- ABB 1SCA151250R1001 OTM125F4C20D400C 4P 2.5 kA Icw Automatic Transfer Switch ABB 1SCA151250R1001 OTM125F4C20D400C 4P 2.5 kA Icw Automatic Transfer Switch
ABB 1SCA151250R1001 OTM125F4C20D400C 4P 2.5 kA Icw Automatic Transfer Switch
ABB 1SCA151250R1001 OTM125F4C20D400C 4P 2.5 kA Icw Automatic Transfer Switch
Get Quote
- Description
Rated 125 A across 4 poles, the ABB 1SCA151250R1001 OTM125F4C20D400C is a self-supplied compact automatic transfer switch for 380-415 V AC mains-generator installations. Its type 20D control unit carries fixed operating parameters set at the factory, which keeps commissioning simple where the switching logic does not need field adjustment. It withstands 2.5 kA for 1 s and mounts on a DIN rail or base plate.
Technical Specifications
| SKU | 1SCA151250R1001 |
| Brand | ABB |
| Series | Compact ATS |
| Catalog Designation | OTM125F4C20D400C |
| EAN | 6417019815633 |
| Number of Poles | 4P |
| Controller Type | 20D - Fixed Operating Parameters |
| Transition Type | Open (1-0-2) |
| Rated Operational Voltage, Main Circuit | 380-415 V |
| Motor Operational Voltage | 380-415 V AC |
| Rated Operational Current AC-21A (Ie) | 125 A |
| Rated Operational Current AC-23A (Ie) | 90 A |
| Rated Operational Power AC-23A (Pe) | 45 kW |
| Conventional Free-air Thermal Current (Ith) | 125 A at 40 degC |
| Rated Short-time Withstand Current (Icw) | 2.5 kA for 1 s |
| Rated Insulation Voltage (Ui) | 800 V |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Degree of Protection | IP20 (front) |
| Mounting Type | Base mounting or DIN-rail mounting |
| Terminal Type | Screw terminals |
| Power Loss per Pole | 6.3 W |
| Net Dimensions (W x H x D) | 286 x 103 x 131 mm |
| Net Weight | 2 kg |
Selection Notes
Four switched poles put the 1SCA151250R1001 in the neutral-switching bracket of the 125 A Compact ATS range, needed where the installation isolates neutral between the two sources rather than bonding it on both sides. The 20D controller fixes the voltage thresholds and switching delay at the factory, so there is no field configuration step beyond wiring. Where a project needs those thresholds adjustable on site, the 21D version in the same 125 A, 4-pole frame is the alternative; pick this unit when the standard settings already match the installation.