ABB 1SDA101676R1 - Tmax XT7S M 1250A 4P MCCB, stored-energy mechanism, Ekip Touch Meas.LSI release, 50kA at 400-440V AC, 690V AC rated.
ABB 1SDA101676R1 brings four-pole switching to the Tmax XT7S M 1250 A molded case circuit breaker line, with a spring-charged operating mechanism and an Ekip Touch Measuring LSI release. At 690 V AC it delivers a 50 kA breaking capacity at 400-440 V AC and a 20 kA, 1 s Icw rating.
This four-pole 1250 A unit shares its rating with the three-pole version in the same XT7S M frame - pick the four-pole version only where the neutral must also be switched, since the extra pole adds width (280 mm vs 210 mm) without changing the breaking performance. The stored-energy mechanism's 20,000-cycle mechanical durability makes it the better choice over a plain-lever XT7S where closing operations are frequent.
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
|---|
| Ambient Air Temperature | Operation -40 ... 125 °C |
|---|
| Product Net Width | 280 mm |
|---|---|
| Product Net Height | 268 mm |
| Product Net Depth / Length | 178 mm |
| Product Net Weight | 12.5 kg |
| Part number | 1SDA101676R1 |
|---|---|
| Type designation | XT7S |
| Brand | ABB |
| Condition | New, factory sealed |
| Source | ABB and its authorised distributors |
| Warranty | Manufacturer warranty |
| EAN | 8056221017206 |
| ETIM class | EC000228 |
| eCl@ss | 27370409 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Circuit Breaker Type to be Associated | Power Distribution |
|---|---|
| Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Version | F |
| Current Type | AC |
|---|---|
| Electrical Durability | 3000 cycle, 60 cycles per hour |
| Mechanical Durability | 20000 cycle, 60 cycles per hour |
| Number of Poles | 4P |
| Order Multiple | 1 piece |
| Power Loss | at Rated Operating Conditions per Pole 57 W |
| Rated Current (In) | 1250 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 85 kA, (230 V AC) 85 kA, (240 V AC) 85 kA, (380 V AC) 50 kA, (415 V AC) 50 kA, (440 V AC) 50 kA, (500 V AC) 45 kA, (525 V AC) 45 kA, (690 V AC) 30 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | 20 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 85 kA, (230 V AC) 85 kA, (240 V AC) 85 kA, (380 V AC) 50 kA, (415 V AC) 50 kA, (440 V AC) 50 kA, (500 V AC) 45 kA, (525 V AC) 45 kA, (690 V AC) 30 kA |
| Rated Uninterrupted Current (Iu) | 1250 A |
| Release | Ekip Touch Measuring LSI |
| Release Type | EL |
| Short-Circuit Performance Level | S |
| Standards | IEC60947-2 |
| Sub-type | XT7M |
| Terminal Connection Type | Front |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
|---|---|
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Package Level 1 Units | box 1 piece |
|---|---|
| Package Level 1 Width | 360 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 360 mm |
| Package Level 1 Gross Weight | 14 kg |
| Package Level 1 EAN | 8056221017206 |
| Shipping weight | 12.5 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 02 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of XT7S is 1250 A.
The rated operational voltage of XT7S is 690 V AC.
The tariff (HS) code on file for XT7S is 853620.
The EAN (GTIN) of XT7S is 8056221017206.
XT7S ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
Compare MCCB types including thermal-magnetic, electronic trip, motor protection, current-limiting, and DC-rated units for industrial use. Shop at Stoklink.
Select the right MCCB with our engineer checklist covering IEC 60947-2, sizing, breaking capacity, trip units, and derating for industry. Shop at Stoklink.
IEC 60947-2 defines MCCB ratings Icu, Ics, Icw, utilization categories A and B, and type tests for low-voltage circuit breakers up to 1000V. Shop...