- Home
- ABB
- ABB 1SCA158220R1001 OTDC500F11 2P 1000V DC 10kA Switch Disconnector ABB 1SCA158220R1001 OTDC500F11 2P 1000V DC 10kA Switch Disconnector
ABB 1SCA158220R1001 OTDC500F11 2P 1000V DC 10kA Switch Disconnector
ABB 1SCA158220R1001 OTDC500F11 2P 1000V DC 10kA Switch Disconnector
Get Quote
- Description
The ABB 1SCA158220R1001 OTDC500F11 is a two-pole DC switch-disconnector rated 500 A at 1000 V DC on the M frame, sized for utility-scale photovoltaic combiner boxes and inverters. It carries a 10 kA short-circuit making capacity (Icm), a 1500 V rated insulation voltage and a 12 kV impulse withstand voltage for base-mounted installation.
Technical Specifications
| SKU | 1SCA158220R1001 |
| Brand | ABB |
| Series | DC Switch-Disconnectors |
| Catalog Designation | OTDC500F11 |
| EAN | 6417019873251 |
| Number of Poles | 2P |
| Rated Operational Voltage | 1000 V DC |
| Rated Operational Current (DC-21B/DC-PV1/DC-PV2) | 500 A |
| Rated Operational Current DC-22B | 400 A |
| Rated Insulation Voltage (Ui) | 1500 V |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV |
| Rated Short-Circuit Making Capacity (Icm) | 10 kA |
| Rated Short-time Withstand Current (Icw) | 10 kA for 1 s |
| Conventional Free-air Thermal Current (Ith) | 500 A at 40 degC |
| Conventional Thermal Current, Fully Enclosed (Ithe) | 500 A |
| Degree of Protection | IP20 (front) |
| Pollution Degree | 3 |
| Mounting Type | Base mounting |
| Terminal Type | Lug terminals |
| Terminal Width | 30 mm |
| Net Dimensions (W x H x D) | 157.5 x 211 x 135 mm |
| Net Weight | 3.5 kg |
Certifications & Standards
- IEC 60947-1
- IEC 60947-3
Selection Notes
The DC-22B mixed resistive/inductive utilization rating is capped at 400 A even though the DC-21B, DC-PV1 and DC-PV2 ratings all reach 500 A, so a project driven by inductive switching duty should size against the lower 400 A figure rather than the headline 500 A. This switch shares the M-frame footprint with the 400 A and 630 A units in the range, keeping combiner box layouts consistent as current scales. At 1000 V DC it fits installations capped at that bus voltage; a 1500 V utility-scale string needs the corresponding higher-voltage variant.