- Home
- ABB
- ABB 1SCA153613R1001 OXB1250E3S3QT 1250A 4P LCD Controller Top Feed Automatic Transfer Switch ABB 1SCA153613R1001 OXB1250E3S3QT 1250A 4P LCD Controller Top Feed Automatic Transfer Switch
ABB 1SCA153613R1001 OXB1250E3S3QT 1250A 4P LCD Controller Top Feed Automatic Transfer Switch
ABB 1SCA153613R1001 OXB1250E3S3QT 1250A 4P LCD Controller Top Feed Automatic Transfer Switch
Get Quote
- Description
1250 A, 4 poles, top-fed supply: the ABB 1SCA153613R1001 (OXB1250E3S3QT) is a TruONE automatic transfer switch for 200-480 V AC systems with independently earthed neutrals. Its Level 3 LCD controller displays source and transition status locally, and the switch is rated for a 65 kA / 0.1 s short-time withstand current with delayed I-O-II transition between sources.
Technical Specifications
| SKU | 1SCA153613R1001 |
| Brand | ABB |
| Series | Automatic Transfer Switches TruONE |
| Catalog Designation | OXB1250E3S3QT |
| EAN | 6417019846392 |
| Number of Poles | 4P |
| Fourth Pole Configuration | Switched, simultaneous function, left and right side mounting |
| Rated Operational Voltage | 200-480 V AC (Main Circuit) |
| Rated Operational Current (AC-31B) | 1250 A (200-415 V AC) |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV |
| Rated Short-time Withstand Current (Icw) | 65 kA for 0.1 s |
| Conventional Free-air Thermal Current (Ith) | 1250 A at 40 degC |
| Rated Frequency | 50-60 Hz |
| Controller Type | Level 3 (LCD display) |
| Transition Type | Delayed (I-O-II) |
| Terminal Position | Supply on top, load on bottom |
| Terminal Type | Bolt |
| Degree of Protection | Front IP20 |
| Pollution Degree | 3 |
| Power Loss | 26 W per pole / 78 W total |
| Dimensions (W x H x D) | 712 x 359 x 212 mm |
| Net Weight | 37.11 kg |
Certifications & Standards
- IEC 60947-6-1
Selection Notes
Because this 1250 A / 4P unit is rated AC-31B only, reserve the AC-32B/AC-33B-rated QB sibling for boards that switch motor loads directly, and use this top-fed (QT) version for standard distribution feeders instead. The Level 3 LCD controller gives local visibility of source and transition status. Switching phase and neutral together (4P) is the reason to pick this frame over the 3-pole equivalent whenever the two sources carry independently earthed neutrals.