- Home
- ABB
- ABB 1SDA071352R1 E1.2N 630 Ekip Dip LSI 4p F F 66kA Air Circuit Breaker ABB 1SDA071352R1 E1.2N 630 Ekip Dip LSI 4p F F 66kA Air Circuit Breaker
ABB 1SDA071352R1 E1.2N 630 Ekip Dip LSI 4p F F 66kA Air Circuit Breaker
ABB 1SDA071352R1 E1.2N 630 Ekip Dip LSI 4p F F 66kA Air Circuit Breaker
Get Quote
- Description
1SDA071352R1 identifies the ABB SACE Emax 2 E1.2N 630 Ekip Dip LSI 4p F F, a fixed four-pole air circuit breaker rated 630 A uninterrupted current (Iu) with a 66 kA ultimate breaking capacity (Icu) at 400 V AC. The front-terminal, bolt-type connection needs no cradle or racking hardware.
Technical Specifications
| SKU | 1SDA071352R1 |
| Brand | ABB |
| Series | SACE Emax 2 |
| Catalog Designation | E1.2N 630 Ekip Dip LSI 4p F F |
| EAN | 8015644752026 |
| Number of Poles | 4P |
| Neutral Pole Current | 100% of Iu |
| Rated Current (In / Iu) | 630 A |
| Rated Operational Voltage (Ue) | 690 V AC |
| Rated Insulation Voltage (Ui) | 1000 V AC |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV (IEC 60947-2) |
| Rated Ultimate Breaking Capacity (Icu) at 400 V AC | 66 kA |
| Rated Service Breaking Capacity (Ics) at 400 V AC | 50 kA (100% of Icu) |
| Rated Short-Time Withstand Current (Icw) | 50 kA / 1 s, 30 kA / 3 s |
| Release / Trip Unit | Ekip Dip LSI |
| Short-Circuit Performance Level | N |
| Terminal Connection | Front, bolt-type |
| Connecting Capacity | 400 mm² |
| Mounting | Fixed |
| Current Type | AC |
| Suitable for IT Networks | Yes, up to 690 V |
| Power Loss | 31 W |
| Net Dimensions (W x H x D) | 280 x 296 x 183 mm |
| Net Weight | 16 kg |
Selection Notes
With the short-time delay (S) stage active, Ekip Dip LSI and the 50 kA/1 s Icw allow this breaker to stay closed through a downstream fault for selective coordination, the reasoning that favors it over the LI-only 630 A four-pole F F sibling in applications with downstream breakers to coordinate with. The fourth pole carries 100% of Iu for installations needing the neutral switched, and the fixed body is the right call where drawout isolation is not required — the WMP version of this same rating exists for cradle-mounted, isolate-for-maintenance positions.