The ABB 2CSF202001R3630 F202 AC-63/0.3 is a 2-pole instantaneous residual current circuit breaker rated 63 A with a 300 mA Type AC trip, rated for 10 kA conditional short-circuit current at 230 V AC. It is the highest-current, standard-sensitivity model in this instantaneous F202 AC group, suited to a heavier sub-distribution circuit than the 25 A or 40 A versions.
Technical Specifications
| SKU | 2CSF202001R3630 |
| Brand | ABB |
| Series | F202 |
| Catalog Designation | F202 AC-63/0.3 |
| EAN | 8012542780809 |
| Type of Residual Current | Type AC |
| Operating Characteristic | Instantaneous |
| Number of Poles | 2P |
| Rated Current (In) | 63 A |
| Rated Residual Current | 300 mA |
| Rated Voltage (Ur) | 230 V |
| Rated Insulation Voltage (Ui) | 500 V |
| Rated Impulse Withstand Voltage (Uimp) | 4 kV |
| Rated Conditional Short-Circuit Current (Inc) | 10 kA |
| Test Voltage (Ut) | 110-254 V |
| Maximum Surge Current | 0.25 kA |
| Rated Frequency | 50/60 Hz |
| Power Loss | at Rated Operating Conditions per Pole 3.2 W | Total 6.4 W |
| Degree of Protection | Terminals IP20 | Housing IP40 |
| Terminal Type | Screw Terminals, Failsafe Bi-directional Cylinder-lift |
| Net Width | 35 mm |
| Net Height | 85 mm |
| Net Depth | 69 mm |
| Net Weight | 200 g |
Certifications & Standards
- IEC/EN 61008
- UL 1053
Selection Notes
The AC-63/0.3 is the largest-current model in this instantaneous F202 AC batch, stepping up from the 25 A and 40 A versions at the same 300 mA setting for a heavier sub-distribution board. Its Type AC sensing covers sinusoidal residual current only, so specify the Type A range instead wherever the circuit includes variable-speed drives or other sources of pulsed DC leakage. Where a lower 30 mA threshold is needed at this same 63 A rating, the equivalent 0.03 version in the range provides it.