- Home
- ABB
- ABB 1SCA152042R1001 OXB200E3X3QB 3P 200A 18kA Automatic Transfer Switch ABB 1SCA152042R1001 OXB200E3X3QB 3P 200A 18kA Automatic Transfer Switch
ABB 1SCA152042R1001 OXB200E3X3QB 3P 200A 18kA Automatic Transfer Switch
ABB 1SCA152042R1001 OXB200E3X3QB 3P 200A 18kA Automatic Transfer Switch
Get Quote
- Description
ABB's OXB200E3X3QB, order code 1SCA152042R1001, is a 3-pole, 200 A TruONE automatic transfer switch with an 18 kA, 0.3 s short-time withstand rating. The Level 3 controller adds an LCD display for on-site parameter review, and the QB arrangement feeds supply cables in at the bottom with the load exiting at the top.
Technical Specifications
| SKU | 1SCA152042R1001 |
| Brand | ABB |
| Series | Automatic Transfer Switches TruONE |
| Catalog Designation | OXB200E3X3QB |
| EAN | 6417019827629 |
| Number of Poles | 3P |
| Rated Operational Voltage | 200-480 V AC (main circuit) |
| Rated Operational Current AC-31B (Ie) | 200 A at 200-415 V AC |
| Rated Operational Current AC-32B (Ie) | 200 A at 200-415 V AC |
| Rated Operational Current AC-33B (Ie) | 200 A at 200-415 V AC |
| Conventional Free-air Thermal Current (Ith) | 200 A at 40 degC |
| Rated Short-time Withstand Current (Icw) | 18 kA for 0.3 s |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Frequency | 50-60 Hz |
| Transition Type | Delayed (I-O-II) |
| Controller Type | Level 3 (LCD) |
| Line Terminal Position | Supply bottom, load top |
| Terminal Type | Bolt |
| Handle Type | Direct Mount |
| Degree of Protection | IP20 (front) |
| Pollution Degree | 3 |
| Power Loss | 5.8 W per pole, 17.4 W total |
| Dimensions (W x H x D) | 330 x 305 x 183 mm |
| Net Weight | 13.95 kg |
Certifications & Standards
- IEC 60947-6-1
Selection Notes
The OXB200E3X3QB keeps the neutral solid in its 3-pole (X) build, fitting installations where the neutral does not need switching; the 4-pole S variant is the one to specify when it does. Stepping up from the base Level 2 DIP controller, the Level 3 LCD version adds an on-site display for transfer parameter review and event history, without the full touchscreen of Level 4. At 200 A with an 18 kA, 0.3 s short-time withstand, it is sized for sub-distribution rather than a main incomer. QB termination feeds supply cabling in at the bottom.