Part number
1SVR730794R3300
Model no
CM-PVS.41S
$134.41 In stock · 50+ Dispatch Planned dispatch date. We aim to ship within 1 business day. Depending on warehouse workload it can take 2–3 business days. · From Türkiye
CM

ABB 1SVR730794R3300 CM-PVS.41S Three-Phase Monitoring Relay 2 C/O 300-500V AC 4A 0.1-30s Phase Sequence Voltage

Rated current
4 A
Rated operational voltage
300–500 V AC
EAN
4016779851848
Description

About the CM-PVS.41S

The ABB CM-PVS.41S (SKU: 1SVR730794R3300) is a three-phase monitoring relay designed to protect industrial equipment from phase faults including phase loss, phase sequence errors, and voltage asymmetry across a wide input range of 300–500 V AC. Part of ABB's CM series, the CM-PVS.41S features a dual changeover (2 C/O) output contact, an adjustable time delay of 0.1 to 30 seconds, and a compact 30 mm wide housing suited for DIN rail installation in control panels and motor protection circuits.

Certifications & Standards

  • CE: Conformité Européenne — meets EU safety, health, and environmental requirements
  • UKCA: UK Conformity Assessed — meets Great Britain market requirements
  • cULus: UL/CSA dual certification for US and Canadian markets
  • UL 508: UL standard for industrial control equipment
  • CAN/CSA C22.2 No.14: Canadian Standards Association industrial control equipment standard
  • CCC: China Compulsory Certification for the Chinese market
  • IEC/EN 60255-27: Measuring relays and protection equipment — product safety
  • IEC/EN 63000: Technical documentation for assessment of electrical and electronic products with respect to restriction of hazardous substances
  • IEC/EN 61000-6-2: Electromagnetic compatibility — generic immunity standard for industrial environments
  • IEC/EN 61000-6-3: Electromagnetic compatibility — generic emission standard for residential environments
  • IEC 60715: Dimensions of low-voltage switchgear and controlgear — standardised mounting on rails
  • REACH: EU regulation on Registration, Evaluation, Authorisation and Restriction of Chemicals
  • RoHS: Restriction of Hazardous Substances — compliant with EU Directive 2011/65/EU

Applications & Use Cases

  • Motor protection against phase loss, phase sequence reversal, and voltage unbalance in three-phase systems
  • Protection of pumps, compressors, and HVAC systems operating on 300–500 V AC three-phase networks
  • Industrial automation control panels requiring phase integrity monitoring
  • Building management systems and critical infrastructure where phase faults must be detected and isolated rapidly
  • OEM machine builders integrating compact DIN-rail-mountable protection relays into motor starter assemblies

Frequently Asked Questions

What faults does the CM-PVS.41S detect?
The CM-PVS.41S monitors three-phase supplies for phase loss, incorrect phase sequence, and voltage outside the rated 300–500 V AC window, triggering its 2 C/O output contacts after the set time delay.
What is the adjustable time delay range?
The time delay is adjustable from 0.1 to 30 seconds, allowing coordination with downstream protective devices and preventing nuisance tripping during brief supply disturbances.
Is the CM-PVS.41S suitable for DIN rail mounting?
Yes. At 30 mm wide and compliant with IEC 60715, the CM-PVS.41S mounts directly onto standard 35 mm DIN rails.
Which markets is this relay approved for?
The CM-PVS.41S carries CE, UKCA, cULus (UL 508 / CSA C22.2 No.14), and CCC certifications, making it suitable for European, UK, North American, and Chinese markets.
Specification

Full specification

67 values · Last verified 30 Oct 2026

Dimensions 4

Product Net Width 22.5 mm
Product Net Height 85.6 mm
Product Net Depth / Length 103.7 mm
Product Net Weight 0.139 kg

