- Home
- ABB
- ABB 1SCA150003R1001 OXB500E3S4QB 500A 4P 42kA Automatic Transfer Switch ABB 1SCA150003R1001 OXB500E3S4QB 500A 4P 42kA Automatic Transfer Switch
ABB 1SCA150003R1001 OXB500E3S4QB 500A 4P 42kA Automatic Transfer Switch
ABB 1SCA150003R1001 OXB500E3S4QB 500A 4P 42kA Automatic Transfer Switch
Get Quote
- Description
ABB 1SCA150003R1001, catalog code OXB500E3S4QB, is a 500 A TruONE automatic transfer switch built for 4-pole switching between utility and generator supply. The open-style unit runs on 200-480 V AC, uses a Level 4 Touch controller with a delayed I-O-II transition, holds a 42 kA (0.1 s) Icw rating, and has bottom-fed line terminals.
Technical Specifications
| Catalog Designation | OXB500E3S4QB |
| SKU | 1SCA150003R1001 |
| Brand | ABB |
| Series | TruONE Automatic Transfer Switch |
| Rated Operational Voltage | 200-480 V AC |
| Rated Operational Current AC-31B (Ie) | 500 A (200-415 V AC) |
| Rated Operational Current AC-32B (Ie) | 500 A (200-415 V AC) |
| Rated Operational Current AC-33B (Ie) | 500 A (200-415 V AC) |
| Number of Poles | 4P |
| Fourth Pole | Switched, simultaneous function, left and right side position |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV |
| Rated Short-time Withstand Current (Icw, 0.1 s) | 42 kA rms |
| Conventional Free-air Thermal Current (Ith at 40°C) | 500 A |
| Rated Frequency | 50-60 Hz |
| Controller Type | Level 4 (Touch) |
| Transition Type | Delayed (open style, I-O-II operation) |
| Position of Line Terminals | Supplies on Bottom - Load on Top |
| Terminal Type | Bolt |
| Degree of Protection | Front IP20 |
| Pollution Degree | 3 |
| Power Loss | 17.2 W per pole, 51.6 W total |
| Dimensions (W x H x D) | 512 x 313 x 212 mm |
| Net Weight | 21.6 kg |
| EAN | 6417019800516 |
Certifications & Standards
- IEC 60947-6-1
Selection Notes
The switched fourth pole on this 500 A unit breaks the neutral together with the three phases, which TN-S or TT systems with multiple earth points typically need to avoid circulating neutral currents during transfer. The Level 4 controller adds a touchscreen for on-device commissioning, event logging and diagnostics, useful on sites where a dedicated screen replaces laptop-based setup tools. Bottom-fed line terminals (QB) suit panels wired with incoming supply below the switch; pick the QT variant instead when busbars feed in from above. For higher continuous-current duty, the 630 A frame in the same OXB TruONE range covers loads this 500 A unit does not.