- Home
- ABB
- ABB 2CDS383001R0404 S303P-C40 3P 40A 20kA DIN Rail Miniature Circuit Breaker (MCB) ABB 2CDS383001R0404 S303P-C40 3P 40A 20kA DIN Rail Miniature Circuit Breaker (MCB)
ABB 2CDS383001R0404 S303P-C40 3P 40A 20kA DIN Rail Miniature Circuit Breaker (MCB)
ABB 2CDS383001R0404 S303P-C40 3P 40A 20kA DIN Rail Miniature Circuit Breaker (MCB)
Get Quote
- Description
ABB's S300P series 2CDS383001R0404 (S303P-C40) is a 3-pole, 40 A miniature circuit breaker with a Curve C trip and 20 kA breaking capacity at 415 V AC, dual-certified to IEC/EN 60898-1 and IEC/EN 60947-2. Its UL 1077 rating adds 10 kA interrupting capacity at 480Y/277 V AC for mixed IEC/UL installations.
Technical Specifications
| Catalog No | S303P-C40 |
| SKU | 2CDS383001R0404 |
| Brand | ABB |
| Series | S300P |
| Number of Poles | 3P |
| Tripping Characteristic | Curve C |
| Rated Current (In) | 40 A |
| Rated Short-Circuit Capacity (Icn, IEC 60898-1) | 20 kA at 415 V AC |
| Rated Ultimate Breaking Capacity (Icu, IEC 60947-2) | 25 kA at 415 V AC (15 kA at 440 V AC) |
| Rated Operational Voltage (Ue) | 415 V AC |
| Rated Insulation Voltage (Ui) | 500 V |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Overvoltage Category | IV |
| Power Loss | 8.7 W total / 2.9 W per pole |
| Interrupting Rating (UL 1077) | 10 kA at 125 V DC / 480Y/277 V AC |
| Terminal Type | Screw terminals, failsafe bi-directional cylinder-lift |
| Connecting Capacity | Rigid/stranded 0.75-35 mm², flexible 0.75-25 mm², busbar 10 mm² |
| Degree of Protection | IP20 (IP40 with cover) |
| Ambient Temperature (Operation) | -40 to +70 °C |
| Mounting | DIN rail TH35-15 / TH35-7.5, IEC 60715 |
| Dimensions (W x H x D) | 52.5 x 88 x 69 mm |
| Net Weight | 0.384 kg |
| EAN | 4016779077804 |
Certifications & Standards
- IEC/EN 60898-1
- IEC/EN 60947-2
- UL 1077
- CSA 22.2 No. 235
Selection Notes
At 40 A, Icn is 20 kA at 415 V AC, the same ceiling as the 32 A frame in the S303P-C family and a step down from the 25 kA held by the 20 A variant. This is adequate for most industrial boards, but where the prospective fault current at the installation point approaches 20 kA, verify the upstream protection's let-through energy before relying on this breaker alone. Curve C's 5-10 x In magnetic trip threshold matches loads with moderate inrush rather than purely resistive circuits. The 3-pole configuration switches all three phases without disconnecting the neutral, the standard choice for balanced three-phase loads on a TN-S system.