Technical 27

Function Phase failure detection, Phase sequence monitoring, Over- and undervoltage monitoring
Measuring Range (L-L) 300 ... 500 V AC
Time Range Tripping Delay (ON or OFF) ≤ 0 s
Rated Control Supply Voltage (Us) (L-L) 300 ... 500 V AC
Rated Frequency (f) Supply Circuit 50/60 Hz
Output 2 C/O Contacts
Terminal Type Screw Terminals
Rated Operational Current AC-12 (Ie) (230 V) 4 A
Rated Operational Current AC-15 (Ie) (230 V) 3 A
Rated Operational Current DC-12 (Ie) (24 V) 4 A
Rated Operational Current DC-13 (Ie) (24 V) 2 A
Minimum Switching Capacity 24 V, 10 mA
Rated Impulse Withstand Voltage (Uimp) Input Circuit 6 kV, Output Circuit 4 kV
Rated Insulation Voltage (Ui) Input Circuit / Output Circuit 600 V, Output Circuit 1 / Output Circuit 2 300 V
Degree of Protection Housing IP50, Terminals IP20
Overvoltage Category III
Pollution Degree 3
Short-Circuit Protective Devices Output Circuit NC - F Type Fuses 6 A, Output Circuit NO - F Type Fuses 10 A
Electrical Durability AC-12 100000 cycle
Mechanical Durability Nr. Operations 30000000 cycle
Connecting Capacity Flexible with Ferrule 1x 0.5 ... 2.5 mm², Flexible with Ferrule 2x 0.5 ... 1.5 mm², Flexible with Insulated Ferrule 1x 0.5 ... 2.5 mm², Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm², Flexible 1x 0.5 ... 2.5 mm², Flexible 2x 0.5 ... 1.5 mm², Rigid 1x 0.5 ... 4 mm², Rigid 2x 0.5 ... 2.5 mm²
Tightening Torque 0.6 ... 0.8 N·m
Wire Stripping Length 8 mm
Recommended Screw Driver 0.8 x 4, 4.5, Pozidriv 1
Mounting Position 1 ... 6
Mounting on DIN Rail TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715, TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Standards CAN/CSA C22.2 No.14, IEC/EN 63000, IEC/EN 60255-27, IEC/EN 61000-6-2, IEC/EN 61000-6-3, UL 508

Technical UL/CSA 6

Maximum Operating Voltage UL/CSA Output Circuit 300 V AC
Contact Rating UL/CSA B300
Connecting Capacity UL/CSA Flexible 1x 18-14 AWG, Flexible 2x 18-16 AWG, Rigid 1x 20-12 AWG, Rigid 2x 20-14 AWG
Tightening Torque UL/CSA 7.08 in·lb
Pilot Duty UL/CSA B300
Flammability According to UL94 V-0
Show all 67 specifications ↓ Show less ↑30 more values in Identification, Environmental, Material Compliance, External Classifications and Standards, Logistics.

Identification 10

Part number 1SVR730794R3300
Type designation CM-PVS.41S
Brand ABB
Condition New, factory sealed
Source ABB and its authorised distributors
Warranty Manufacturer warranty
EAN 4016779851848
eCl@ss 27371803
Minimum Order Quantity 1 piece
Customs Tariff Number 85364900

Environmental 2

Ambient Air Temperature Operation -25 ... +60 °C, Storage -40 ... +85 °C
Maximum Operating Altitude Permissible Without Derating 2000 m

Material Compliance 4

REACH Declaration 1SVD981001-4501
RoHS Declaration 1SVD981001-4401
RoHS Information Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA 2CMT2023-006536

External Classifications and Standards 4

ETIM 7 EC001441 - Phase monitoring relay
eClass V11.0 : 27371803
UNSPSC 39122332
E-Number (Sweden) 3860584

Logistics 10

Package Level 1 Units box 1 piece
Package Level 1 Width 97 mm
Package Level 1 Depth / Length 30 mm
Package Level 1 Height 109 mm
Package Level 1 Gross Weight 0.164 kg
Package Level 1 EAN 4016779851848
Shipping weight 0.164 kg
Ships from Türkiye
Dispatch 18 Nov
Stock In stock

Source: manufacturer data · Last verified: 30 Oct 2026

Documents

Documents for 1SVR730794R3300

No documents are on file for this part yet.

Ask us for the datasheet
Certifications

Certifications and standards

  • CE
  • RoHS
  • CCC
  • CAN/CSA C22.2 No.14
  • IEC/EN 63000
  • IEC/EN 60255-27
  • IEC/EN 61000-6-2
  • IEC/EN 61000-6-3
  • UL 508
Quick answers

Questions about the CM-PVS.41S

What is the rated current of CM-PVS.41S?

The rated current of CM-PVS.41S is 4 A.

Which supply voltage is CM-PVS.41S rated for?

The rated operational voltage of CM-PVS.41S is 300–500 V AC.

What is the HS code of CM-PVS.41S for customs?

The tariff (HS) code on file for CM-PVS.41S is 85364900.

What is the EAN of CM-PVS.41S?

The EAN (GTIN) of CM-PVS.41S is 4016779851848.

Where does CM-PVS.41S ship from, and how fast?

CM-PVS.41S ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.

Guides

Guides for monitoring relays

All guides for monitoring relays
Reviews

Customer reviews

Series

ABB CM

Brand
ABB
Series
CM
$134.41 In stock · 18 Nov
Quote

Get a Quote

CM-PVS.41S

Genuine parts

Genuine, factory-sealed parts

ABB · 1SVR730794R3300

Every part on Stoklink is new, unused and made by the manufacturer named on the page.

Condition
New and unused, in the manufacturer's factory-sealed packaging.
Sourced from
ABB and its authorised distributors.
Warranty
The manufacturer's warranty applies.
If a part is not genuine
We refund the full amount.

Added to cart Could not add to cart