 | S06 |
| Number of Units in Package 2 | 15 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 70.735 kg |
| Shipping weight | 3.2 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated operational voltage of BLRCH377A452B52 is 525 V AC.
The tariff (HS) code on file for BLRCH377A452B52 is 853210.
BLRCH377A452B52 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
Size AC-6b contactors for capacitor bank switching correctly: avoid weld failures with proven IEC 60947-4-1 sizing methods and kvar checks. Shop at Stoklink.