- ABB 2CSA255103R1165 DS-ARC1 B16 A30 1P+N 16A 7.5kA Arc Fault Detection Device (AFDD) ABB 2CSA255103R1165 DS-ARC1 B16 A30 1P+N 16A 7.5kA Arc Fault Detection Device (AFDD)
ABB 2CSA255103R1165 DS-ARC1 B16 A30 1P+N 16A 7.5kA Arc Fault Detection Device (AFDD)
ABB 2CSA255103R1165 DS-ARC1 B16 A30 1P+N 16A 7.5kA Arc Fault Detection Device (AFDD)
Get Quote
- Description
DS-ARC1 B16 A30 is the catalog designation behind the ABB 2CSA255103R1165, a 1P+N arc fault detection device with integrated RCBO rated 16 A, curve B, 30 mA Type A and 7.5 kA breaking capacity. Housed in three DIN-rail modules, it covers overcurrent, short-circuit, earth-fault and arc-fault protection on one final circuit.
Technical Specifications
| SKU | 2CSA255103R1165 |
| Brand | ABB |
| Series | Arc Fault Detection Devices with Integrated Overcurrent and Residual Current Protection - AFDD+RCBO |
| Catalog Designation | DS-ARC1 B16 A30 |
| EAN | 8012542735519 |
| Number of Poles | 1P+N |
| Rated Current (In) | 16 A |
| Tripping Characteristic | B |
| Rated Residual Current | 30 mA |
| Type of Residual Current | Type A |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | 7.5 kA |
| Rated Service Short-Circuit Breaking Capacity (Ics) | 6 kA |
| Rated Residual Breaking Capacity (IΔm) | 6 kA |
| Rated Operational Voltage | 230...240 V AC |
| Rated Insulation Voltage (Ui) | 500 V |
| Rated Impulse Withstand Voltage (Uimp) | 4 kV |
| Rated Frequency (f) | 50 … 60 Hz |
| Overvoltage Category | III |
| Power Loss | Total 3.1 W |
| Degree of Protection | Terminals IP20 | Housing IP40 |
| Number of Modules | 3 |
| Product Net Width | 52.5 mm |
| Product Net Weight | 240 g |
Certifications & Standards
- IEC/EN 62606
- IEC/EN 61009-1
- IEC/EN 61009-2-1
Selection Notes
16 A on a B curve covers a heavier lighting or socket-outlet circuit than the 10 or 13 A versions while still assuming resistive-type loads with limited inrush. Above this rating, the 20 A version in the same B-curve series is the next step; below it, the 10, 13 or 6 A versions fit smaller circuits. A circuit at 16 A with motor or transformer inrush should instead use the C16 A30 version, since its 5-to-10 times In threshold tolerates that inrush without nuisance tripping.