ABB SACE Emax 2 Air Circuit Breaker: Selection, Application and Maintenance Guide
ABB Emax 2 air circuit breaker selection, sizing, trip units, selectivity, and maintenance guide for 630 to 6300 A LV switchgear engineers. Shop at...
ABB SACE Emax 2 E1.2N 1000 Ekip Dip LSI 4p F F air circuit breaker, 1000 A, 66 kA Icu at 400 V AC, fixed front terminals.
The ABB 1SDA071432R1, SACE Emax 2 E1.2N 1000 Ekip Dip LSI 4p F F, is a fixed four-pole air circuit breaker rated 1000 A uninterrupted current (Iu) with a 66 kA ultimate breaking capacity (Icu) at 400 V AC. Front terminals and bolt-type connections allow direct busbar or cable termination without a drawout cradle.
Ekip Dip LSI keeps the short-time delay (S) stage alongside overload (L) and instantaneous (I) protection, and the 50 kA/1 s Icw lets this breaker stay closed through a downstream fault long enough for a smaller breaker to clear first — the reasoning for placing it as a main or sub-main rather than at a final load. At 1000 A it is the higher-current fixed F F option in the E1.2N performance class (66 kA Icu) compared with the 630 A and 800 A versions of the same frame, so pick it when the incoming or bus-tie current exceeds 800 A.
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
|---|
| Product Net Width | 280 mm |
|---|---|
| Product Net Height | 296 mm |
| Product Net Depth / Length | 183 mm |
| Product Net Weight | 16 kg |
| Product Main Type | SACE Emax 2 |
|---|---|
| Product Name | Air Circuit Breaker |
| Product Type | Air Circuit Breaker |
| Version | F |
| Part number | 1SDA071432R1 |
|---|---|
| Type designation | E1.2N |
| Brand | ABB |
| Condition | New, factory sealed |
| Source | ABB and its authorised distributors |
| Warranty | Manufacturer warranty |
| EAN | 8015644752828 |
| ETIM class | EC000228 |
| eCl@ss | 27370409 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Connecting Capacity | 1000 mm² |
|---|---|
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 8000 cycle, Ue = 500 ... 690 V 8000 cycle, 30 cycles per hour |
| Mechanical Durability | 20000 cycle, 60 cycles per hour |
| Neutral Pole Current ([%Iu]) | 100 % |
| Number of Poles | 4P |
| Power Loss | 78 W |
| Rated Current (In) | 1000 A |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 50 kA, (230 V AC) 50 kA, (380 V AC) 50 kA, (400 V AC) 50 kA, (415 V AC) 50 kA, (440 V AC) 50 kA, (500 V AC) 50 kA, (660 V AC) 50 kA, (690 V AC) 50 kA |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100 % |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 50 kA, for 3 s 30 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 66 kA, (415 V AC) 66 kA, (440 V AC) 66 kA, (500 V AC) 50 kA, (525 V AC) 50 kA, (690 V AC) 50 kA |
| Rated Uninterrupted Current (Iu) | 1000 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | M12 |
| Release | Ekip Dip LSI |
| Release Type | EL |
| Short-Circuit Performance Level | N |
| Standards | IEC |
| Sub-type | E1.2 |
| Suitable for IT Networks | Yes, 690V |
| Terminal Connection Type | Front |
| Terminal Type | Bolt |
| Tightening Torque | 45 N·m |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
|---|---|
| UNSPSC | 39121615 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Package Level 1 Units | box 1 piece |
|---|---|
| Package Level 1 Width | 350 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 330 mm |
| Package Level 1 Gross Weight | 18 kg |
| Package Level 1 EAN | 8015644752828 |
| Shipping weight | 16.0 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 02 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of E1.2N is 1000 A.
The rated operational voltage of E1.2N is 690 V AC.
The tariff (HS) code on file for E1.2N is 853620.
The EAN (GTIN) of E1.2N is 8015644752828.
E1.2N ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
ABB Emax 2 air circuit breaker selection, sizing, trip units, selectivity, and maintenance guide for 630 to 6300 A LV switchgear engineers. Shop at...
Select the correct ABB Emax 2 Ekip trip unit with this guide to LI, LSI, LSIG codes, frame sizing, and measurement classes for switchgear....
Compare ABB Emax 2, Schneider MasterPact MTZ, and Siemens 3WL air circuit breakers by ratings, features, IEC 60947 compliance, and price. Shop at Stoklink.